0. p0010 = 3 is used for the subsequent commissioning of additional drive data sets (creating data sets: see p0010 = 15). p0010 = 29, 39, 49: Only for internal Siemens use! p0015 Macro drive unit / Macro drv unit...
Page 42
Description: Enter the inductance of a filter connected at the power unit output. Dependency: This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the power unit. Refer to: p0230 Note: When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined SIE- MENS filter or to zero.
Page 43
Description: Enters the capacitance of a sine-wave filter connected at the power unit output. Dependency: This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the power unit. Refer to: p0230 Note: The parameter value includes the sum of all of the capacitances of a phase connected in series (phase - ground).
Page 220
When calculating motor, open-loop and closed-loop control parameters (such as for p0340 = 1) parameters associ- ated with a selected Siemens catalog motor are not overwritten. If a catalog motor has not been selected (see p0300), then the following parameters are reset with p3900 > 0 in order to restore the situation that applied when commissioning the drive for the first time: for induction motors p0320, p0352, p0362 ...
Command and Drive Data Sets – Overview Command and Drive Data Sets – Overview 1.3.1 Command Data Sets (CDS) Product: SINAMICS G120C, Version: 4402100, Language: eng, Type: CDS p0700[0...n] Command source selection / Cmd src sel p0840[0...n] BI: ON / OFF (OFF1) / ON / OFF (OFF1) p0844[0...n]...
Motor data identification modulated voltage generation / MotID U_gen mod 1.3.3 Motor Data Sets (MDS) Product: SINAMICS G120C, Version: 4402100, Language: eng, Type: MDS p0300[0...n] Motor type selection / Mot type sel p0301[0...n] Motor code number selection / Mot code No. sel p0304[0...n]...
Connector/Binector (BICO)-Parameters Connector/Binector (BICO)-Parameters 1.4.1 Binector Input Parameters Product: SINAMICS G120C, Version: 4402100, Language: eng, Type: BI p0730 BI: CU signal source for terminal DO 0 / CU S_src DO 0 p0731 BI: CU signal source for terminal DO 1 / CU S_src DO 1 p0782[0...1]...
BI: CAN status word bit 15 / Status word bit 15 1.4.2 Connector Input Parameters Product: SINAMICS G120C, Version: 4402100, Language: eng, Type: CI p0771[0...1] CI: CU analog outputs signal source / CU AO S_src p1044[0...n] CI: Motorized potentiometer setting value / Mop set val p1070[0...n]...
CO: CAN status word / Status word 1.4.5 Connector/Binector Output Parameters Product: SINAMICS G120C, Version: 4402100, Language: eng, Type: CO/BO r0046.0...31 CO/BO: Missing enable sig / Missing enable sig r0050.0...1 CO/BO: Command Data Set CDS effective / CDS effective r0052.0...15...
Page 285
For some parameters the value for the factory setting is calculated during commissioning for they are dependent on Power Module and motor (see Section 1.1.1 "Calculated"). Explanations for the function diagrams Function diagram FP_1020_97_61.vsd - 1020 - Explanation of the symbols (Part 1) SINAMICS G120C 13.12.2010 V4.4...
Page 286
S & H y = x if SET = 1 Axxxxx (not retentively saved at POWER OFF) Monitoring Monitoring Fxxxxx Explanations for the function diagrams Function diagram FP_1021_97_61.vsd - 1021 - Explanation of the symbols (Part 2) SINAMICS G120C 13.12.2010 V4.4...
Page 287
The following applies to I = 1 signal: y = x1 + x2 H(s) = The following applies to I = 0 signal: y = x1 s + 1 fn_n fn_n Explanations for the function diagrams Function diagram FP_1022_97_61.vsd - 1022 - Explanation of the symbols (Part 3) SINAMICS G120C 13.12.2010 V4.4...
Page 288
Terminal 5 (Kl.5) acts as "Jog bit 0". The output of the motorized potentiometer acts as main setpoint for the speed controller. p1070[0] = 1050 Explanations for the function diagrams Function diagram FP_1030_97_61.vsd - 1030 - Handling BICO technology SINAMICS G120C 13.12.2010 V4.4...
