The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use, or disclosure of it without the written permission of Vertiv is strictly prohibited.
Page 4
5.5.9 External Protective Devices 5.5.10 Power Cable Connection Steps 5.6 Power Connection of PMC Rack 5.7 Power Connection through the Vertiv™ Liebert® RXA Remote Power Distribution System 5.7.1 Input Power Connections 5.7.2 Output Power Connections 5.8 Power Connection through the Busbar 6 Data Communication Connection 6.1 Connecting Communications Cables of Indoor Cooling Unit...
Page 5
7.4 Vertiv™ Liebert® APM2 Option Configurations 7.4.1 Options List 7.5 Options Introduction 7.5.1 Battery Temperature Sensor Kit 7.5.2 Cooling Systems 7.5.3 Setting up the Vertiv™ Liebert® CRV CRD25 and CRD35 7.5.4 Main Functions 7.5.5 Menu Structure and Parameters 7.5.6 Alarm Information 7.5.7 Teamwork Control 7.5.8 Third-Party Condenser Setting...
This manual contains important safety instructions that should be followed during the installation and maintenance of the Vertiv™ SmartAisle™ Infrastructure Solution. Read this manual thoroughly before attempting to install or operate this cabinet. Retain this manual for the entire service life of the product.
Page 9
Vertiv™ SmartAisle™ Installer/User Guide NOTICE After an alarm sound via the Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit, it is critical to determine and treat the cause quickly to avoid further system damage. NOTICE The unit control must be used exclusively for its intended purpose. This product is tailored for industrial, commercial, or other professional applications such as manufacturing, electrical, and instrumentation setups.
2 Introduction 2.1 Product Overview The Vertiv™ SmartAisle™ is a pre-engineered edge data center complete with power, cooling, and all the critical components required to ensure continuous data center availability. SmartAisle™ is a data center solution integrated with in-row air conditioners, in-row or external UPS.
Vertiv™ SmartAisle™ Installer/User Guide 2.3 System Appearance and Components The Figure 2.1 below provides an overview of the Vertiv™ SmartAisle™ solution. Based on your system configuration, the number of server rack cabinets may vary. Figure 2.1 Full Dimensional Solution View...
149.24 2.5.2 Power Management System and Distribution The power distribution system includes a PDU module that is powered by either Vertiv™ Liebert® APM2 30 to 120 kVA. The power distribution system includes the following parameters and components. Table 2.4 UPS System Specification...
2.6.1 Operating Conditions The installation position of Vertiv™ SmartAisle™ should be placed away from heat sources and places that are prone to sparks and placed to avoid exposure to direct sunlight. There should be no corrosive gases and organic solvents in the equipment room.
Maximum: -8 m 2.6.5 Load Bearing In all configuration, Vertiv™ SmartAisle™ maximum weighs about 9.4 tons. See Table 2.3 on page 12 for more information. After user devices are installed, the equipment is heavy. Therefore, the load-bearing capability of the equipment room should be considered before installation.
Vertiv™ SmartAisle™ Installer/User Guide 2.7 Configuration Scheme This section shows the typical configuration layout of Vertiv™ SmartAisle™ models. Figure 2.10 Layout of Model Number SA1E08060MFB0 Item Description 1 to 8 Server racks Vertiv™ Liebert® APM2 UPS Battery cabinet Vertiv™ Liebert® RXA...
Page 27
Table 2.10 Typical Configuration List of Model Number SA1E08060MFB0 Description of Component Part Number Description of Part Number Quantity Component Vertiv™ DCC containment roof - L5200 AW1200 H2000, consist of: • 1 x DCC roof elements L5200 AW1200 • 1 x RXA filler element 030290008001 •...
Page 28
Component Part Number Description of Part Number Quantity Component Vertiv™ Liebert® APM2 60 kVA N+1 120 kVA compact Maint. switch APMZ6011AAAA000 No Int. bat. IP20 CoO China. VB60K1DEAL20000 Battery cabinet -10Y: 40X82 AH TYPE K - 2 wires (ex 75Ah) 10H32479P01 Battery temperature compensation kit.
Page 30
Table 2.11 Typical Configuration List of Model Number SA1E08090MFB0 Description of Component Part Number Description of Part Number Quantity Component Vertiv™ DCC containment roof - L5800 AW1200 H2000, consist of: • 1x DCC roof elements L5800 AW1200 • 1x RXA Filler element 030290008002 •...
