Dell 5600R OL HV-US 5600W User Manual page 69

Online rack ups 5600w
Hide thumbs Also See for 5600R OL HV-US 5600W:
Table of Contents

Advertisement

Table 16. Typical Alarms and Conditions (continued)
Alarm or Condition
Battery Test Failed
(Alarm 191)
Intermittent Alarm
Service Battery
(Alarm 149)
Continuous Alarm
Utility Not Present
(Alarm 59)
Intermittent Alarm
Bypass Not Available
(Alarm 105)
Input AC Over Voltage
(Alarm 6)
Intermittent Alarm
Input AC Under Voltage
(Alarm 7)
Intermittent Alarm
Input Under/Over Frequency
(Alarm 8)
Intermittent Alarm
Site Wiring Problem
(Alarm 194)
Continuous Alarm
Remote Emergency Power
Off
(Alarm 12)
Continuous Alarm
Output Overload
(Alarm 25)
Continuous Alarm
Possible Cause
A weak battery string was
detected during the last battery
test.
A faulted battery string has
been detected and as a result,
the charger is disabled.
The utility level has fallen
below the Utility Not Present
threshold (typically <25 to
50V).
The utility is outside of the
bypass limits defined in the
UPS.
The utility voltage exceeds the
maximum operating range.
The utility voltage is below the
minimum operating range.
The utility frequency is out of
usable frequency range.
An alarm triggers when the
difference between ground and
neutral voltage is >15V.
The external contacts in the
rear of the UPS are configured
for REPO operation and they
have been activated.
The load level is at or has
exceeded the configurable
threshold limit for a Level 1
Overload condition.
Action
This is a warning notice. Dell recommends
that you replace the batteries soon.
Contact your service representative.
Transfer to battery if supporting load. Power
down if not supporting load.
Check the bypass settings. See "Settings" on
page 42.
The UPS transfers to Battery mode if
supporting load.
The UPS transfers to Battery mode if
supporting load.
The UPS transfers to Battery mode if
supporting load.
Have a qualified electrician correct the wiring
problem. If the UPS is not wired with a neutral
wire, Site Fault should be disabled in the
Settings menu (see page 42).
The UPS de-energizes the load and enters
Standby mode. See "Installing Remote
Emergency Power-off" on page 25 for more
information.
The UPS can support the load indefinitely at
this load level.
The alarm clears when the load drops below
5% of the set point.
Troubleshooting
|
69

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

5600wK812n

Table of Contents