Page 294
[[2526] Status word closed-loop control [6630] Torque limit [2530] Status word closed-loop current control [6640] Current-power limit Overviews Function diagram FP_1700_97_05.vsd - 1700 - Vector control, speed control and generation of the torque limits SINAMICS G120C 13.12.2010 V4.4...
Page 295
[6730] Interface to the Power Module for an induction motor (p0300 = 1) [6731] Interface to the Power Module for a synchronous motor (p0300 = 2) Overviews Function diagram FP_1710_97_05.vsd - 1710 - Vector control, current control SINAMICS G120C 13.12.2010 V4.4...
Page 298
CU DI status r0722 Kl.17 Kl.17 Kl.17 p0796.5 r0722 <1> <1> Kl. = Terminal Sampling time of the DI : 2 ms External Interfaces Function diagram FP_2220_97_05.vsd - 2220 - Digital inputs, electrically isolated (DI0 DI5) SINAMICS G120C 13.12.2010 V4.4...
Page 299
CU DI status r0723 Kl.4 AI0- r0722 p0796.11 r0722 <1> Kl. = Terminal Sampling time of the DI : 4 ms External Interfaces Function diagram FP_2223_97_05.vsd - 2223 - Analog inputs as Digital inputs (DI11) SINAMICS G120C 13.12.2010 V4.4...
Page 300
CU S_src DO 1 r0747 p0731 (52.7) 24 V Kl.21 Kl.22 Sampling time of the DO : 2 ms <2> Kl. = Terminal External Interfaces Function diagram FP_2230_97_05.vsd - 2230 - Digital outputs (DO0 DO1) SINAMICS G120C 13.12.2010 V4.4...
Page 301
For p0756 = 2, 3 the units are mA. Sampling time of the AI : 4 ms For p0756 = 0, 1, 4 the units are V. Kl. = Terminal External Interfaces Function diagram FP_9567_97_05.vsd - 9567 - Analog input 0 (AI0) SINAMICS G120C 13.12.2010 V4.4...
Page 302
The input signals are referred to the reference quantities p2000 ... r2004 (100 % = p200x). Sampling time of the AO : 4 ms External Interfaces Function diagram FP_9573_97_05.vsd - 9573 - Analog output 0 (AO0) SINAMICS G120C 13.12.2010 V4.4...
Page 305
Fieldbus t_monit Monitoring functions 0 ... 1999999 [ms] p2040 (100) Cyclic telegrams from the master Fieldbus configuration Field bus baud 4 ... 13 4 ... 13 F01910 "Fieldbus IF: setpoint timeout" p2020 (8) Field bus address No telegrams from the master 0 ...
Page 306
Signal targets for fieldbus STW1 (p0700 = 6) [Function diagram] [Function diagram] Interconnection Signal Meaning Inverted internal control word signal target parameters = ON (pulses can be enabled) STW1.0 p0840[0] = r2090.0 [2501.3] Sequence control 0 = OFF1 (braking with ramp-function generator, then pulse cancellation & ready for switching on) 1 = No OFF2 (enable is possible) STW1.1 p0844[0] = r2090.1...
Page 307
Signal sources for fieldbus ZSW1 (p0700 = 6) Inverted Interconnection [Function diagram] [Function diagram] Signal Meaning signal target <1> parameters internal control word ZSW1.0 p2080[0] = r0899.0 [2503.7] 1 = Ready for switching on Sequence control ZSW1.1 1 = Ready for operation (DC link loaded, pulses inhibited) p2080[1] = r0899.1 [2503.7] Sequence control...
Page 311
A01901 "PROFIBUS: Parameterizing telegram incorrect" Diagnostic parameters <1> The response monitoring time t_An is automatically defined by the configuration tool (e.g. HW Config made by Siemens) within the framework of PROFIBUS configuration. PROFIdrive / PROFIBUS Function diagram FP_2410_97_61.vsd - 2410 -...
Page 312
<4> In order to comply with the PROFIdrive profile, PZD1 must be used as control word 1 (STW1) or status word 1 (ZSW1). p2037 = 2 should be set if STW1 is not transferred with PZD1 as specified in the PROFIdrive profile. PROFIdrive / PROFIBUS Function diagram FP_2420_97_61.vsd - 2420 - Telegrams and Process Data (PZD) SINAMICS G120C DP 13.12.2010 V4.4...
