SmartAisle™
Installer/User Guide

Advertisement

loading
Need help?

Need help?

Do you have a question about the SmartAisle SA1E08060MFB0 and is the answer not in the manual?

Questions and answers

Summary of Contents for Vertiv SmartAisle SA1E08060MFB0

  • Page 1 SmartAisle™ Installer/User Guide...
  • Page 2 The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use, or disclosure of it without the written permission of Vertiv is strictly prohibited.
  • Page 3: Table Of Contents

    4 Piping and Refrigeration Connections 4.1 Connecting Pipelines of Indoor Cooling System 4.2 Connecting Pipelines of Outdoor Cooling System 5 Cooling Units and UPS Power Connections 5.1 Indoor Cooling Unit Power Connections 5.2 Connecting Power Supply Cable Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 4 5.5.9 External Protective Devices 5.5.10 Power Cable Connection Steps 5.6 Power Connection of PMC Rack 5.7 Power Connection through the Vertiv™ Liebert® RXA Remote Power Distribution System 5.7.1 Input Power Connections 5.7.2 Output Power Connections 5.8 Power Connection through the Busbar 6 Data Communication Connection 6.1 Connecting Communications Cables of Indoor Cooling Unit...
  • Page 5 7.4 Vertiv™ Liebert® APM2 Option Configurations 7.4.1 Options List 7.5 Options Introduction 7.5.1 Battery Temperature Sensor Kit 7.5.2 Cooling Systems 7.5.3 Setting up the Vertiv™ Liebert® CRV CRD25 and CRD35 7.5.4 Main Functions 7.5.5 Menu Structure and Parameters 7.5.6 Alarm Information 7.5.7 Teamwork Control 7.5.8 Third-Party Condenser Setting...
  • Page 6 10 Maintenance 10.1 Preventive Maintenance Checklist 11 Troubleshooting 11.1 Monitoring Unit Common Issues and Solutions 11.2 Vertiv™ SmartAisle™ Common Issues and Solutions Appendices Appendix A: Technical Support and Contacts Appendix B: Submittal Drawings Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 7: Important Safety Instructions

    This manual contains important safety instructions that should be followed during the installation and maintenance of the Vertiv™ SmartAisle™ Infrastructure Solution. Read this manual thoroughly before attempting to install or operate this cabinet. Retain this manual for the entire service life of the product.
  • Page 8 CAUTION: During installation, charging operations are prohibited. CAUTION: The presence of sharp edges, objects, and bare hooks poses a risk of injury. Use caution when handling any of the aforementioned items. Proprietary and Confidential ©2025 Vertiv Group Corp. 1 Important Safety Instructions...
  • Page 9 Vertiv™ SmartAisle™ Installer/User Guide NOTICE After an alarm sound via the Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit, it is critical to determine and treat the cause quickly to avoid further system damage. NOTICE The unit control must be used exclusively for its intended purpose. This product is tailored for industrial, commercial, or other professional applications such as manufacturing, electrical, and instrumentation setups.
  • Page 10 Vertiv™ SmartAisle™ Installer/User Guide This page intentionally left blank Proprietary and Confidential ©2025 Vertiv Group Corp. 1 Important Safety Instructions...
  • Page 11: Introduction

    2 Introduction 2.1 Product Overview The Vertiv™ SmartAisle™ is a pre-engineered edge data center complete with power, cooling, and all the critical components required to ensure continuous data center availability. SmartAisle™ is a data center solution integrated with in-row air conditioners, in-row or external UPS.
  • Page 12: System Appearance And Components

    Vertiv™ SmartAisle™ Installer/User Guide 2.3 System Appearance and Components The Figure 2.1 below provides an overview of the Vertiv™ SmartAisle™ solution. Based on your system configuration, the number of server rack cabinets may vary. Figure 2.1 Full Dimensional Solution View...
  • Page 13 Item Description Camera - Network Video Recorder (NVR) Monitor and control system RDU501 with embedded expansion card RDU501-8COM Network switch with 24 Power Over Ethernet (POE) ports 10/100/1000 Mbps Blanking panel 2 Introduction Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 14 Vertiv™ SmartAisle™ Installer/User Guide Figure 2.3 Server Rack Figure 2.4 UPS Overview Proprietary and Confidential ©2025 Vertiv Group Corp. 2 Introduction...
  • Page 15 Vertiv™ SmartAisle™ Installer/User Guide Figure 2.5 CRD Overview Item Description Top panel Human Machine Interface (HMI) display Front door Caster Leveling foot Side panel 2 Introduction Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 16 Vertiv™ SmartAisle™ Installer/User Guide Figure 2.6 Vertiv™ Liebert® RXA Overview Proprietary and Confidential ©2025 Vertiv Group Corp. 2 Introduction...
  • Page 17: Model Nomenclature

    . Table 2.1 below attributes a variable to each digit in the model number. The number can then be used to reference Table 2.2 on the next page for an explanation of what each individual character represents. Table 2.1 Nomenclature Model Number Digit Variable 2 Introduction Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 18: Technical Specifications

    Table 2.3 SmartAisle™ Specifications Model SA1E08060MFB0 SA1E08090MFB0 SA1E11120MFB0 SA1E11175HFB0 General Description Designed IT load (kVA) Number of IT racks Average IT load per rack 7.40 11.04 10.90 15.90 (240 V) Proprietary and Confidential ©2025 Vertiv Group Corp. 2 Introduction...
  • Page 19 Power consumption (W) 55.08 55.08 73.44 73.44 Power distribution box 4 (supplied loose) 6 (supplied loose) How supplied Pre-assembled rPDU model Vertiv™ Geist™ VP4G30A0 rPDU type Metered rPDU capacity (A) rPDU phases 2 Introduction Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 20: Power Management System And Distribution

    149.24 2.5.2 Power Management System and Distribution The power distribution system includes a PDU module that is powered by either Vertiv™ Liebert® APM2 30 to 120 kVA. The power distribution system includes the following parameters and components. Table 2.4 UPS System Specification...
  • Page 21: Cooling System