Page 31
Component Part Number Description of Part Number Quantity Component Vertiv™ Liebert® APM2 90 kVA N+1 120 kVA compact Maint. switch APMZ9011AAAA000 no Int. bat. IP20 CoO China VB60K1DEAL20000 Battery cabinet -10Y: 40X82AH Type K - 2 wires (ex 75Ah) 10H32479P01 Battery temperature compensation kit.
Page 32
• Set of balancing sheet metal • Sealing set • Set Protector brackets Aisle containment Vertiv™ SmartAisle™ sliding door set-M - no Lock, system for server contains racks Mechanical door closing 030290268011 • 2x DCC sliding door AW1200 H2000 •...
Page 33
4x Joining section w200 • 2x Set cross cable filler panel 200x200 • 1x Set cross cable filler panel 600x600 Vertiv™ DCM rack ST SP H2000 W800 D1200 011477228001 MLR2500 electronic lock front and rear door 2 pieces. PDU brackets installed. Server rack...
Page 34
(Vertiv™ Liebert® GXT3, Vertiv™ Liebert® GXT4, separate battery Vertiv™ Liebert® NXC, Vertiv™ Liebert® EXS, Vertiv™ cabinet Liebert® APM, Vertiv™ Liebert® APS, EXL S1, Vertiv™ Liebert® ITA, Vertiv™ Liebert® ITA2) products. Compatible with Vertiv™ Liebert® SN sensors. Vertiv™ Intellislot interface kit for relay contacts for power products (Vertiv™...
Page 36
030290008004 • Set of balancing sheet metal • Sealing set • Set protector brackets Vertiv™ SmartAisle™ sliding door -M - no Lock. Contains Mechanical door closing 030290268011 • 2x DCC sliding door AW1200 H2000 • 2x Mechanical door closing system Cable - Raceway L6600 - 1x W200 / 1xW600 •...
Page 37
(Vertiv™ Liebert® GXT3, Vertiv™ Liebert® GXT4, separate battery Vertiv™ Liebert® NXC, Vertiv™ Liebert® EXS, Vertiv™ cabinet Liebert® APM, Vertiv™ Liebert® APS, EXL S1, Vertiv™ Liebert® ITA, Vertiv™ Liebert® ITA2) products. compatible with SN sensors. Vertiv Intellislot Interface kit for relay contacts for power products (Vertiv™...
SmartCam Bullet recommendations) Kit4 • 4x IP cameras, shipped loose to be installed onsite according to customer preferences or Vertiv recommendations. MG05M4B1-26PJ63-3PS6B2A10-S. rPDU, Monitored Unit Level EC, 32A, 230V, 7.3kW, Vertical, (20) Locking IEC VP4G30A0 C13, (6) Locking IEC C19, 3 m power cord with 1P+N+E (IP44), Black Powder Coat.
Vertiv™ SmartAisle™ Installer/User Guide 3 Installation The Vertiv™ SmartAisle™ product is on the heavier side and there is a risk of severe injury if not handled properly. Read all the instructions carefully prior to unpacking, shifting, or installing the unit.
2. Measure and verify the installation site level prior to installation. 3. Confirm that charging operations are stalled and the installed power is disconnected before installation. 4. For installation of indoor and outdoor air conditioning units, refer to SL-70747 Vertiv™ Liebert® CRV CRD25 and CRD35 User Manual.
• SL-70642 Vertiv™ Liebert® CCD25 and CCD35 User Manual • SL-71076 Vertiv™ Liebert® APM2 30 to 120 kVA UPS User Manual 2. Install the SmartAisle™ roof element. a. Remove the top screw from the boreholes in the cabinet cover. b. Remove the webs in the angle sections with side cutting pliers if necessary. Position angle sections such that the U-shaped opening faces the rear wall of the cabinet with air regulation openings at the ends of the aisles.
Page 43
Description Torx screwdriver TX 30 Allen key (10 mm) NOTE: When the Vertiv™ DCM racks are placed in a row, the alignment plates must be inserted between the angle section and rack. Figure 3.2 Alignment Plates and Washer 3. To bridge the height difference between cabinets with a height of 2200 mm and cabinets with a height of 2000 mm, secure angle section using at least two screws.
4 Piping and Refrigeration Connections 4.1 Connecting Pipelines of Indoor Cooling System For connections of pipelines of the indoor cooling system, refer to the SL-70747 Vertiv™ Liebert® CRV CRD25 and CRD35 User Manual. 4.2 Connecting Pipelines of Outdoor Cooling System For connections of pipelines of the outdoor cooling system, refer to the SL-70642 Vertiv™...