Page 313
<2> Data type according to to the PROFIdrive profile: I16 = Integer16, U16 = Unsigned16. <3> Display parameters for receive data according to [2460]. <4> Only SIEMENS telegram 350 PROFIdrive / PROFIBUS Function diagram FP_2440_97_61.vsd - 2440 - PZD receive signals interconnection SINAMICS G120C DP 13.12.2010...
Page 314
Bit 10 in STW1 must be set to ensure that the drive accepts the process data. <3> Interconnection is not disabled. PROFIdrive / PROFIBUS Function diagram FP_2441_97_61.vsd - 2441 - STW1 control word interconnection (p2038 = 2) SINAMICS G120C DP 13.12.2010 V4.4...
Page 315
Used in telegrams 1, 352. <1> <2> Bit 10 in STW1 must be set to ensure that the drive accepts the process data. PROFIdrive / PROFIBUS Function diagram FP_2442_97_61.vsd - 2442 - STW1 control word interconnection (p2038 = 0) SINAMICS G120C DP 13.12.2010 V4.4...
Page 316
= r2093.13 [2513.2] [8060.1] 0 = External fault 1 (F07860) STW3.14 Reserved STW3.15 Reserved <1> Used in telegrams 350. PROFIdrive / PROFIBUS Function diagram FP_2444_97_05.vsd - 2444 - STW3 control word interconnection (p2038 = 0) SINAMICS G120C DP 13.12.2010 V4.4...
Page 317
[8065] ZSW3 Status word 3 r0053 [2454] <1> Data type according to the PROFIdrive profile: I16 = Integer16, U16 = Unsigned16. PROFIdrive / PROFIBUS Function diagram FP_2450_97_61.vsd - 2450 - PZD send signals interconnection SINAMICS G120C DP 13.12.2010 V4.4...
Page 318
The drive object is ready to accept data. <2> The ZSW1 is generated using the binector-connector converter (BI: p2080[0...15], inversion: p2088[0].0...p2088[0].15) <4> Interconnection is not disabled. PROFIdrive / PROFIBUS Function diagram FP_2451_97_61.vsd - 2451 - ZSW1 status word interconnection (p2038 = 2) SINAMICS G120C DP 13.12.2010 V4.4...
Page 319
The ZSW1 is generated using the binector-connector converter (BI: p2080[0...15], inversion: p2088[0].0...p2088[0].15) <3> The drive is ready to accept data. PROFIdrive / PROFIBUS Function diagram FP_2452_97_61.vsd - 2452 - ZSW1 status word interconnection (p2038 = 0) SINAMICS G120C DP 13.12.2010 V4.4...
Page 320
1 = Techn. contr. out at upper limit [2511.7] [7958.7] ZSW3.12 Reserved ZSW3.13 Reserved Reserved ZSW3.14 ZSW3.15 Reserved <1> Used in telegrams 350. PROFIdrive / PROFIBUS Function diagram FP_2454_97_61.vsd - 2454 - ZSW3 status word interconnection (p2038 = 0) SINAMICS G120C DP 13.12.2010 V4.4...
Page 321
The following applies for temperature values: 100° C -> 100 % = 4000 hex, 0° C -> 0 %. PROFIdrive / PROFIBUS Function diagram FP_2468_97_05.vsd - 2468 - Receive telegram, free interconnection via BICO (p0922 = 999) SINAMICS G120C DP 13.12.2010 V4.4...
Page 322
The following applies for temperature values: 100° C -> 100 % = 4000 hex; 0° C -> 0%. PROFIdrive / PROFIBUS Function diagram FP_2470_97_61.vsd - 2470 - Send telegram, free interconnection via BICO (p0922 = 999) SINAMICS G120C DP 13.12.2010 V4.4...
Page 324
Telegram: up to 4 words or 64 bits. The sum of the various objects must not exceed 8 words. COB-ID: CAN object identification CANopen Function diagram FP_9204_97_68.vsd - 9204 - Receive telegram, free PDO mapping (p8744 = 2) SINAMICS G120C CAN 13.12.2010 V4.4...