    -35 to 48 °C ) Dimensions (W x H x D) mm 1562 x 1272 x 830 2362 x 1272 x 830 1562 x 1272 x 830 2362 x 1272 x 830 2 Introduction Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 22: Remote Power Distribution System

    2.6.1 Operating Conditions The installation position of Vertiv™ SmartAisle™ should be placed away from heat sources and places that are prone to sparks and placed to avoid exposure to direct sunlight. There should be no corrosive gases and organic solvents in the equipment room.
  • Page 23: Storage Environment

    Vertiv™ SmartAisle™ Installer/User Guide 2.6.2 Storage Environment Table 2.8 below describes the storage environment of Vertiv™ SmartAisle™. Table 2.8 Storage Environment Item Description Storage environment Indoor, clean (dust free) Ambient humidity 5 % RH to 90 % RH (non-condensing) Ambient temperature -23 °C to +52 °C...
  • Page 24 NOTE: There should be no obstruction within 4000 mm of the condenser air outlet. NOTE: There should be maintenance space with a width of 600 mm on the front, rear, left, and right sides of the condenser. Proprietary and Confidential ©2025 Vertiv Group Corp. 2 Introduction...
  • Page 25: Distance Between Indoor And Outdoor Units

    Maximum: -8 m 2.6.5 Load Bearing In all configuration, Vertiv™ SmartAisle™ maximum weighs about 9.4 tons. See Table 2.3 on page 12 for more information. After user devices are installed, the equipment is heavy. Therefore, the load-bearing capability of the equipment room should be considered before installation.
  • Page 26: Configuration Scheme

    Vertiv™ SmartAisle™ Installer/User Guide 2.7 Configuration Scheme This section shows the typical configuration layout of Vertiv™ SmartAisle™ models. Figure 2.10 Layout of Model Number SA1E08060MFB0 Item Description 1 to 8 Server racks Vertiv™ Liebert® APM2 UPS Battery cabinet Vertiv™ Liebert® RXA...
  • Page 27 Table 2.10 Typical Configuration List of Model Number SA1E08060MFB0 Description of Component Part Number Description of Part Number Quantity Component Vertiv™ DCC containment roof - L5200 AW1200 H2000, consist of: • 1 x DCC roof elements L5200 AW1200 • 1 x RXA filler element 030290008001 •...
  • Page 28 Component Part Number Description of Part Number Quantity Component Vertiv™ Liebert® APM2 60 kVA N+1 120 kVA compact Maint. switch APMZ6011AAAA000 No Int. bat. IP20 CoO China. VB60K1DEAL20000 Battery cabinet -10Y: 40X82 AH TYPE K - 2 wires (ex 75Ah) 10H32479P01 Battery temperature compensation kit.
  • Page 29 Vertiv™ SmartAisle™ Installer/User Guide Figure 2.11 Layout of Model Number SA1E08090MFB0 Item Description 1 to 8 Server racks Vertiv™ Liebert® APM2 UPS Battery cabinet Secondary Vertiv™ RXA Offset 14 to 17 Vertiv™ Liebert® CRD35 2 Introduction Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 30 Table 2.11 Typical Configuration List of Model Number SA1E08090MFB0 Description of Component Part Number Description of Part Number Quantity Component Vertiv™ DCC containment roof - L5800 AW1200 H2000, consist of: • 1x DCC roof elements L5800 AW1200 • 1x RXA Filler element 030290008002 •...
  • Page 31 Component Part Number Description of Part Number Quantity Component Vertiv™ Liebert® APM2 90 kVA N+1 120 kVA compact Maint. switch APMZ9011AAAA000 no Int. bat. IP20 CoO China VB60K1DEAL20000 Battery cabinet -10Y: 40X82AH Type K - 2 wires (ex 75Ah) 10H32479P01 Battery temperature compensation kit.
  • Page 32 • Set of balancing sheet metal • Sealing set • Set Protector brackets Aisle containment Vertiv™ SmartAisle™ sliding door set-M - no Lock, system for server contains racks Mechanical door closing 030290268011 • 2x DCC sliding door AW1200 H2000 •...
  • Page 33 4x Joining section w200 • 2x Set cross cable filler panel 200x200 • 1x Set cross cable filler panel 600x600 Vertiv™ DCM rack ST SP H2000 W800 D1200 011477228001 MLR2500 electronic lock front and rear door 2 pieces. PDU brackets installed. Server rack...
  • Page 34 (Vertiv™ Liebert® GXT3, Vertiv™ Liebert® GXT4, separate battery Vertiv™ Liebert® NXC, Vertiv™ Liebert® EXS, Vertiv™ cabinet Liebert® APM, Vertiv™ Liebert® APS, EXL S1, Vertiv™ Liebert® ITA, Vertiv™ Liebert® ITA2) products. Compatible with Vertiv™ Liebert® SN sensors. Vertiv™ Intellislot interface kit for relay contacts for power products (Vertiv™...
  • Page 35 Item Description 1 to 11 Server racks 13 to 18 Vertiv™ Liebert® CRD35 NOTE: UPS and battery cabinets are placed externally according to space requirements around 3 m from base unit. 2 Introduction Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 36 030290008004 • Set of balancing sheet metal • Sealing set • Set protector brackets Vertiv™ SmartAisle™ sliding door -M - no Lock. Contains Mechanical door closing 030290268011 • 2x DCC sliding door AW1200 H2000 • 2x Mechanical door closing system Cable - Raceway L6600 - 1x W200 / 1xW600 •...
  • Page 37 (Vertiv™ Liebert® GXT3, Vertiv™ Liebert® GXT4, separate battery Vertiv™ Liebert® NXC, Vertiv™ Liebert® EXS, Vertiv™ cabinet Liebert® APM, Vertiv™ Liebert® APS, EXL S1, Vertiv™ Liebert® ITA, Vertiv™ Liebert® ITA2) products. compatible with SN sensors. Vertiv Intellislot Interface kit for relay contacts for power products (Vertiv™...
  • Page 38: Power Management Cabinet

