Indoor Sensor - Lennox ZHD036 Installation Instructions Manual

Heat pump packaged units
Table of Contents

Advertisement

Operating Mode
Initializing
Monitoring
Mitigation
(Leak Detected)
Fault / Service
*Solid green interrupted by a blue flash indicates the mitigation process has previously occurred.
Applies to
Red Wink
Individual
Sensor(s)
1
Yes
2
No
3
Yes
4
Yes
5
No
6
No
Operation Mode
Press the Test button to...
Trigger a leak detection response. Verify all
Monitoring
equipment is wired correctly into the RDSC
(after installation).
Reset the RDSC to a normal mode of opera-
Mitigating
tion after a previous leak has been detected
(Leak Detected)
and purged from the HVAC system.
Reset the RDSC after troubleshooting and
resolving a fault condition. If the fault is not
Fault/Service
resolved, the RDSC will enter the Fault mode
again.
RDS SENSORS
Units are equipped with factory-installed RDS Sensors
located on different points on the unit. The RDS sensors
provide the Unit Controller with continuous readings for
leaked refrigerant concentration levels and sensor health
status (Good or Fault). These readings are used to modify
unit operation to disperse the leaked refrigerant and to
remove possible ignition sources. In addition, the Unit
Controller uses these readings to initiate alarms to alert
the operator of a refrigerant leak or faulty sensor(s).
Each sensor must be specifically placed for proper unit
operation and to initiate valid alarms. To identify sensor
locations see TABLE 9. See TABLE 10 for a list of alarms.
ZHD 036, 048, 060
LED Operational Modes / Troubleshooting
LED Status
Flashing green
Solid green*
Flashing blue
Solid blue, interrupted by red flash code
Red LED Diagnostic Codes / Troubleshooting
Issue
RDS Sensor Fault
Replace sensor
Check VFD for alarms, remedy alarms present. If float switch is installed, verify proper
VFD alarm / Drain pan
switch mounting location, depth in pan, unobstructed condensate drain line; correct as
overflow
needed.
Incompatible sensor
Replace sensor
installed
Sensor communication
Check sensor connection. Ensure connection is clean and tight
issue
Check for 24VAC power connected to thermostat R terminal on the RDSC. 24VAC power
R-input not available
should only be provided at A194-R quick connection for the RDSC to function.
Invalid configuration of
Not applicable
sensor count
Test Button Functions
TABLE 6
TABLE 7
TABLE 8
Press
Action
Clear purge-counter if prior mitigation has occured;
Short
test mitigation.
Long
Reset control.
Short
If testing mitigation, end test.
Reevaluate fault condition - if cleared, return to
Short
monitoring, otherwise update indicator.
Long
Reset control.
Model
ZHD036-060
1 sensor
TABLE 10 - RDS Alarms
Alarm
Alarm description
Refrigerant leak sensor fault in
257
the Indoor section (sensor #1)
Refrigerant leak sensor fault in
258
the control panel/compressor
section (sensor #2)
Page 22
Action
None
None
Check coil tubes for leak.
Repair the issue and restart the equipment.
Refer to table for troubleshooting guidance.
Action
TABLE 9
RDS Sensor Figures
Qty.
Type

INDOOR SENSOR

RDS Sensor Location
Indoor compartment
"Control/Compressor
or
Compressor compartment"
Figure
FIGURE 13