Page 325
<2> Telegram: up to 4 words or 64 bits. The sum of the various objects must not exceed 8 words. CANopen Function diagram FP_9206_97_68.vsd - 9206 - Receive telegram, Predefined Connection Set (p8744 = 1) SINAMICS G120C CAN 13.12.2010 V4.4...
Page 326
Telegram: up to 4 words or 64 bits. The sum of the various objects must not exceed 8 words. COB-ID: CAN object identification CANopen Function diagram FP_9208_97_68.vsd - 9208 - Send telegram, free PDO mapping (p8744 = 2) SINAMICS G120C CAN 13.12.2010 V4.4...
Page 327
Telegram: up to 4 words or 64 bits. The sum of the various objects must not exceed 8 words. COB-ID: CAN object identification CANopen Function diagram FP_9210_97_68.vsd - 9210 - Send telegram, Predefined Connection Set (p8744 = 1) SINAMICS G120C CAN 13.12.2010 V4.4...
Page 328
Can be freely connected pxxxx[y] = r2090.15 <1> Depending on the position of the CANopen control word in p8750, the number of the binector to be connected changes. CANopen Function diagram FP_9220_97_68.vsd - 9220 - Control word, CANopen SINAMICS G120C CAN 13.12.2010 V4.4...
Page 329
Status word bit 14 p8786 Freely interconnectable (BI: p8786) Status word bit 15 p8787 Freely interconnectable (BI: p8787) <1> With setpoint channel: connect p2151 with r1119 [8011.3]. CANopen Function diagram FP_9226_97_68.vsd - 9226 - Status word, CANopen SINAMICS G120C CAN 13.12.2010 V4.4...
Page 331
To the brake control [2701.4] PROFIdrive-STW1 [2420]. Only relevant for CDS0. Reserved <3> When the master control is retrieved, predefined by STARTER or AOP30. Internal control/status words Function diagram FP_2501_97_05.vsd - 2501 - Control word, sequence control SINAMICS G120C 13.12.2010 V4.4...
Page 332
From the brake control [2701.8] From the brake control [2701.8] 1 = Command close holding brake r0899.13 Reserved Reserved <1> The drive is ready to accept data. Internal control/status words Function diagram FP_2503_97_05.vsd - 2503 - Status word, sequence control SINAMICS G120C 13.12.2010 V4.4...
Page 333
To the motorized potentiometer [3020.1] Mop lower p1036 [C] To the motorized potentiometer [3020.1] 1 = Motorized potentiometer, lower r1198.14 1 = Bypass ramp-function generator Internal control/status words Function diagram FP_2505_97_05.vsd - 2505 - Control word, setpoint channel SINAMICS G120C 13.12.2010 V4.4...
Page 334
0 = Motor does not run right r2135 [2548.7] ZSW fault/alarm 2 0 = Alarm drive converter overload r2135 r0052.15 1 = No drive converter overload Internal control/status words Function diagram FP_2510_97_05.vsd - 2510 - Status word 1 SINAMICS G120C 13.12.2010 V4.4...
Page 335
1 = Techn. contr. out at lower limit r2349 [7958.7] Tec_ctrl status r0053.11 r2349 1 = Techn. contr. out at upper limit Reserved Reserved Reserved Reserved Internal control/status words Function diagram FP_2511_97_05.vsd - 2511 - Status word 2 SINAMICS G120C 13.12.2010 V4.4...
Page 336
[2505.7] Mop lower p1036 [C] r1198.14 1 = Motorized potentiometer lower Setpoint channel [8560.7] r0836 r0836.0 1 = CDS bit 0 Sequence control Internal control/status words Function diagram FP_2512_97_05.vsd - 2512 - Control word 1 SINAMICS G120C 13.12.2010 V4.4...
Page 337
DC braking control Reserved Reserved Reserved r2138 [2546.7] STW fault/alarm r2138 0 = External fault 1 (F07860) Sequence control Reserved 1 = CDS bit 1 Internal control/status words Function diagram FP_2513_97_05.vsd - 2513 - Control word 2 SINAMICS G120C 13.12.2010 V4.4...