    SmartCam Bullet recommendations) Kit4 • 4x IP cameras, shipped loose to be installed onsite according to customer preferences or Vertiv recommendations. MG05M4B1-26PJ63-3PS6B2A10-S. rPDU, Monitored Unit Level EC, 32A, 230V, 7.3kW, Vertical, (20) Locking IEC VP4G30A0 C13, (6) Locking IEC C19, 3 m power cord with 1P+N+E (IP44), Black Powder Coat.
  • Page 39: Installation

    Vertiv™ SmartAisle™ Installer/User Guide 3 Installation The Vertiv™ SmartAisle™ product is on the heavier side and there is a risk of severe injury if not handled properly. Read all the instructions carefully prior to unpacking, shifting, or installing the unit.
  • Page 40: Installation Precautions

    2. Measure and verify the installation site level prior to installation. 3. Confirm that charging operations are stalled and the installed power is disconnected before installation. 4. For installation of indoor and outdoor air conditioning units, refer to SL-70747 Vertiv™ Liebert® CRV CRD25 and CRD35 User Manual.
  • Page 41 Name of Tools Drawing Electrician knife Cable ties Crimping pliers Insulating gloves Insulated torque wrench Heat shrinkable tube Multimeter Torque screwdriver Clip-on ammeter Insulating Shoes Cutter knife Adjustable spanner Socket wrench Phillips screwdriver 3 Installation Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 42: Installation Steps

    • SL-70642 Vertiv™ Liebert® CCD25 and CCD35 User Manual • SL-71076 Vertiv™ Liebert® APM2 30 to 120 kVA UPS User Manual 2. Install the SmartAisle™ roof element. a. Remove the top screw from the boreholes in the cabinet cover. b. Remove the webs in the angle sections with side cutting pliers if necessary. Position angle sections such that the U-shaped opening faces the rear wall of the cabinet with air regulation openings at the ends of the aisles.
  • Page 43 Description Torx screwdriver TX 30 Allen key (10 mm) NOTE: When the Vertiv™ DCM racks are placed in a row, the alignment plates must be inserted between the angle section and rack. Figure 3.2 Alignment Plates and Washer 3. To bridge the height difference between cabinets with a height of 2200 mm and cabinets with a height of 2000 mm, secure angle section using at least two screws.
  • Page 44 Install the sensor onto the air duct. Attach the SensorBOX from the outside to the angle bracket. Figure 3.4 SensorBOX Installation Item Description Screws (quantity: 4) Torx screwdriver TX 25 NOTE: Roof element must be installed before door mounting. Proprietary and Confidential ©2025 Vertiv Group Corp. 3 Installation...
  • Page 45: Sliding Door Installation

    Torx screwdriver TX 30 Screws (quantity: 2) Allen key (10 mm) 2. Attach the side parts to the mounting brackets at a distance of 1220 mm. Do not tighten the screws. 3 Installation Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 46 Screws (quantity: 6) Torx screwdriver TX 30 3. For aisle height of 2000 mm and aisle width of 1500 mm and 1800 mm, attached door bracket. Figure 3.7 Attaching Door Bracket Proprietary and Confidential ©2025 Vertiv Group Corp. 3 Installation...
  • Page 47 Item Description Screws (quantity: 10) Torx screwdriver TX 30 4. Align the frame centrally and tighten the screws on the side parts, as shown in Figure 3.6 on the previous page. 3 Installation Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 48: Retaining Rail

    Figure 3.9 Retaining Rail Item Description Screws (quantity: 6) Install the internal door stoppers in the rail, as shown in Figure 3.10 below. Figure 3.10 Retaining Rail Stopper Item Description Screws (quantity: 4) Proprietary and Confidential ©2025 Vertiv Group Corp. 3 Installation...
  • Page 49: Door Leafs

    Attach the outer door stoppers: Check the alignment of the door stoppers. • Sliding door with electrical door closer: Handles point outwards. • Sliding door with mechanical door closer: Handles point inwards. 3 Installation Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 50: Floor Rails

    Centrally to the longitudinal directions of the bottoms of the doors. • Approximately 8 cm below the closed doors. Attach the bottom guide to the rail. Figure 3.13 Floor Rails Bottom Guide Item Description Screws (quantity: 4) Proprietary and Confidential ©2025 Vertiv Group Corp. 3 Installation...
  • Page 51: Mechanical Door Closer

    2. Install the rails. Figure 3.14 Floor Rail Installation Item Description Screws (quantity: 4) 3.5.5 Mechanical Door Closer Attach the mounting bracket for the cam. Figure 3.15 Mounting Bracket for Cam 3 Installation Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 52 Torx screwdriver TX 30 2. Attach the cam. Figure 3.16 Cam Attachment Item Description Screws (quantity: 4) Torx screwdriver TX 25 3. Attach the counter piece at the end of the door leafs. Proprietary and Confidential ©2025 Vertiv Group Corp. 3 Installation...
  • Page 53 Description Screws (quantity: 6) Torx screwdriver TX 25 4. Attach the counter holder and magnet. Figure 3.18 Attaching Counter Holder and Magnet Item Description Screws (quantity: 8) Torx screwdriver TX 30 3 Installation Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 54 6. Connect the gas pressure springs using an adapter, as shown in Figure 3.20 below. Figure 3.20 Gas Pressure Springs and Adapter 7. Pull the gas pressure springs through the guide bracket and secure them. Proprietary and Confidential ©2025 Vertiv Group Corp. 3 Installation...
  • Page 55 Vertiv™ SmartAisle™ Installer/User Guide Figure 3.21 Securing Gas Pressure Springs 8. Install front gas pressure springs. Figure 3.22 Front Gas Pressure Springs 3 Installation Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 56 Figure 3.23 Cover Trim Installation Item Description Screws (quantity: 4) Torx screwdriver TX 30 Figure 3.24 Securing Cover Trim Item Description Screws (quantity: 8) Torx screwdriver TX 25 Torx screwdriver TX 30 Proprietary and Confidential ©2025 Vertiv Group Corp. 3 Installation...
  • Page 57: Brush Strips

