AIR CONDITIONER (MULTI TYPE)
Installation data
(Table, Graph)
Outdoor Unit
Model name:
<Heat Recovery and Heat Pump Compatible Model>
MMY-SUG0801MT8P-E
MMY-SUG1001MT8P-E
MMY-SUG1201MT8P-E
MMY-SUG1401MT8P-E
MMY-SUG1601MT8P-E
MMY-SUG0801MT8JP-E
MMY-SUG1001MT8JP-E
MMY-SUG1201MT8JP-E
MMY-SUG1401MT8JP-E
MMY-SUG1601MT8JP-E
MMY-SUG0801MT8P-A
MMY-SUG1001MT8P-A
MMY-SUG1201MT8P-A
MMY-SUG1401MT8P-A
MMY-SUG1601MT8P-A
Scan QR CODE to access installation and owner's manual on website.
https://www.toshiba-carrier.co.th/manuals/default.aspx
Manual are available in EN/FR/DE/IT/ES/PT/NL/EL/RU/SV/FI/DA/NO/
PL/BG/RO/ET/LV/HR/CS/SK/SL/HU.
MMY-SUG1801MT8P-E
MMY-SUG2001MT8P-E
MMY-SUG2201MT8P-E
MMY-SUG2401MT8P-E
MMY-SUG1801MT8JP-E
MMY-SUG2001MT8JP-E
MMY-SUG2201MT8JP-E
MMY-SUG2401MT8JP-E
MMY-SUG1801MT8P-A
MMY-SUG2001MT8P-A
MMY-SUG2201MT8P-A
MMY-SUG2401MT8P-A
R32
For commercial use
English

Advertisement

loading
Need help?

Need help?

Do you have a question about the MMY-SUG0801MT8P-E and is the answer not in the manual?