Page 338
1 = Ramp-function generator set r1407.12 1 = Sensorless operation due to a fault r1407.13 Reserved 1 = Torque limit reached (without pre-control) Internal control/status words Function diagram FP_2522_97_05.vsd - 2522 - Status word, speed controller SINAMICS G120C 13.12.2010 V4.4...
Page 339
[6220.8][6320.8] 1 = Vdc_max controller active r0056.14 [6030.6] [6710.2] [6220.8][6320.8] 1 = Vdc_min controller active r0056.15 [6710.2] <1> Only for V/f control Internal control/status words Function diagram FP_2526_97_61.vsd - 2526 - Status word, closed-loop control SINAMICS G120C 13.12.2010 V4.4...
Page 340
Reserved r1408.10 [6730.3] 1 = Speed adaption limitation Reserved r2198 [8012.7] ZSW monitor 2 1 = Motor stalled r2198 r1408.12 Reserved Reserved Reserved Internal control/status words Function diagram FP_2530_97_64.vsd - 2530 - Status word, current control SINAMICS G120C 13.12.2010 V4.4...
Page 341
From extended signals [8020.8] 1 = Load missing r2197.11 r2197.12 From extended signals [8021.8] 1 = |n_act| > n_max (with delay) Reserved Reserved Reserved Internal control/status words Function diagram FP_2534_97_05.vsd - 2534 - Status word, monitoring functions 1 SINAMICS G120C 13.12.2010 V4.4...
Page 342
1 = Motor blocked r2198.6 From torque messages, motor locked/stalled [8012.8] 1 = Motor stalled r2198.7 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Internal control/status words Function diagram FP_2536_97_05.vsd - 2536 - Status word, monitoring functions 2 SINAMICS G120C 13.12.2010 V4.4...
Page 343
1 = Ramp-up/ramp-down completed From speed signals [8011.8] r2199.5 [8012.1] 0 = Ramp-function generator active Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Internal control/status words Function diagram FP_2537_97_05.vsd - 2537 - Status word, monitoring functions 3 SINAMICS G120C 13.12.2010 V4.4...
Page 344
External fault 1 p2106 [C] To fault buffer [8060.1] <1> = External fault 1 (F07860) r2138.13 Reserved Reserved <1> These parameters refer to the Command Data Sets (CDS).. Internal control/status words Function diagram FP_2546_97_05.vsd - 2546 - Control word, faults/alarms SINAMICS G120C 13.12.2010 V4.4...
Page 345
From the thermal monitoring, motor [8016.8] 1 = Alarm motor overtemperature r2135.14 r2135.15 From the thermal monitoring, motor [8016.8] 1 = Alarm, thermal overload, power module Internal control/status words Function diagram FP_2548_97_61.vsd - 2548 - Status word, faults/alarms 1 and 2 SINAMICS G120C 13.12.2010 V4.4...
Page 346
1 = Demagnetizing not completed r0046. r0046. 1 = Brake open missing Reserved r0046.30 1 = Speed controller inhibited 1 = Jog setpoint active r0046.31 Internal control/status words Function diagram FP_2634_97_61.vsd - 2634 - Sequence control - Missing enable signals SINAMICS G120C 13.12.2010 V4.4...
Page 348
If p1215 = 0, 2 -> t = 0 ms. applied. <4> Only if Safety Integrated is active. <10> Start frequency with V/f control: p1351, p1352 [6310.6]; Start torque with vector control: p1475 [6040.3] Braking Control Function diagram FP_2701_97_05.vsd - 2701 - Basic braking control SINAMICS G120C 13.12.2010 V4.4...
Page 350
<1> Comparator, refer to [1021] <2> Analog signal memory, refer to [1021] The target checksum must be equal to the actual checksum. <3> Safety Integrated Function diagram FP_2800_97_63.vsd - 2800 - Basic Functions, Parameter Manager SINAMICS G120C 13.12.2010 V4.4...
Page 351
Cross checking list Diagnostics for STOP F [2810.3] F01600/F30600 "STOP A initiated" SI status P1 r9772 [2804.2] r9772 SI Status P2 r9872 [2804.5] r9872 Safety Integrated Function diagram FP_2802_97_63.vsd - 2802 - Basic Functions, Monitoring functions and faults/alarms SINAMICS G120C 13.12.2010 V4.4...