    Depending on the version (left/right), cut the ribs on the support bracket flushly with side cutting pliers as shown in Figure 3.25 below. Figure 3.25 Brush Strips Item Description Screws (quantity: 4) Torx screwdriver TX 30 3 Installation Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 58 Vertiv™ SmartAisle™ Installer/User Guide This page intentionally left blank Proprietary and Confidential ©2025 Vertiv Group Corp. 3 Installation...
  • Page 59: Piping And Refrigeration Connections

    4 Piping and Refrigeration Connections 4.1 Connecting Pipelines of Indoor Cooling System For connections of pipelines of the indoor cooling system, refer to the SL-70747 Vertiv™ Liebert® CRV CRD25 and CRD35 User Manual. 4.2 Connecting Pipelines of Outdoor Cooling System For connections of pipelines of the outdoor cooling system, refer to the SL-70642 Vertiv™...
  • Page 60 Vertiv™ SmartAisle™ Installer/User Guide This page intentionally left blank 4 Piping and Refrigeration Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 61: Cooling Units And Ups Power Connections

    The unit has been fixed to the floor or the adjacent cabinets. • All electrical components are in good condition. • All terminal screws are tight. • The supply voltage and frequency are indicated on the unit. 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 62: Connecting Power Supply Cable

    2 as secondary. When power supply 1 fails, power supply 2 automatically takes over. When power supply 1 restores, it automatically resumes its function as the primary power feed. 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 63 Figure 5.2 Power Supply Cable Connections for CRD35 Item Description Item Description Main circuit breaker Connecting to power supply 2 Connecting to power supply 1 Connecting to condenser 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 64: Outdoor Cooling Unit Power Connections

    The outdoor breaker is located under the electric control box 1. 2. Connect one end of the power cable to the L1, L2, L3, N, and PE terminals of the outdoor breaker. 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 65 3. In the CCD25 condenser, remove two M5 screws from its electric control box and remove the cover. 4. Connect the other end of the power cable to the L1, L2, L3, N, and PE terminals of the circuit breaker. 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 66 Vertiv™ SmartAisle™ Installer/User Guide Figure 5.4 CCD25 — Location of the Electric Control Box in Condenser Item Description Electric control box Figure 5.5 CCD25 — Circuit Breaker in Condenser 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 67 1. Remove four M4 screws from the electric control box cover and remove the cover. 2. Connect one end of the power cable to the L1, L2, L3, N, and PE terminals of the outdoor breaker. 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 68 4. Connect the other end of the power cable to the L1, L2, L3, N, and PE terminals of the circuit breaker. Figure 5.8 CCD35 — Location of the Electric Control Box in Condenser Item Description Electric control box 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 69 Access for condenser fan power supply cable Access for low ambient kit power supply cable (reserved) Access for communications cable Access for condenser power supply cable 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 70: Connecting Power Cable For The Low Ambient Kit

    Power cable of the low ambient kit 3. Connect the cable to the L and N terminals of the terminal block. 4. Fasten the cable gland. 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 71 Vertiv™ SmartAisle™ Installer/User Guide Figure 5.12 CCD25 — Communications Terminal in Condenser Figure 5.13 CCD35 — Communications Terminal in Condenser 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 72: Ups Connections

    Vertiv™ SmartAisle™ Installer/User Guide 5.4 UPS Connections This section describes the electrical installation of the Vertiv™ Liebert® APM2 UPS. After completing the mechanical installation of the UPS, it is necessary to connect the power cable and signal cable of the UPS.
  • Page 73: Recommended Cross Sectional Area (Csa) Of Ups Cable

    Bypass Input 120 kVA 250 A/3P 250 A/4P 250 A/3P WARNING! When the output switch is loaded and closed, it may cause the bypass switch to trip. 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 74: Distance Between The Ups Connection Point And Floor

    WARNING! Failure to ground as required may cause EMI, electric shock, or fire risk. 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 75: External Protective Devices

    The protective devices should provide functions such as the overcurrent protection, short circuit protection, isolation protection and tripping upon backfeed. Refer to SL-71076 Vertiv™ Liebert® APM2 30 to 120 kVA UPS User Manual for more information. 2. Split bypass configuration.
  • Page 76: Power Cable Connection Steps

    The UPS output distribution must be configured with a protective device. The protective device must be different from the input distribution protection switch and able to provide overload protection. Refer SL-71076 Vertiv™ Liebert® APM2 30 to 120 kVA UPS User Manual.
  • Page 77 Vertiv™ SmartAisle™ Installer/User Guide Figure 5.15 Power Cable Connection Terminals 120 kVA Item Description Item Description Split-bypass Common input 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 78 WARNING! Risk of electric shock or fire. Can cause equipment damage, personnel injury or death. The earth grounding cable and neutral line connection must comply with the national electrical code and all the applicable local code. 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 79: Battery Connection

    (BAT-) to (-), (N) to (N). Do not reconnect these links and do not close the battery switch box before authorization to do so by the service engineer. 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 80: Power Connection Of Pmc Rack

    HMI, RDU501, Network Switch, NVR, Beacon, and Power Supply Units (PSUs). NOTE: Model numbers SA1E08060MFB0 and SA1E08090MFB0 have rack PDUs powered by RXA, whereas SA1E11120MFB0 and SA1E11175HFB0 have busbars. 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 81: Power Connection Through The Vertiv™ Liebert® Rxa Remote Power Distribution System

