Do not connect or disconnect the battery of the product in hazardous locations such as a damp room. Using batteries other than those supplied by CLA-VAL may lead to a risk of explosion and void the product warranty. The battery provided with the product is not rechargeable and must be disposed properly at end of life.
Installation is not recommended for signal quality under -95 dBm. As the cellular network quality may fluctuate strongly across the site, it is recommended to test at different locations. If network quality at the installed location is not sufficient, it may be necessary to relocate the MD35 or extend its antenna with adequate CLA-VAL extension cables.
NETWORK QUALITY BETWEEN -80 dBm and -95 dBm If the signal quality at the valve level is between -80 dBm and -95 dBm, check if the MD35 can be installed closer to the well opening, while maintaining a maximum distance of 3 m to the pressure sensors. If this is not possible, an antenna extension with optional CLA-VAL antenna extension cables might be necessary.
An optional orientable wall-mounted or valve bracket for MD35 is also available. 5.3.3 STRANDARD INSTALLATION The standard installation of the MD35 on the wall should be, as close as possible to the well opening, but not further than 3 m from the pressure sensor(s) connection(s) on the valve. CLA-VAL Europe www.cla-val.ch...
INSERTING THE SIM CARD Insert the SIM card with the golden contacts facing downwards into the card holder. Refer to Figure 2 - Chapter 2 «MD35 Characteristics» and the symbol printed on the MD35 for correct SIM card orientation. The SIM card must be completely inserted into the card holder.
Switch to "Acquisition" mode on your MD35 as indicated in Figure 4 (from "Standby" mode, press the button for 5 seconds). INSTALLATION VALIDATION The simplest and fastest way to verify the successful start of the product is to use the MD35 LED. The LED flashes green every 10 seconds when in "Acquisition" mode. CLA-VAL Europe www.cla-val.ch...
The default password is: MD35_< last 4 digits of the series serial number > We strongly recommend changing the default password at first installation. Note: The network generated by the MD35 has no Internet access. Any error messages about this can be ignored.
Periodic synchronization is recommended. This operation can only be performed if the MD35 is connected to the cellular network (option). If not, go directly to step 8.
Autonomous Modulation Electronic Controller Click on "SYNCHRONIZE NOW" to update your unit's clock immediately. This operation can only be performed if the MD35 is connected to the cellular network (option). If not, go directly to step 8. Check that the time displayed on the clock under the navigation menu is correct. If not, you can manually set the time in "Manually set date and time".
SETTING THE PARAMETERS OF A M-35 The output identified by M-35 is the dedicated output for the CLA-VAL motor. The M-35 motor is a type of electric motor used to modulate a CLA-VAL automatic control valve. Click on the "...
Click "SAVE" to apply the changes. 9.11 VALVEFLOW™ SETTING (OPTION) The ValveFlow allows calculating the flow through a CLA-VAL valve, thanks to inlet pressure, outlet pressure, and valve opening. Configure the ValveFlow by clicking on " ValveFlow ".
Choose the transfer interval and the time when the transfer will start. This interval will determine the frequency of communications of the MD35 and Link2Valves. Please note that a faster interval will have a negative impact on the battery life and generate potential additional data communication costs.
Associate the MD35 unit with your Link2Valves user account. First, enter the email address of your Link2Valves account. If you do not have one, please contact CLA-VAL to get one for free. Then click on "REGISTER NOW" and wait for the message "Success! ".
Page 42
CLA-VAL MD35 Autonomous Modulation Electronic Controller After configuring HTTPS Peering on Link2Valves, the next step is to set up the MD35 devices so they can communicate with each other. To configure Peering on the MD35, follow these steps: Access the Peering submenu from the Settings menu.
Page 43
After selecting the publisher, choose the data refresh interval and set the timeout duration in case no data is available. c. Click "Add" and then click the button to add the channels you wish to subscribe to. By completing these steps, the MD35 devices will be able to communicate effectively via HTTPS Peering. CLA-VAL Europe www.cla-val.ch cla-val@cla-val.ch...
9.18 PRIORITY ON OUTPUTS The MD35 product provides multiple outputs, including the M-35, a digital output, and two solenoid outputs. These outputs can be controlled by various regulation blocs such as control curves 1 to 4, PID 1 to 4, actions, and ValvApps™. When two blocks are simultaneously controlling the same output, a priority list determines which one takes precedence over the other.
Page 46
The LED will blink purple. Do not disconnect the power during this time! When the update is complete, the MD35 will return in "Configuration" mode and the LED will blink blue. After some minutes of inactivity, the MD35 will exit "Configuration" mode and enter “Acquisition” mode.