Page 352
Functions available on Processor 1 und Bit No. Processor 2 1 = STO supported via terminals Reserved <1> 1 = PROFIsafe supported Reserved <1> only PROFIBUS variants Safety Integrated Function diagram FP_2804_97_63.vsd - 2804 - Basic Functions, Status words SINAMICS G120C 13.12.2010 V4.4...
Page 353
Redundant functions in the Processor 1 (P1) and Processor 2 (P2). STO: Safe Torque Off Transistors inhibited for a "0" signal. <3> Safety Integrated Function diagram FP_2810_97_05.vsd - 2810 - Basic Functions, STO: Safe Torque Off SINAMICS G120C 13.12.2010 V4.4...
Page 354
DI COM & F-DI0 Kl.17 Kl.34 DI COM2 Kl.28 SI STO t_debou P2 0.00 ... 100000.00 [μs] p9851 (0.00) F-DI: Fail-safe Digital Input Safety Integrated Function diagram FP_2812_97_63.vsd - 2812 - Basic Functions, F-DI: Fail-safe Digital Input SINAMICS G120C 13.12.2010 V4.4...
Page 358
[2634.8] 1: OFF1 enable missing (r0046.0) <2> If initial rounding-off is active (p1025.2 = 1), the selected ramp-up/ down times are exceeded accordingly. <3> Only effective if p1025.0 = 0. Setpoint channel Function diagram FP_3020_97_05.vsd - 3020 - Motorized potentiometer SINAMICS G120C 13.12.2010 V4.4...
Page 359
<2> =1 if technology controller is activated (p2200 > 0, p2251 = 0). <3> The connection to the source for the main and additional setpoint is estabished automatically via the setting in p1000. Setpoint channel Function diagram FP_3030_97_05.vsd - 3030 - Main/supplementary setpoint, setpoint scaling, jogging SINAMICS G120C 13.12.2010 V4.4...
Page 360
1 = Direction reversal 1 = Inhibit negative direction of 1 = Inhibit positive direction of rotation rotation Setp after limit [1/min] n_set_1 [3030.8] r1114 [3050.1] Setpoint channel Function diagram FP_3040_97_05.vsd - 3040 - Direction limitation and direction reversal SINAMICS G120C 13.12.2010 V4.4...
Page 361
If the drive is not stopped via the input setpoint, but via controlled intervention, the lower hysteresis branch is relevant after a subsequent run-up. Setpoint channel Function diagram FP_3050_97_05.vsd - 3050 - Skip speed bands and speed limitations SINAMICS G120C 13.12.2010 V4.4...
Page 362
<4> With activated Technology controller (p2200 > 0, p2251 = 0) the ramp-function generator is bypassed. <5> Value range and/or factory setting depend on Power Module Setpoint channel Function diagram FP_3070_97_05.vsd - 3070 - Extended ramp-function generator SINAMICS G120C 13.12.2010 V4.4...
Page 364
For p1320 = 0, the voltage boost via p1310 is not effective. p1322 p1326 <2> p1312 is only active at the first acceleration after pulse enable. V/f control Function diagram FP_6300_97_05.vsd - 6300 - V/f characteristic and voltage boost SINAMICS G120C 13.12.2010 V4.4...
Page 365
If p1349 = 0: the limit is 0,95 x f Mot N <= 45 Hz. <2> Activation with r0056.4 = 1 till r0066 >= p1334 and p1216 has expired. 100 % equal r0330 (Rated motor slip) V/f control Function diagram FP_6310_97_05.vsd - 6310 - Resonance damping and slip compensation SINAMICS G120C 13.12.2010 V4.4...
Page 369
1 = Torque limit reached r1407 [2522.7] <1> For p1472 = 0.0 s or 100.0 s, the I component is disabled (integral action time = infinite). Vector control Function diagram FP_6040_97_05.vsd - 6040 - Speed controller SINAMICS G120C 13.12.2010 V4.4...
