Dc powered microprocessor controlled transmitter style 5 enclosure

Advertisement

4-4
Scaled Pulse Output
CAT3-DC-MIL Pulse Output can be configured for turbine raw
frequency or for unit of measure scaled for the least significant digit of
the internal total. A scaling factor of 1, 10 or 100 is available to reduce
or increase the resolution of the pulse output. For example, if the Total
Decimal Point is set to 0000000.0, and the Pulse Scale is 1, then 1
pulse will be output for each tenth (0.1) of a unit of measure. Changing
the Pulse Scale to 10, would result in an output pulse for each 1.0 unit
of measure. The output must be scaled so that the pulse frequency does
not exceed the Pulse Frequency setting (100 Hz. Max) at the maximum
flow rate.
4-5
Communications Interface
An RS232 communications port located under the top plate allows
CAT3-DC-MIL to be remotely configured and trouble-shoot using a
Windows based program.
communication details.
The communication function is available only when CAT3-DC-MIL
device is powered.
Refer to the Appendix B section for