Vertiv™ SmartAisle™ Installer/User Guide 5.4 UPS Connections This section describes the electrical installation of the Vertiv™ Liebert® APM2 UPS. After completing the mechanical installation of the UPS, it is necessary to connect the power cable and signal cable of the UPS.
The protective devices should provide functions such as the overcurrent protection, short circuit protection, isolation protection and tripping upon backfeed. Refer to SL-71076 Vertiv™ Liebert® APM2 30 to 120 kVA UPS User Manual for more information. 2. Split bypass configuration.
The UPS output distribution must be configured with a protective device. The protective device must be different from the input distribution protection switch and able to provide overload protection. Refer SL-71076 Vertiv™ Liebert® APM2 30 to 120 kVA UPS User Manual.
Power wiring must be installed by licensed electricians. All power wiring must comply with applicable local codes. 5.7.1 Input Power Connections NOTE: Remove the Vertiv™ Liebert® RXA conduit plate prior to punching or drilling to prevent metallic debris from entering the unit.
Page 83
NOTE: The main circuit breaker is supplied, installed, and cabled. The other circuit breakers are supplied separately by Vertiv and must be installed at a later stage by the Vertiv technician. NOTE: The other circuit breakers are Miniature Circuit Breaker (MCB) and are hot-swappable and plug-in breakers that can be installed directly in the panelboard inside the RXA.
The modular system ensures correct power configuration at set-up that can be easily reconfigured as data center needs change. The UPS outfeed is supplied to PDUs through busbar. Refer SL-70927 Vertiv™ PowerBar iMPB Installer/User Guide and SL-71013 Vertiv™ iMPB Submittals Addendum Document for more details.
Velocity protocol communication 6.2.1 SNMP Protocol Communication Vertiv's UNITY network management card make the UPS an IOT device. These cards support SNMP protocol that helps to monitor the UPS through network. IRM series sensor can also be connected to these cards to provide environmental monitoring function. When the intelligent equipment generates an alarm, the UNITY card can notifies you by recording the log, sending trap information, and triggering e-mails.
To ensure the accuracy of the PDU monitoring data, the PDU address settings must be completed in according to Table 7.3 on page 91. All Vertiv™ Geist™ Monitored and Switched rPDUs are shipped with the IMD-5M module. The module provides the same features as the IMD-3E, with the addition of an RS-232 serial port via RJ-45.
Table 7.2 PDU Operation Display Panel (continued) Item Name Description 16 sensors. The optional Vertiv™ A2D Converter can be added to support analog sensing. The optional SN-ADAPTER can be added to support Liebert® Integrated and Modular Sensors. Serial port RS-232 via RJ-45 port.
To set the communication address for intelligent locks on server rack cabinets: The address setting can be done through the intelligent lock debugging program or through the web UI of the Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit. The Table 7.4 below shows the DIP switch numbers (on the back of the lock) and the corresponding communication addresses.
Page 100
(BCB) box. For the installation and connection of the battery ground fault detector. Seismic Anchor Kit Vertiv™ Liebert® APM2 UPS has an optional seismic anchor kit. It helps to avoid and reduce the damage to UPS caused by earthquake or vibration in the earthquake prone areas.
Page 103
Reset button Sensor-network ports (SN sensors only) RS-485 port (BACnet/MSTP, Modbus RTU or YDN23. Only one may be used) For further description and installation of the IS-UNITY-DP card, refer to SL-52645 Vertiv™ Liebert® IntelliSlot™ Unity Card User Manual. BCB Cabinet If users wish to choose a battery system with a long backup time, they can choose an external battery cabinet, which can carry more battery modules.
Prerequisites Before setting the IP address, complete the following: Connect the computer network port directly to the Vertiv™ Liebert® IntelliSlot™ Unity communications card using a network cable. 2. Set the IP address of the computer's corresponding interface to the same network segment as the default IP of the Vertiv™...
Vertiv™ SmartAisle™ Installer/User Guide 7.5.3 Setting up the Vertiv™ Liebert® CRV CRD25 and CRD35 HMI Display The HMI display is a 7 inch touchscreen color display. Figure 7.12 HMI Display The indicator (1) is located under the screen. Its colors and indication are described in Table 7.11 below.