Page 370
M_max lower eff [Nm] [6640.8] r1539 <1> Acceleration control is inhibited for p1517 = 100 ms. <2> M_set is also influenced by the speed limit controller. Vector control Function diagram FP_6060_97_05.vsd - 6060 - Torque setpoint SINAMICS G120C 13.12.2010 V4.4...
Page 372
Danger: Negative values at <1> represent a minimum torque for the other torque direction and can cause the motor to accelerate uncontrollably. <2> positive values at <2> Vector control Function diagram FP_6630_97_05.vsd - 6630 - Upper/lower torque limit SINAMICS G120C 13.12.2010 V4.4...
Page 373
0.00 ... 100000.00 [kW] p1530 [D] (0.00) <1> <1> Intervention by the Vdc controller. <2> Intervention when the speed limit is exceeded + 2 % n_rated. Vector control Function diagram FP_6640_97_05.vsd - 6640 - Current/power/torque limits SINAMICS G120C 13.12.2010 V4.4...
Page 374
ZSW cl-loop ctrl r0056 [2526.6] r0056 Iq_min [6220.8] [6640.8] M_set total [Nm] Iq_set [Aeff] Interpolator and r0077 r0079 smoothing for voltage limits [6714.1] [6060.8] [6721.1] [6730.1] Vector control Function diagram FP_6710_97_05.vsd - 6710 - Current setpoint filter SINAMICS G120C 13.12.2010 V4.4...
Page 375
[6799.6] <2> [6731.4] Id_act [Aeff] r0076 [6799.6] <1> For induction motors <2> For synchronous motors <3> Is set automatically at the end of commissioning. Vector control Function diagram FP_6714_97_05.vsd - 6714 - Iq and Id controllers SINAMICS G120C 13.12.2010 V4.4...
Page 376
Torque setting value, speed controller [6060.7] [6040.4] M_acceleration r1539 [6060.4] Motor model deviation component 1 [6731.2] n-Ctrl = 1 PEM: Permanent-magnet synchronous motor Vector control Function diagram FP_6721_97_05.vsd - 6721 - Id setpoint (PEM, p0300 = 2) SINAMICS G120C 13.12.2010 V4.4...
Page 377
Mot I_mag_rtd act [Aeff] r0331 [D] <1> Value range and/or factory setting depend on Power Module ASM: Induction motor Vector control Function diagram FP_6722_97_05.vsd - 6722 - Field weakening characteristic, Id setpoint (ASM, p0300 = 1) SINAMICS G120C 13.12.2010 V4.4...
Page 378
Id_setp total [Aeff] r1624 Flux setpoint smoothed [6722.8] [6714.1] Saturation characteristic p0362 ... p0369 Id current limit [6722.8] ASM: Induction motor Vector control Function diagram FP_6723_97_05.vsd - 6723 - Field weakening controller, flux controller (ASM, p0300 = 1) SINAMICS G120C 13.12.2010 V4.4...
Page 379
Mot I_mag_rtd act [Aeff] r0331 [D] Flux setp total [%] 100 % r1598 I_outp max [Aeff] r0067 [6640.3] PEM: Permanent-magnet synchronous motor Vector control Function diagram FP_6724_97_05.vsd - 6724 - Field weakening controller (PEM, p0300 = 2) SINAMICS G120C 13.12.2010 V4.4...
Page 380
Outp_ph_seq rev p1820 Stall monitoring [8012.3] r1408.12 p1745 + BRP Model control [6722.7] - BRN [6640.5] Brake control [6710.2] p1755 Vector control Function diagram FP_6730_97_05.vsd - 6730 - Interface to the Power Module (ASM, p0300 = 1) SINAMICS G120C 13.12.2010 V4.4...
Page 381
+ BRP [6714.1] Motor model - BRN Model control Brake control U_phase act val r0089 p1755 PEM: Permanent-magnet synchronous motor Vector control Function diagram FP_6731_97_05.vsd - 6731 - Interface to the Power Module (PEM, p0300 = 2) SINAMICS G120C 13.12.2010 V4.4...
Page 382
Cos phi act r0072 [6730.1] Cos phi smooth r0087 <1> [6730.4] r0038 300 ms P_act [kW] [6731.1] r0082 <1> For induction motors <2> For synchronous motors Vector control Function diagram FP_6799_97_61.vsd - 6799 - Display signals SINAMICS G120C 13.12.2010 V4.4...
Page 384
The DC braking current is determined during automatic calculation (p0340 = 1). <3> DC braking when starting speed for DC braking (p1234) is fallen below. Technology functions Function diagram FP_7017_97_05.vsd - 7017 - DC brake (p0300 = 1) SINAMICS G120C 13.12.2010 V4.4...
Page 388
For p2230.0 = 0, this setpoint is entered after ON. <2> If initial rounding-off is active (p2230.2 = 1), the selected ramp-up/down times are exceeded accordingly. Technology controller Function diagram FP_7954_97_61.vsd - 7954 - Motorized potentiometer SINAMICS G120C 13.12.2010 V4.4...
Page 389
0.00 ... 100.00 [s] <7> p2251 = 0: I component is stopped, when r2294 is below the minimum speed or within a suppression bandwidth. p2293 (1.00) Technology controller Function diagram FP_7958_97_05.vsd - 7958 - Closed-loop control SINAMICS G120C 13.12.2010 V4.4...
Page 394
[2548.2] Overload response Alarm with I2t overload PU overld response 95.0 [%] 0 ... 3 p0290 (2) A07805 "Power module overload" Signals and monitoring functions Function diagram FP_8014_97_05.vsd - 8014 - Thermal monitoring, power module SINAMICS G120C 13.12.2010 V4.4...
Page 395
2 : Warning and fault, no reduction of I_max <4> The relevant rated response temperature in °C depends on the temperature sensor chosen by the motor manufacturer. Signals and monitoring functions Function diagram FP_8016_97_05.vsd - 8016 - Thermal monitoring, motor SINAMICS G120C 13.12.2010 V4.4...
Page 396
<1> Only if there is a temperature sensor (p0601 = 2). Only if <1> are not met. <2> Signals and monitoring functions Function diagram FP_8017_97_05.vsd - 8017 - Thermal I²t motor model (PEM, p0300 = 2) SINAMICS G120C 13.12.2010 V4.4...
Page 400
This fault is overwritten when "more recent" faults occur. r2139 <2> The buffer parameters are cyclically updated in the background (refer to the status signal in r2139). [2548.2] r2139 Faults and warnings Function diagram FP_8060_97_05.vsd - 8060 - Fault buffer SINAMICS G120C 13.12.2010 V4.4...
Page 401
RESET Fault buffer change [8060.8] r2139 r2139 POWER ON [2548.2] <1> The buffer parameters are updated cyclically in the background (see status signal in r2139). Faults and warnings Function diagram FP_8065_97_05.vsd - 8065 - Warning buffer SINAMICS G120C 13.12.2010 V4.4...
Page 403
The fault response and acknowledge mode for all faults and alarms are set to meaningful default values in the factory setting. Changes that may be required are only possible in specific value ranges specified by SIEMENS. When the message type is changed, the supplementary information is tranferred from fault value r0949 to alarm value r2124 and vice versa.
Page 405
(2) CDS1 CDS0 CDS effective r0050 r0050 r0050.1 Note Data sets can only be applied and cleared when p0010 = 15 is set. Data sets Function diagram FP_8560_97_05.vsd - 8560 - Command Data Sets (CDS) SINAMICS G120C 13.12.2010 V4.4...
Brackets including the letters A, F, or N indicate that the message type can be changed, e.g. A01016 (F) means that the alarm A01016 can be parameterized as a fault. This function is not enabled for SINAMICS G120C. Faults are stored in parameter r0945/r0947, under their code number (e.g.
Page 414
Acknowledge: NONE Cause: At least one firmware file in the directory /SIEMENS/SINAMICS/ has been changed without authorization with respect to the version shipped from the factory. No changes are permitted in this directory. Alarm value (r2124, interpret decimal): 0: Checksum of one file is incorrect.
Page 444
See also: p0205 (Power unit application), r0206 (Rated power unit power), r0207 (Rated power unit current), r0208 (Rated power unit line supply voltage), r0209 (Power unit, maximum current) Remedy: Replace the power unit or inform Siemens Customer Service. A07850 (F) External alarm 1...