    Power wiring must be installed by licensed electricians. All power wiring must comply with applicable local codes. 5.7.1 Input Power Connections NOTE: Remove the Vertiv™ Liebert® RXA conduit plate prior to punching or drilling to prevent metallic debris from entering the unit.
  • Page 82 3. Remove the bottom terminal covers and connect the input cables to the terminals (tightening torque: max 20 Nm) as per stickers indications, see Figure 5.19 below. 4. Replace the bottom terminal covers. Figure 5.19 Location of Terminals 5 Cooling Units and UPS Power Proprietary and Confidential ©2025 Vertiv Group Corp. Connections...
  • Page 83 NOTE: The main circuit breaker is supplied, installed, and cabled. The other circuit breakers are supplied separately by Vertiv and must be installed at a later stage by the Vertiv technician. NOTE: The other circuit breakers are Miniature Circuit Breaker (MCB) and are hot-swappable and plug-in breakers that can be installed directly in the panelboard inside the RXA.
  • Page 84: Output Power Connections

    The modular system ensures correct power configuration at set-up that can be easily reconfigured as data center needs change. The UPS outfeed is supplied to PDUs through busbar. Refer SL-70927 Vertiv™ PowerBar iMPB Installer/User Guide and SL-71013 Vertiv™ iMPB Submittals Addendum Document for more details.
  • Page 85: Data Communication Connection

    Figure 6.1 Terminal Block Item Description Item Description CRD25 evaporator 41/42 Static pressure sensor CRD35 evaporator 24/51 Water leakage sensor A2/B2 RS485 75/76 Common alarm 37/38 Remote on/off device 6 Data Communication Connection Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 86: Connecting The Communications Cable Between The Evaporator And Condenser

    6.1.3 Connecting the Water Leakage Sensor The water leakage sensor is provided in the accessories bag. To connect the water leakage sensor, connect it to the 51 and 24 terminals. Proprietary and Confidential ©2025 Vertiv Group Corp. 6 Data Communication Connection...
  • Page 87: Connecting The Monitor Device To Unity Card

    Remote temperature sensor 3 Remote temperature sensor 4 Remote temperature sensor 5 Remote temperature sensor 6 Remote temperature sensor 7 Remote temperature sensor 8 Remote temperature sensor 9 Remote temperature sensor 10 6 Data Communication Connection Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 88: Connecting For Teamwork

    Figure 6.3 Location of DIP SW3 and Jumper J27 Item Description Item Description Slider electrical box (electrical box 2) DIP SW3 Liebert® iCOM™ Edge board Jumper J27 EEV Driver board Proprietary and Confidential ©2025 Vertiv Group Corp. 6 Data Communication Connection...
  • Page 89 NOTE: CAN ID 0 is master unit. Teamwork parameters only can be set in master unit and then shared to secondary units. Secondary units upload operation status and alarms to the master unit. 6 Data Communication Connection Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 90: Communication Cable Connections Of Outdoor Cooling Unit

    Figure 6.4 Communications Terminal in Evaporator CRD25 and CRD35 Item Description Item Description CRD25 evaporator 41/42 Static pressure sensor CRD35 evaporator 24/51 Water leakage sensor A2/B2 RS485 75/76 Common alarm 37/38 Remote on/off device Proprietary and Confidential ©2025 Vertiv Group Corp. 6 Data Communication Connection...
  • Page 91: Communication Cable Connections Of Ups

    Velocity protocol communication 6.2.1 SNMP Protocol Communication Vertiv's UNITY network management card make the UPS an IOT device. These cards support SNMP protocol that helps to monitor the UPS through network. IRM series sensor can also be connected to these cards to provide environmental monitoring function. When the intelligent equipment generates an alarm, the UNITY card can notifies you by recording the log, sending trap information, and triggering e-mails.
  • Page 92: Vertiv™ Liebert® Rxa Data Communication Connection

    Vertiv™ SmartAisle™ Installer/User Guide 6.4 Vertiv™ Liebert® RXA Data Communication Connection Figure 6.5 Connectivity without Vertiv™ Liebert® DPM Item Description X1 Terminal: MICB Coil (for remote EPO) • Pin 1: +24 V • Pin 2: GND • Pin 3: N/A X2 Terminal: MICB Status •...
  • Page 93: Configuring The Network Settings

    Sequence Number Cabinet Address DIP1 - DIP4 DIP5 - DIP6 THD-PMC 1001 THD-1 0001 THD-2 0010 THD-3 0011 THD-4 0100 THD-5 0101 THD-6 0110 THD-7 0111 THD-8 1000 7 Configuring the Network Settings Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 94 WEB as the environment volume of cabinet 1; the cut data of the temperature and humidity data of cabinet 1 is the same as that displayed on the LCD screen and WEB cabinet 1. There is one-to-one correspondence between temperature and humidity. Proprietary and Confidential ©2025 Vertiv Group Corp. 7 Configuring the Network Settings...
  • Page 95: Power Distribution Unit (Pdu)

    To ensure the accuracy of the PDU monitoring data, the PDU address settings must be completed in according to Table 7.3 on page 91. All Vertiv™ Geist™ Monitored and Switched rPDUs are shipped with the IMD-5M module. The module provides the same features as the IMD-3E, with the addition of an RS-232 serial port via RJ-45.
  • Page 96: Setting The Pdu Ip Address

    Table 7.2 PDU Operation Display Panel (continued) Item Name Description 16 sensors. The optional Vertiv™ A2D Converter can be added to support analog sensing. The optional SN-ADAPTER can be added to support Liebert® Integrated and Modular Sensors. Serial port RS-232 via RJ-45 port.
  • Page 97: Restoring Account Information

    Press and hold the Network Reset button located below the Ethernet Port for 15 seconds. -or- • Press and hold the button in the center of the LED display for 10 seconds. 7 Configuring the Network Settings Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 98: Intelligent Locks

    To set the communication address for intelligent locks on server rack cabinets: The address setting can be done through the intelligent lock debugging program or through the web UI of the Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit. The Table 7.4 below shows the DIP switch numbers (on the back of the lock) and the corresponding communication addresses.
  • Page 99: Communication Address Example