Questions and answers

Summary of Contents for Toshiba MMY-SUG0801MT8P-E

  • Page 1 AIR CONDITIONER (MULTI TYPE) For commercial use Installation data (Table, Graph) Outdoor Unit Model name: <Heat Recovery and Heat Pump Compatible Model> MMY-SUG0801MT8P-E MMY-SUG1801MT8P-E MMY-SUG1001MT8P-E MMY-SUG2001MT8P-E MMY-SUG1201MT8P-E MMY-SUG2201MT8P-E MMY-SUG1401MT8P-E MMY-SUG2401MT8P-E MMY-SUG1601MT8P-E MMY-SUG0801MT8JP-E MMY-SUG1801MT8JP-E MMY-SUG1001MT8JP-E MMY-SUG2001MT8JP-E MMY-SUG1201MT8JP-E MMY-SUG2201MT8JP-E MMY-SUG1401MT8JP-E MMY-SUG2401MT8JP-E MMY-SUG1601MT8JP-E...
  • Page 2 [1] [Confirmation of installation space and floor area] • Indoor unit type, room height and fl oor area in which it is installed, and total refrigerant volume determine the necessary safety measures. Be sure to install safety measures as required. •...
  • Page 3 Line A Total system refrigerant [kg] Total system refrigerant [kg] Minimum Ceiling mounted Minimum Ceiling mounted Wall mount and Under ceiling type Wall mount and Under ceiling type fl oor area fl oor area and Duct type and Duct type Room height is Room height is Room height is...
  • Page 4 Line B Total system refrigerant [kg] Total system refrigerant [kg] Minimum Ceiling mounted Minimum Ceiling mounted Wall mount and Under ceiling type Wall mount and Under ceiling type fl oor area and Duct type fl oor area and Duct type Room height is Room height is Room height is...
  • Page 5 [2] [Safety measures] (Installation patterns for each safety device) The table below shows installation example of safety measures for each safety system. Position where Leak Detector and Flow Selector unit, Shut-off Valve unit can be installed is determined by room area, combination, indoor unit type and capacity, etc. For details, refer to [ 3 ] [Leak Detector installation] and [ 4 ] [Safety shut-off valve installation].
  • Page 6 [3] [Leak Detector installation] [Installation positions of leak detectors] Indoor unit Indoor unit ≧ Leak Detector ≧ 10 m ≦ ※ 300 mm 300 mm ≦ ≦ ※ It must be placed within a horizontal distance of 10 meters and on the wall in the room where the indoor unit is installed. However, when it does not enter the fi...
  • Page 7 (The examples for safety measures installations) The location of the Leak Detector varies depending on the safety system and the room. Incorrect Correct Case Install the refrigerant Leak Detector in the same room as the connected indoor unit. FS-S FS-S FS-S FS-S Group setting of indoor...
  • Page 8 [4] [Safety Shut-off valve installation] ○ Setting up the CODE No. [107] to 1 (Pump-down operation) ■ Flow Selector unit Multi-port type (12 ports and 8 ports type) In case that connection pipe length on the downstream side is 180 m. (Connecting pipe length on the downstream side is total length of each port.) Installation Installation...
  • Page 9 ■ Flow Selector unit Multi-port type (12 ports and 8 ports type) □ Room height is 2.2 m or more Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP...
  • Page 10 Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 16 HP 18 HP 20 HP 22 HP 24 HP 28 HP 32 HP 36 HP...
  • Page 11 □ Room height is less than 2.2 m Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP 3 HP...
  • Page 12 Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 16 HP 18 HP 20 HP 22 HP 24 HP 28 HP 32 HP 36 HP...
  • Page 13 ■ Flow Selector unit Multi-port type (4 ports type) □ Room height is 2.2 m or more Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP...
  • Page 14 Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 16 HP 18 HP 20 HP 22 HP 24 HP 25.6 HP 19.9 34.0...
  • Page 15 □ Room height is less than 2.2 m Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP 3 HP...
  • Page 16 Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 16 HP 18 HP 20 HP 22 HP 24 HP 25.6 HP 21.1 11.2...
  • Page 17 ■ Flow Selector unit Single-port type (4 HP and 6.4 HP type) □ Room height is 2.2 m or more Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP...
  • Page 18 □ Room height is less than 2.2 m Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP 3 HP...
  • Page 19 ■ Flow Selector unit Single-port type (10 HP type) □ Room height is 2.2 m or more Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP...
  • Page 20 □ Room height is less than 2.2 m Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP 3 HP...
  • Page 21 ○ Setting up the CODE No. [107] to 1 (Pump-down operation) ■ Shut-off Valve unit (4 HP type) □ In case that connection pipe length on the downstream side is 10 m. Installation Installation not permitted not permitted Installation permitted Installation permitted Minimum floor area A Minimum floor area A...
  • Page 22 □ In case that connection pipe length on the downstream side is 300 m. Installation Installation not permitted not permitted Installation permitted Installation permitted Minimum floor area A Minimum floor area A Room height is 2.2 m or more Room height is less than 2.2 m □...
  • Page 23 ■ Shut-off Valve unit (6.4 HP type) □ In case that connection pipe length on the downstream side is 10 m. Installation Installation not permitted not permitted Installation permitted Installation permitted Minimum floor area A Minimum floor area A Room height is 2.2 m or more Room height is less than 2.2 m □...
  • Page 24 □ In case that connection pipe length on the downstream side is 300 m. Installation Installation not permitted not permitted Installation permitted Installation permitted Minimum floor area A Minimum floor area A Room height is 2.2 m or more Room height is less than 2.2 m □...
  • Page 25 ■ Shut-off Valve unit (24 HP type) □ In case that connection pipe length on the downstream side is 10 m. Installation Installation not permitted not permitted Installation permitted Installation permitted Minimum floor area A Minimum floor area A Room height is 2.2 m or more Room height is less than 2.2 m □...
  • Page 26 □ In case that connection pipe length on the downstream side is 300 m. Installation Installation not permitted not permitted Installation permitted Installation permitted Minimum floor area A Minimum floor area A Room height is 2.2 m or more Room height is less than 2.2 m □...
  • Page 27 ■ Shut-off Valve unit (4 HP and 6.4 HP type) □ Room height is 2.2 m or more Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP...
  • Page 28 □ Room height is less than 2.2 m Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP 3 HP...
  • Page 29 ■ Shut-off Valve unit (24 HP type) □ Room height is 2.2 m or more Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP...
  • Page 30 Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 16 HP 18 HP 20 HP 22 HP 24 HP 28 HP 32 HP 32.4 HP...
  • Page 31 □ Room height is less than 2.2 m Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP 3 HP...
  • Page 32 Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 16 HP 18 HP 20 HP 22 HP 24 HP 28 HP 32 HP 32.4 HP...
  • Page 33 ○ Setting up the CODE No. [107] to 2 (Individual shut-off operation) ■ Flow Selector unit Single-port type (4 HP type) In case that connection pipe length on the downstream side is 10 m. Installation Installation not permitted not permitted Installation permitted Installation permitted Minimum floor area A...
  • Page 34 ■ Flow Selector unit Single-port type (4 HP and 6.4 HP type) □ Room height is 2.2 m or more Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP...
  • Page 35 □ Room height is less than 2.2 m Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP 3 HP...
  • Page 36 ■ Flow Selector unit Single-port type (10 HP type) □ Room height is 2.2 m or more Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP...
  • Page 37 □ Room height is less than 2.2 m Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP 3 HP...
  • Page 38 ■ Shut-off Valve unit (4 HP type) In case that connection pipe length on the downstream side is 10 m. Installation not permitted Installation not permitted Installation permitted Installation permitted Minimum floor area A Minimum floor area A Room height is 2.2 m or more Room height is less than 2.2 m ■...
  • Page 39 ■ Shut-off Valve unit (4 HP and 6.4 HP type) □ Room height is 2.2 m or more Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP...
  • Page 40 □ Room height is less than 2.2 m Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP 3 HP...
  • Page 41 ■ Shut-off Valve unit (24 HP type) □ Room height is 2.2 m or more Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP...
  • Page 42 Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 16 HP 18 HP 20 HP 22 HP 24 HP 28 HP 32 HP 32.4 HP...
  • Page 43 □ Room height is less than 2.2 m Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 0.3 HP 1 HP 2 HP 3 HP...
  • Page 44 Connectable pipe length to the downstream side of the shut-off valve [m] Minimum fl oor area Total capacity of indoor units on the downstream side of the shut-off valve [HP] 16 HP 18 HP 20 HP 22 HP 24 HP 28 HP 32 HP 32.4 HP...
  • Page 45 [7] [Safety measures for Flow Selector and Shut-off Valve Unit] (Installation Example) CODE No. [107] Installation example Case Not required In area (b) or (c), install a Leak Detector using the Leak Detector Interface. In area (c), additionally install mechanical ventilation. FS-S Connect the external output terminal of Leak Detector to mechanical ventilation.
  • Page 46 144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI, AMPHUR MUANGPATHUMTHANI, PATHUMTHANI 12000, THAILAND 1 1 4 0 1 0 1 1 0 1 -3 A...