Introduction:
This application note will address the wiring set up of a pressure transducer with a
FRENIC-MEGA G2 drive, and parameter settings, to operate under PID control using a
4-20mA feedback signal.
Wiring:
The pressure regulator sensor with a 4-20mA output is to be connected as follows:
1) Connect drive terminal PLC (24VDC) to the sensor's red lead or terminal 1 (+)
2) Connect drive terminal C1 (+) to the sensor's black lead or terminal 2 (-)
3) Connect a wire jumper between drive terminals 11 and CM
Refer to FIGURE 1 below:
FEA-ACDR-AN-205
PID Control with Pressure Transducer
Wiring and Function Code Settings
FRENIC-MEGA G2 series
All versions
None
FEA-ACDR-IN-125
Michael Zeidan
04/01/2025
REV.0
1
FEA-ACDR-AN-205
Data subject to change without notificación

Advertisement

loading
Need help?

Need help?

Do you have a question about the FRENIC-MEGA G2 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Fuji Electric FRENIC-MEGA G2 Series

  • Page 1 APPLICATION NOTE FEA-ACDR-AN-205 PID Control with Pressure Transducer Wiring and Function Code Settings Inverter type FRENIC-MEGA G2 series Software version All versions Required options None Related documentation FEA-ACDR-IN-125 Author Michael Zeidan Date 04/01/2025 Revision REV.0 Introduction: This application note will address the wiring set up of a pressure transducer with a FRENIC-MEGA G2 drive, and parameter settings, to operate under PID control using a 4-20mA feedback signal.
  • Page 2 Function Codes The following table displays the parameters that need to be set in the drive to operate PID control using the keypad to set the command (target) value, and 4-20mA feedback signal. Code Setting Description 1 - for normal operation (typically PID Control Mode used) 2 - for inverse operation...
  • Page 3 Entering the Set value To enter the set value, the setting the PID loop is to maintain, for the above settings you will enter the set value through the keypad. Utilize the LEFT and UP arrow keys to set the value. Pressing LEFT will allow you to move the cursor to the left most digit for faster setting.