    This helps to prevent over charging of the battery during high ambient temperature. NOTE: Keep one battery temperature sensor and one cross head screwdriver handy before starting the installation. 7 Configuring the Network Settings Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 100 (BCB) box. For the installation and connection of the battery ground fault detector. Seismic Anchor Kit Vertiv™ Liebert® APM2 UPS has an optional seismic anchor kit. It helps to avoid and reduce the damage to UPS caused by earthquake or vibration in the earthquake prone areas.
  • Page 101 2. Use M8 × 25 tapping screws (4 pieces) to install seismic anchor on the front bottom side of the UPS cabinet, and use M12 expansion bolts (3 pieces) to install seismic anchor on the ground, as shown in Figure 7.6 on the next page. 7 Configuring the Network Settings Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 102 CAUTION: It is recommended to use the shielded cables to enhance the Electromagnetic Compatibility (EMC). The appearance of the IS-UNITY-DP card is shown in Figure 7.7 below. Figure 7.7 IS-UNITY-DP Card Proprietary and Confidential ©2025 Vertiv Group Corp. 7 Configuring the Network Settings...
  • Page 103 Reset button Sensor-network ports (SN sensors only) RS-485 port (BACnet/MSTP, Modbus RTU or YDN23. Only one may be used) For further description and installation of the IS-UNITY-DP card, refer to SL-52645 Vertiv™ Liebert® IntelliSlot™ Unity Card User Manual. BCB Cabinet If users wish to choose a battery system with a long backup time, they can choose an external battery cabinet, which can carry more battery modules.
  • Page 104 NOTE: Mark the battery string when configuring the divided BCB cabinet and note that the marked number must be correspond to the battery terminals in the BCB cabinet when connecting the power cables. Figure 7.9 Front Dimension of BCB Cabinet (unit: mm) Proprietary and Confidential ©2025 Vertiv Group Corp. 7 Configuring the Network Settings...
  • Page 105: Parallel Cable

    For the UPS with shorting copper bar of common input configuration, the user should select the shorting copper bar kit to short the mains input and bypass input. 7 Configuring the Network Settings Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 106: Cooling Systems

    Prerequisites Before setting the IP address, complete the following: Connect the computer network port directly to the Vertiv™ Liebert® IntelliSlot™ Unity communications card using a network cable. 2. Set the IP address of the computer's corresponding interface to the same network segment as the default IP of the Vertiv™...
  • Page 107: Setting Up The Vertiv™ Liebert® Crv Crd25 And Crd35

    Vertiv™ SmartAisle™ Installer/User Guide 7.5.3 Setting up the Vertiv™ Liebert® CRV CRD25 and CRD35 HMI Display The HMI display is a 7 inch touchscreen color display. Figure 7.12 HMI Display The indicator (1) is located under the screen. Its colors and indication are described in Table 7.11 below.
  • Page 108: Main Functions

    You can power on or off the unit by pressing and holding the ON/OFF button for three seconds. NOTE: If no password is entered, you can only view the menu settings. Figure 7.13 Entering Password Proprietary and Confidential ©2025 Vertiv Group Corp. 7 Configuring the Network Settings...
  • Page 109 Shows the graphs of average return air temperature, average return air humidity, average supply air Graph button temperature, and average remote temperature. Setting button To set temperature and humidity. 7 Configuring the Network Settings Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 110: Control Mode

    Theoretical supply air humidity calculated according to current data Desired supply air temperature, return air temperature, or remote temperature set by user Supply air temperature, return air temperature, or remote temperature, depending on the control mode Proprietary and Confidential ©2025 Vertiv Group Corp. 7 Configuring the Network Settings...
  • Page 111: Menu Structure And Parameters

    Vertiv™ SmartAisle™ Installer/User Guide 7.5.5 Menu Structure and Parameters For menu structure and parameters, refer SL-70747 Vertiv™ Liebert® CRV CRD25 and CRD35 User Manual. 7.5.6 Alarm Information Press the menu button and choose Alarm Information to check active alarms and historical alarms. Active Alarms show the active alarms and the time they are generated.
  • Page 112: Third-Party Condenser Setting

    -20°C (-4°F). NOTE: This parameter must be set with the unit turned OFF only and it must be set up by Vertiv professional technical support team. For more information and precautions, please confirm with Vertiv technical support team before selecting and installing a third-party condenser in advance.
  • Page 113: Ip Camera

    To configure a static IP address: Open a web browser and enter the default IP address 192.168.0.10. 2. Enter your username and password, then click Login. 3. Click Setup. 7 Configuring the Network Settings Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 114: Configuring The Video Parameters

    4. Adjust the position of the Area boxes either by dragging them directly on the live view or by specifying the coordinates under X-Axis/Y-Axis column. NOTE: An OSD of type custom must be set, responsible for the IP camera name not being displayed in the Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit.
  • Page 115 3. From the Onvif tab, enable Onvif by clicking the Enable toggle button. 4. Select Digest/WSSE from the Authentication Type drop-down menu. 5. Select HTTP/HTTPS from the Protocol drop-down menu. 6. Enter the administrator's username and password. 7. Click OK. 7 Configuring the Network Settings Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 116: Formatting A Hard Disk

    3. Select Channel from the Channel drop-down menu. 4. Select Main Stream from the Stream Mode drop-down menu. 5. Click Save. 6. Click Schedule and set the recording time. Proprietary and Confidential ©2025 Vertiv Group Corp. 7 Configuring the Network Settings...
  • Page 117: Navigating The Monitoring Unit Web User Interface

    Web User Interface (UI). For more detailed information and instructions, refer to the SL-71186 Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit User Manual shipped with the unit and located on www.Vertiv.com.
  • Page 118 Vertiv™ SmartAisle™ Installer/User Guide Figure 8.1 Web UI Login Page 2. Enter the default username and password: admin/Vertiv 3. Click LOGIN. After logging into the system for the first time, you must change the default password. To change the default password: The General Scenario page opens and displays the prompt: Modify the default password confirmation interface.
  • Page 119: Home

