Our liability as a manufacturer shall not be affected due to incorrect use of the equipment, lack of or unsuitable servicing or incorrect installation. To ensure continuous improvement in the quality of our devices, ALDES reserves the right to amend any device details published in this document at any time.
11027070 EXHAUSTO V2 REMOTE CONTROL Connected and powered by the unit - remote control connection (X4) 11023386 ALDES CONNECT BOX Connected and powered by the unit - USB connection (X5) 2-speed remote control 11026011 Connected and powered by the unit - Ibus connection (X6)
The product serial number can be found: - on the box - on the product (located under the electronic board case near the terminal block) - via Aldes Configurator and in the remote control Information menu > Product ID 4. INSTALLATION INSTRUCTIONS 4.1. Transport/Unpacking On receipt of the product, verify its condition and record any comments for the attention of the delivery company on the delivery slip.
INSTALLATION INSTRUCTIONS 4.4. Air connections The unit is designed with 4 Ø 160 mm connectors. Aldes recommends the use of Aldes Algaine Alu soundproofed and insulated flexible ducts. 300 mm x 300 mm min. 300 mm x 300 mm min.
4.7. Electrical connections The unit is supplied pre-wired with a 1.7 m cable. Aldes recommends that the product (or its socket) has its own circuit breaker on the dweling's electrical panel. The wiring diagram describes the product connections in detail.
INSTALLATION INSTRUCTIONS 5. INSTALLATION The product can be installed on the ceiling or the floor. Caution: The condensate connection must be planned in advance to determine the best position and direction of flow for the product. The fastening anchors must be suitable for the supporting wall and designed to withstand a load of 120 kg. Torx 40 5.1.
The installer must choose the most suitable connection solution for the application and the airflow direction chosen (A or B): Important: if you make a mistake when installing the screw connection, Aldes supplies a foam patch to plug the wrong hole from the outside.
- the Aldes InspirAIR ® remote control, which includes a commissioning assistant for the first start-up. - the Aldes Configurator software (for professionals only) The unit's motors cannot be started until commissioning has been successfully completed. 6.3. Commissioning assistant Menu...
START-UP AND SETTINGS ® 6.4. Menu structure of the InspirAIR remote control The INFORMATION menu can be accessed without a password. It is used to display the unit's key parameters without being able to modify them. It enables the installer to check the unit's settings and operation. The user can easily use it to communicate information remotely to the installer if the unit does not seem to be operating correctly, and to carry out an initial remote diagnosis.
Page 12
(no cut-out of the supply motor allowed). Aldes recommends the "Non PassivHaus" configuration if possible. Allows the user to manually activate the unit's bypass. Aldes recommends not allowing this option, unless the Bypass installation is fitted with geothermal equipment (ground-coupled heat exchanger).
Holding (4x) RS485 Customisable from 1 to 99 16: “Write” register be changed) be changed) be changed) be changed) with Aldes Configurator Use this QR code to find the complete Modbus table for interacting with our product: InspirAIR ® Side...
INSPIRAIR SIDE 300 CLASSIC FILTER KIT EPM10 50% “Particulate” filter (ex-M5) “Dust” filter – Coarse 65% (ex-G4) High-quality filters available as accessories As the experts in indoor air quality, Aldes offers a range of filters with different levels of efficiency Item Designation Filtration level...
INSPIRAIR SIDE 300 VOC Filter ePM10 > 85% / ePM1 50% *In order to guarantee their lifespan, Aldes includes the filter in question, plus a dust "pre-filter" to be fitted above the main filter to extend its lifespan, in the following references.
0-10V left motor control Light signal (LED) 0-10V right motor control Bypass Pressure sensor (depending on version) Self Right motor power supply Left motor power supply 7.6. List of spare parts Visit the Aldes website https://www.aldes.fr/documentations-services/pieces-de-rechange X7 X8 X9-X12 InspirAIR ® Side...
8.1. General terms and conditions Please refer to the general terms and conditions of sale at www aldes.fr. The system must be installed by a qualified professional in compliance with best practices, the standards in force and the recommendations in our instructions. The system must be used normally and regularly serviced by a specialist.
ERP SHEET 9. ERP SHEET Supplier brand Aldes InspirAIR ® Side 180 Classic Side 180 Classic Designation Side 150 Prima Side 180 Classic ERV DHU References 11027130 11027131 11027132 11027133 Energy class – Average climate Average climate – SEC – Specific energy consumption (kWh/(m...
Page 20
ERP SHEET ® Supplier brand Aldes InspirAIR Designation Side 300 Classic Side 300 Classic DHU Side 300 Classic ERV DHU References 11027134 11027135 11027136 Energy class – Average climate Average climate – SEC – Specific energy consumption (kWh/(m year) -36,46...
Need help?
Do you have a question about the InspirAIR Side 150 Prima and is the answer not in the manual?
Questions and answers