  • Page 1 12 TON OUTDOOR PORTABLE AIR-COOLED SPOT COOLER ENGINEERING, INSTALLATION AND SERVICE MANUAL OCEANAIRE, Inc. 1731 Wall Street, Suite 100 Mount Prospect, Il 60056 OA-IN-OPAC144-08.2024 (847) 583-0311 oceanaire-inc.com...
  • Page 2 Page 14 Product Warranty FORWARD This manual provides the user with basic details for the installation and operation of the OceanAire OPAC144 Outdoor Portable Air Conditioning unit. It is highly recommended to read and fully understand the instructions outlined within this manual, before operating the OPAC144 unit.
  • Page 3: General Information

    With optional 22KW electric heat, the unit can provide temporary heat as well, allowing for multi-seasonal usage. The OPAC144 is designed to pass through a standard commercial doorway, allowing access to interior building spaces for critical cooling applications. The heavy-gauge steel cabinet is fabricated with an integral welded frame to maintain the integrity of the cabinet when handled by heavy equipment.
  • Page 4: Technical Specifications

    Compressor: Scroll Compressor HP: • Compressor RLA: 17.9 Compressor LRA: Evaporator CFM - High: 4000 Blower Type: OPAC144 FRONT VIEW Twin Forward Curved Fans Evaporator Motor: Two 1-HP each Condenser Fan: Reverse Curved Impeller COND CFM: 6250 COND Watts: 2400...
  • Page 5: General Description

    SHOWN WITH COVER OPEN OPAC144 ELECTRICALS Phase Alarm Main Indicator Power Switch Fan Speed Switch CAM-LOK Power Connections PHASE ALARM LIGHT (ILLUMINATES WHEN OUT OF PHASE) Optional SUPPLY BLOWER CAM-LOK FAN SPEED SWITCH Buss Bar (Guard in place) OPAC144 POWER PANEL...
  • Page 6 RETURN AIR DUCT PANEL 2 x 16-Inch Filter Access Panel Condensate Drain Fitting 3/4” MGHT OPAC144 - SUPPLY & RETURN DUCT PANELS NYLON Knob Filter Replacement Fastener (3) The OPAC144 unit is equipped with three disposable 2-Inch pleated filters. To change the filters:...
  • Page 7 Model Number: Model Number: MODEL: OPAC14434 START-UP GUIDELINES NOTICE - CONNECT ONLY TO POWER SOURCE AS SPECIFIED ON UNIT NAMEPLATE 1. Connect Power Cords to Unit using CAM-LOK Receptacles. Connect GROUND first. Check that all power connections are secure and Connect Supply Power 2.
  • Page 8 Model Number: Model Number: MODEL: OPAC14434 OPAC14434 CONTROLS HEATER OVERLOAD (-AH MODELS) HEATER CONTACTOR (-AH, MODELS) COMPRESSOR CONTACTOR CONDENSER BLOWER RELAY EVAPORATOR BLOWER RELAY (HIGH SPEED) EVAPORATOR BLOWER RELAY (LOW SPEED) HOUR METER PHASE MONITOR TRANSFORMER CIRCUIT BREAKER CIRCUIT BERAKERS (1 AMP) (2@ 1 AMP)
  • Page 9 Model Number: Model Number: MODEL: OPAC14434 OPAC14434 WIRING DIAGRAM...
  • Page 10 Model Number: Model Number: MODEL: OPAC14434 OPAC14434AH WIRING DIAGRAM...
  • Page 11 Powering and Starting the Unit - Follow the Instructions on Page 7 of this manual. 1. Make sure that the power connected to the OPAC144 unit matches the power shown on the unit nameplate, and that the correct voltage is going to all three power leads.
  • Page 12 Model Number: Model Number: MODEL: OPAC14434 OPAC144 Control Sequence - continued Evaporator Fan Speed Switch Located at the Power Panel is the Evaporator Fan Speed Switch. The fan speed can be switched from Low to High, as needed. NOTICE: High Fan Speed is required for ducted SUPPLY AIR, to avoid freeze-ups.
  • Page 13 Model Number: Model Number: MODEL: OPAC14434 OPAC144 Control Sequence - HEAT MODE (-AH Models) Heating Mode (from Left to Right) Phase Monitor GREEN LED - POWER YELLOW LED - Relay is ON Fan Delay GREEN (blinking) - DELAY TIMER GREEN (solid) - Relay is ON...
  • Page 14 Model Number: Model Number: MODEL: OPAC14434 OPAC144 Troubleshooting Guide Start Up Thermostat Display OFF and will not Illuminate Check Incoming Power and Connect. Check Transformer Circuit Breaker, and reset the breaker if necessary Phase Alarm Light Disconnect Power Switch any two incoming...
  • Page 15 Model Number: Model Number: MODEL: OPAC14434 Thermostat works, Not Heating (-AH Models) Check HEATING Circuit Relay, is GREEN LED illuminated? If YES, Check Heater Thermal Overload If YES, Check Evaporator Fan Operation/Fan Pressure Switch If NO, Check the PHASE MONITOR GREEN LED = POWER YELLOW LED = ON No LED YELLOW or GREEN, Check incoming power...
  • Page 16: Limited Warranty

    LIMITED WARRANTY The Manufacturer (OceanAire, Inc.) warrants to the original owner that the Product will be free from defects in material or workmanship for a period not to exceed one (1) year from date of installation. If upon examination by the Manufacturer, the Product is shown to have a defect in material or workmanship during the warranty period, the Manufacturer will repair or replace, at its option, that part of the Product which is shown to be defective.