    Figure 8.2 Home Page Overview Item Description System title Product name Alarm reminder sound settings IT Mgmt events Alarm information Username Logout button System time 8 Navigating the Monitoring Unit Proprietary and Confidential ©2025 Vertiv Group Corp. Web User Interface...
  • Page 120: Device

    Aisle Temperature: The average temperature of the cold and hot aisles in the module. For details about the temperature sensor of the rack in the module, refer to SL-71186 Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit User Manual shipped with the unit and located on www.Vertiv.com.
  • Page 121: Facility Overview

    NOTE: Some device types have specific state diagrams that cannot be removed nor configured. The diagrams can only be updated with state map location information, such as Computer Room Air Conditioning (CRACs), UPSs, and so Figure 8.3 Device Overview Page 8 Navigating the Monitoring Unit Proprietary and Confidential ©2025 Vertiv Group Corp. Web User Interface...
  • Page 122: Sampling

    4. Click on the asterisk in the Favorite on Card column to change the default signal that appears in the device card list, then confirm your selection. 8 Navigating the Monitoring Unit Proprietary and Confidential ©2025 Vertiv Group Corp. Web User Interface...
  • Page 123: Control

    From the Safe Mgmt page, click Door Access Mgmt. The Door Access Mgmt page allows you to configure and view information related to card management, authorization management, historical events, resetting authorization, and remote control capabilities. 8 Navigating the Monitoring Unit Proprietary and Confidential ©2025 Vertiv Group Corp. Web User Interface...
  • Page 124: Card Management

    7. Enter the cardholder's department (optional). 8. Click Save. The access control card appears in the Card Mgmt tab. See Figure 8.5 on the facing page. 8 Navigating the Monitoring Unit Proprietary and Confidential ©2025 Vertiv Group Corp. Web User Interface...
  • Page 125: Authority Management

    NOTE: The maximum number of users for a single operation is 4. The maximum number of locks for a single operation is 100. Figure 8.6 Authorization Management 8 Navigating the Monitoring Unit Proprietary and Confidential ©2025 Vertiv Group Corp. Web User Interface...
  • Page 126: History Events

    Locate the invalid card swiping event in the history log, then select it to be redirected to the Card Mgmt tab where you can add the card. 8 Navigating the Monitoring Unit Proprietary and Confidential ©2025 Vertiv Group Corp. Web User Interface...
  • Page 127: Video Surveillance

    Turn on the video image magnification. Zoom NOTE: A red icon indicates turn on the video image magnification. Zoom Turn off the video image magnification. 8 Navigating the Monitoring Unit Proprietary and Confidential ©2025 Vertiv Group Corp. Web User Interface...
  • Page 128 IP cameras must support both the onvif protocol and the RTSP protocol. Video management supports the latest versions of these browsers: • Google Chrome (recommended) • Microsoft Edge 8 Navigating the Monitoring Unit Proprietary and Confidential ©2025 Vertiv Group Corp. Web User Interface...
  • Page 129: Power Management

    PUE modes. You can also clean up the configuration information on the page. To switch PUE modes: Click the Power Mode or Power Consumption Mode radio button at the top of the screen. 8 Navigating the Monitoring Unit Proprietary and Confidential ©2025 Vertiv Group Corp. Web User Interface...
  • Page 130 2. At the confirmation window, click the CONFIRM button. 3. Click SAVE, then click CONFIRM. Figure 8.8 Power Mode Tab Figure 8.9 System Load Percent Setting Tab 8 Navigating the Monitoring Unit Proprietary and Confidential ©2025 Vertiv Group Corp. Web User Interface...
  • Page 131: Device Options

    7. Enter a new storage cycle (for example: 3600), then click the OK button. All non-zero storage cycles in the device type sampling signal update to the new specified cycle. 8 Navigating the Monitoring Unit Proprietary and Confidential ©2025 Vertiv Group Corp. Web User Interface...
  • Page 132: Alarm Actions

    The PMC and front door of the cabinet are equipped with three colored lights. Refer to Table 8.3 on the facing page for the meaning of each color. 8 Navigating the Monitoring Unit Proprietary and Confidential ©2025 Vertiv Group Corp. Web User Interface...
  • Page 133 To extinguish the front door 3-color light-blue light: Use the rocker switch located on the front panel of the PMC to turn off the light. 8 Navigating the Monitoring Unit Proprietary and Confidential ©2025 Vertiv Group Corp. Web User Interface...
  • Page 134: Additional Information

    For more information on the functionality and usage of the Vertiv™ Liebert® RDU501 intelligent monitoring unit, refer SL-71186 Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit User Manual. The user manual is shipped with the unit and can be also located through the interface.
  • Page 135: Operation

    (carry out the operation in accordance with the SL-70747 Vertiv™ Liebert® CRV CRD25 and CRD35 User Manual to preheat the environment of the equipment room, so as to ensure the amount of heat load necessary for commissioning.
  • Page 136: Startup

    NOTE: After the UPS is powered on, manually turn on the inverter on the panel. For the more information about the precautions for the UPS startup process, refer the SL-71076 Vertiv™ Liebert® APM2 30 to 120 kVA UPS User Manual .
  • Page 137 Less than or equal to 100 COM ports Standard category 4 twisted-pair cable Less than or equal to 100 NOTE: Product Certificate: RDU501 satisfies CE allege, UL, CE, FCC and RoHS R10. 9 Operation Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 138: Authorized Startup

    9.3.2 Authorized Startup When logging in to Vertiv™ Liebert® RDU501 for the first time, open the browser and enter the IP address of RDU501 in the address bar (the default IP address of LAN1 is 192.168.0.254 and the default IP address of LAN2 is 192.168.1.254), and open the authorized startup page, as shown in Figure 9.1 below.
  • Page 139 NOTE: For more information about the use methods and precautions for the Liebert® RDU501 monitoring system, refer the SL-71186 Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit User Manual. NOTE: Monitor whether each equipment enters the normal running status on the Vertiv™ Liebert® RDU501 monitoring platform.
  • Page 140: Ac/Ups Commissioning