Vertiv™ SmartAisle™ Installer/User Guide 7.5.5 Menu Structure and Parameters For menu structure and parameters, refer SL-70747 Vertiv™ Liebert® CRV CRD25 and CRD35 User Manual. 7.5.6 Alarm Information Press the menu button and choose Alarm Information to check active alarms and historical alarms. Active Alarms show the active alarms and the time they are generated.
-20°C (-4°F). NOTE: This parameter must be set with the unit turned OFF only and it must be set up by Vertiv professional technical support team. For more information and precautions, please confirm with Vertiv technical support team before selecting and installing a third-party condenser in advance.
4. Adjust the position of the Area boxes either by dragging them directly on the live view or by specifying the coordinates under X-Axis/Y-Axis column. NOTE: An OSD of type custom must be set, responsible for the IP camera name not being displayed in the Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit.
Web User Interface (UI). For more detailed information and instructions, refer to the SL-71186 Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit User Manual shipped with the unit and located on www.Vertiv.com.
Page 118
Vertiv™ SmartAisle™ Installer/User Guide Figure 8.1 Web UI Login Page 2. Enter the default username and password: admin/Vertiv 3. Click LOGIN. After logging into the system for the first time, you must change the default password. To change the default password: The General Scenario page opens and displays the prompt: Modify the default password confirmation interface.
Aisle Temperature: The average temperature of the cold and hot aisles in the module. For details about the temperature sensor of the rack in the module, refer to SL-71186 Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit User Manual shipped with the unit and located on www.Vertiv.com.
For more information on the functionality and usage of the Vertiv™ Liebert® RDU501 intelligent monitoring unit, refer SL-71186 Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit User Manual. The user manual is shipped with the unit and can be also located through the interface.
(carry out the operation in accordance with the SL-70747 Vertiv™ Liebert® CRV CRD25 and CRD35 User Manual to preheat the environment of the equipment room, so as to ensure the amount of heat load necessary for commissioning.
NOTE: After the UPS is powered on, manually turn on the inverter on the panel. For the more information about the precautions for the UPS startup process, refer the SL-71076 Vertiv™ Liebert® APM2 30 to 120 kVA UPS User Manual .
9.3.2 Authorized Startup When logging in to Vertiv™ Liebert® RDU501 for the first time, open the browser and enter the IP address of RDU501 in the address bar (the default IP address of LAN1 is 192.168.0.254 and the default IP address of LAN2 is 192.168.1.254), and open the authorized startup page, as shown in Figure 9.1 below.
Page 139
NOTE: For more information about the use methods and precautions for the Liebert® RDU501 monitoring system, refer the SL-71186 Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit User Manual. NOTE: Monitor whether each equipment enters the normal running status on the Vertiv™ Liebert® RDU501 monitoring platform.
For more information about the air conditioner operations and precautions, see the SL-70747 Vertiv™ Liebert® CRV CRD25 and CRD35 User Manual. For more information about the UPS operations and precautions, see the SL-71076 Vertiv™ Liebert® APM2 30 to 120 kVA UPS User Manual.
In a parallel system, perform each step of the procedures in every UPS module before proceeding to the next step. Transfer the UPS from normal mode to maintenance mode. For more information, refer SL-71076 Vertiv™ Liebert® APM2 30 to 120 kVA UPS User Manual.
Vertiv™ SmartAisle™ Installer/User Guide 10 Maintenance This chapter provides a general maintenance checklist for the Vertiv™ SmartAisle™ solution and a maintenance schedule for the cooling system to ensure system operations are being properly maintained. WARNING! Maintenance operations must be done by professional personnel authorized by Vertiv Technical Training.
For troubleshooting the Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit, refer to the Table 11.1 below for common issues, causes, and solutions. If your specific issue is not addressed in the Table 11.1 below, refer to the SL-71186 Vertiv™ Liebert® RDU501 Intelligent Monitoring Unit User Manual shipped with the unit and located on www.Vertiv.com.
11.2 Vertiv™ SmartAisle™ Common Issues and Solutions For troubleshooting the SmartAisle™ solution, refer to the Table 11.2 below for commons issues, causes, and solutions. If your specific issues are not addressed in the below table, contact Vertiv Technical Support. Table 11.2 SmartAisle™ Troubleshooting...
Page 156
Vertiv™ SmartAisle™ Installer/User Guide A.3 Vertiv™ SmartAisle™ Solution Location Europe, Middle East, and Asia Vertiv Romania, Strada Someșului 30, Cluj-Napoca 400145, Romania Contact NOTE: For the countries not listed below, the toll free contact number is +49872327750. Location Main Telephone Number...