    For more information about the air conditioner operations and precautions, see the SL-70747 Vertiv™ Liebert® CRV CRD25 and CRD35 User Manual. For more information about the UPS operations and precautions, see the SL-71076 Vertiv™ Liebert® APM2 30 to 120 kVA UPS User Manual.
  • Page 141: Procedures For Completely Powering Down Ups While Maintaining Power To Load

    In a parallel system, perform each step of the procedures in every UPS module before proceeding to the next step. Transfer the UPS from normal mode to maintenance mode. For more information, refer SL-71076 Vertiv™ Liebert® APM2 30 to 120 kVA UPS User Manual.
  • Page 142 Vertiv™ SmartAisle™ Installer/User Guide This page intentionally left blank Proprietary and Confidential ©2025 Vertiv Group Corp. 9 Operation...
  • Page 143: Maintenance

    Vertiv™ SmartAisle™ Installer/User Guide 10 Maintenance This chapter provides a general maintenance checklist for the Vertiv™ SmartAisle™ solution and a maintenance schedule for the cooling system to ensure system operations are being properly maintained. WARNING! Maintenance operations must be done by professional personnel authorized by Vertiv Technical Training.
  • Page 144: Preventive Maintenance Checklist

    Verify Inverter to mains synchronization. • Verify transfer from inverter to bypass and vice-versa. • Verify voltage and phase lockout. Battery • Discharge test (with customer approval) major visit only check all connectors for tightness. Proprietary and Confidential ©2025 Vertiv Group Corp. 10 Maintenance...
  • Page 145 Check the condition of all steam hoses. • Check for leaks. • Check operation of humidifier water pumps (if applicable). Major Visit Only • Check power and current absorption. Fans Section 10 Maintenance Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 146 Check coils for damage and corrosion. • Check condensate drain from evaporator coil. Major Visit Only • Set, adjust and tighten the functional elements. • Monitor suction, head and discharge pressure. Proprietary and Confidential ©2025 Vertiv Group Corp. 10 Maintenance...
  • Page 147 Output Peak Current – as required • Output voltage Cleaning/Air Flow Annually • Check air flow, door/compartment seals. • Clean grids, power module and PCB. • Clean inlet/outlet air flow. Busway • Thermal imaging report 10 Maintenance Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 148 Examine protective device for signs of short circuit operation. If a short circuit has occurred on the equipment connected to the Tap-Off Module, check operation of device and the integrity of the device. Proprietary and Confidential ©2025 Vertiv Group Corp. 10 Maintenance...
  • Page 149 Check all air intake and extract fans are operational with no visible debris on guards. • Check fan fault circuit is operational and confirm fan fault alarm is generated. • Check all door latches are secured. • Check no active alarms on HMI or EPMS. 10 Maintenance Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 150 Vertiv™ SmartAisle™ Installer/User Guide This page intentionally left blank Proprietary and Confidential ©2025 Vertiv Group Corp. 10 Maintenance...
  • Page 151: Troubleshooting

    For troubleshooting the Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit, refer to the Table 11.1 below for common issues, causes, and solutions. If your specific issue is not addressed in the Table 11.1 below, refer to the SL-71186 Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit User Manual shipped with the unit and located on www.Vertiv.com.
  • Page 152 If the above solutions do not resolve the issue, the server may be rejecting the session request from the monitoring unit. Contact Vertiv Technical Support for additional assistance. Figure 11.1 Access Card Troubleshooting Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 153: Vertiv™ Smartaisle™ Common Issues And Solutions

    11.2 Vertiv™ SmartAisle™ Common Issues and Solutions For troubleshooting the SmartAisle™ solution, refer to the Table 11.2 below for commons issues, causes, and solutions. If your specific issues are not addressed in the below table, contact Vertiv Technical Support. Table 11.2 SmartAisle™ Troubleshooting...
  • Page 154 Check that the L1 of the fan speed controller is on with L Outdoor fan operates at full speed at low pressure alarm. and that the connection between the condensation outdoor ambient temperatures. pressure sensor and the fan speed controller is loose. Proprietary and Confidential ©2025 Vertiv Group Corp. 11 Troubleshooting...
  • Page 155: Appendices

    Vertiv Headquarters 505 N Cleveland Ave Westerville, OH 43082 Europe Vertiv International GmbH Victor-von-Bruns-Strasse 21 8212 Neuhausen am Rheinfall Switzerland Asia 7/F, Dah Sing Financial Centre 3108 Gloucester Road, Wanchai Hong Kong Appendices Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 156 Vertiv™ SmartAisle™ Installer/User Guide A.3 Vertiv™ SmartAisle™ Solution Location Europe, Middle East, and Asia Vertiv Romania, Strada Someșului 30, Cluj-Napoca 400145, Romania Contact NOTE: For the countries not listed below, the toll free contact number is +49872327750. Location Main Telephone Number...
  • Page 157 Vertiv™ SmartAisle™ Installer/User Guide Location Main Telephone Number Bahrain 0049872327744 Greece 0080044146622 Denmark 0049872327746 Norway 0049872327747 Finland 0049872327748 Appendices Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 158 Vertiv™ SmartAisle™ Installer/User Guide This page intentionally left blank Proprietary and Confidential ©2025 Vertiv Group Corp. Appendices...
  • Page 159: Appendix B: Submittal Drawings

    Vertiv™ SmartAisle™: 11 x IT Rack, 120 kW, N+1 Solution SA1E11175HFB0 Vertiv™ SmartAisle™: 11 x IT Rack, 175 kW, N+1 Solution NOTE: Refer to the submittal drawing available on vertiv.com for more information. Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 160 Vertiv™ SmartAisle™ Installer/User Guide This page intentionally left blank Proprietary and Confidential ©2025 Vertiv Group Corp.
  • Page 162 Vertiv.com | Vertiv Headquarters, 505 N Cleveland Ave, Westerville, OH 43082 USA ©2025 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp.