Page 1
FLOOR-STANDING TYPE AIR CONDITIONER Owner’s Manual & Installation Manual FIP-600M IMPORTANT NOTE: Read this manual and SAFETY MANUAL(if any) carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference. Please check the applicable models, technical data, F-GAS(if any) and manufacturer information from the “Owner's Manual - Product Fiche ”...
Table of Contents Safety Precautions ................04 Owner s Manual ’ Unit Specifications and Features ............08 1. Unit Parts ..........................08 2. Operating temperature......................08 3. Features ..........................09 Manual Operations ..............10 Care and Maintenance ..............15 Troubleshooting ................17...
Page 3
Installation Manual Accessories ..................20 Installation Summary ..............21 Unit Parts ..................22 Indoor Unit Installation ...............23 1. Select installation location .....................23 2. Unfastening the operation panel and detaching the filter ............24 3. Remove the fasteners from the roller ..................24 4. Fastening the indoor unit ......................24 5.
Safety Precautions Read Safety Precautions Before Operation and Installation Incorrect installation due to ignoring instructions can cause serious damage or injury. The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION. CAUTION WARNING This symbol indicates the possibility This symbol indicates the possibility of of personnel injury or loss of life.
Page 5
CLEANING AND MAINTENANCE WARNINGS Turn off the device and disconnect the power before cleaning. Failure to do so can cause • electrical shock. Do not clean the air conditioner with excessive amounts of water. • Do not clean the air conditioner with combustible cleaning agents. Combustible cleaning agents •...
WARNINGS FOR PRODUCT INSTALLATION 1. Installation must be performed by an authorized dealer or specialist. Defective installation can cause water leakage, electrical shock, or fire. 2. Installation must be performed according to the installation instructions. Improper installation can cause water leakage, electrical shock, or fire. (In North America,installation must be performed in accordance with the requirement of NEC and CEC by authorized personnel only.) 3.
WARNING for Using R32/R290 Refrigerant When flammable refrigerant are employed, appliance shall be stored in a well -ventilated area where the room size corresponds to the room area as specified for operation. For R32 frigerant models: Appliance shall be installed, operated and stored in a room with a floor area larger than X m²...
Unit Specifications and Features Unit Parts Air outlet Display panel Operating temperature When your air conditioner is used outside of the following temperature ranges, certain safety protection features may activate and cause the unit to disable. Inverter Split Type FOR OUTDOOR UNITS COOL mode HEAT mode DRY mode...
Manual Operations NOTE: Different models have different display panel. Not all the indicators describing below are available for the air conditioner you purchased. Please check the indoor display panel of the unit you purchased. Illustrations in this manual are for explanatory purposes. The actual shape of your indoor unit may be slightly different.
Model A Model B Model C Model D Auto operation display Cooling operation display Dry operation display Heating operation display Fan operation display Lock operation display Swing operation display Sleep operation display Turbo operation display TIMER ON On timer operation display TIMER OFF Off timer operation display Fan speed display...
Page 12
Fan speed button: This button is used to select the desired fan speed. Each time you push the button, the fan speed is shifted in the following sequence: MED (some units) HIGH AUTO NOTE: You can not select a fan speed under AUTO and DRY mode. The fan speed is automatically controlled.
Page 13
ADJUST button: Temperature adjust: Press the " " and " " to adjust the temperature in a range of 16 °C/17°C~30°C(60 °F/62°F~86°F) or 20°C~28°C(68°F~82°F. Timer adjust: Adjust the timer on/off time under the Timer setting mode(0~24hs). Auxiliary function selection: Select the desired auxiliary function by pressing" "...
LOCK button: Press Lock button to activate lock feature, all buttons will not response except pressing this button again to disable locking (For Model B/C/D). buttons together to activate lock feature, all buttons will not Press and hold response except pressing these two buttons again to disable locking (For Model A) . Under lock mode, if you press any other button on the display panel, the lock symbol will flash 5 seconds at 1Hz.
Care and Maintenance Cleaning Your Indoor Unit CAUTION BEFORE CLEANING OR • Do not use water to clean the inside of MAINTENANCE the indoor unit. This can destroy ALWAYS TURN OFF YOUR AIR insulation and cause electrical shock. CONDITIONER SYSTEM AND •...
Refrigerant Leak Detection System (some Maintenance – models) Pre-Season Inspection In the event of a refrigerant leak, the LCD • screen will display “EC” . After long periods of non-use, or before periods of frequent use, do the following: Maintenance – Long Periods of Non-Use If you plan not to use your air conditioner for an extended period of time, do the following:...
Troubleshooting SAFETY PRECAUTIONS If any of the following conditions occurs, turn off your unit immediately! The power cord is damaged or abnormally warm • You smell a burning odor • The unit emits loud or abnormal sounds • A power fuse blows or the circuit breaker frequently trips •...
Page 18
Issue Possible Causes The outdoor unit The unit will make different sounds based on its current operating mode. makes noises Dust is emitted from The unit may accumulate dust during extended periods of non-use, which will be either the indoor or emitted when the unit is turned on.
Page 19
Problem Possible Causes Solution Wait for the power to be restored Power failure The power is turned off Turn on the power The fuse is burned out Replace the fuse The unit is not working Replace batteries Remote control batteries are dead The Unit’s 3-minute protection Wait three minutes after restarting has been activated...
Accessories The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail. The items are not included with the air conditioner must be purchased separately.
Installation Summary - Indoor Unit INSTALLATION ORDER Install the indoor unit Install the outdoor unit Connect the refrigerant pipes Perform a test run Evacuate the refrigeration system Connect the wires Page 21 ...
Unit Parts Outdoor unit Indoor unit Air outlet Drain pipe, vent pipe Operation panel Connection cable Horizontal airflow control louver Connection pipe Vertical airflow control louver Refrigerant pipe port Air inlet Air outlet NOTE ON ILLUSTRATIONS Illustrations in this manual are for explanatory purposes. The actual shape of your indoor unit may be slightly different.
Indoor Unit Installation Installation Instructions – Indoor unit NOTE ABOUT WALL HOLE: If there is no fixed refrigerant piping: PRIOR TO INSTALLATION While choosing a location, be aware that you should leave ample room for a wall hole (see Before installing the indoor unit, refer to the Drill wall hole for connective piping step) label on the product box to make sure that the for the signal cable and refrigerant piping...
Step 2: Unfastening the operation panel and CAUTION detaching the filter If further support is needed to prevent the Open the packaging and take out the indoor unit from falling down, a protective wedge unit. Remove the protective tape and any can be installed.
NOTE Arrange the piping so that the drainage hose is on the bottom, the connecting piping is in Only models with a ventilation function • the middle, and the electrical wiring is at the contain ventilation ducting. top. The amount and type of electrical wiring •...
Indoor Drainpipe Installation Wall Outdoor Indoor Glue Drain pipe Drain pipe Band for covering the pipe ≈ 0.5~1cm 1. Make sure the drain pipe is connected to the / 0.2~0.4 inch outdoor side downward. 2. The hard polyvinyl chloride (PVC) plastic pipe 3.
Outdoor Unit Installation Install the unit by following local codes and install unit in the following locations: DO NOT regulations , there may be differ slightly Near an obstacle that will block air inlets between different regions. and outlets Near a public street, crowded areas, or where noise from the unit will disturb others Near animals or plants that will be harmed by hot air discharge...
Step 2: Install drain joint IN COLD CLIMATES (Heat pump unit only) In cold climates, make sure that the drain Before bolting the outdoor unit in place, you must hose is as vertical as possible to ensure install the drain joint at the bottom of the unit. Note that there are two different types of drain swift water drainage.
Page 29
Rows of series installation The relations between H, A and L are as follows L ≤ 1/2H 25 cm / 9.8” or more L ≤ H 1/2H < L ≤ H 30 cm / 11.8” or more Can not be installed L >...
Refrigerant Piping Connection When connecting refrigerant piping, do not let substances or gases other than the specified refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity, and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and injury.
Step 3: Flare pipe ends Connection Instructions – Proper flaring is essential to achieve an airtight seal. Refrigerant Piping After removing burrs from cut pipe, seal the ends with PVC tape to prevent foreign Step 1: Cut pipes materials from entering the pipe. Sheath the pipe with insulating material.
NOTES ON MINIMUM BEND RADIUS Step 4: Connect pipes Carefully bend the tubing in the middle Connect the copper pipes to the indoor unit first, according to the diagram below. DO NOT then connect it to the outdoor unit. You should bend the tubing more than 90°...
Wiring BEFORE PERFORMING ANY 9. Every wire must be firmly connected. ELECTRICAL WORK, READ THESE Loose wiring can cause the terminal to overheat, resulting in product malfunction REGULATIONS and possible fire. Do not let wires touch or rest against refrigerant tubing, the 1.
NOTE ON AIR SWITCH Air switch When the maximum current of the air conditioner (purchased seperately) is more than 16A, an air switch or leakage Air switch (purchased protection switch with protective device shall be Indoor unit power wires seperately) used (purchased seperately) .
b. Using wire strippers, strip the rubber jacket 3. Connect the u-lugs to the terminals. from both ends of the signal cable to reveal Match the wire colors/labels with the labels approximately 15cm (5.9”) of wire. on the terminal block. Firmly screw the u-lug c.
Air Evacuation Wait for 5 minutes, then check that there Preparations and Precautions has been no change in system pressure. Air and foreign matter in the refrigerant circuit can If there is a change in system pressure, refer cause abnormal rises in pressure, which can damage to Gas Leak Check section for information the air conditioner, reduce its efficiency, and cause on how to check for leaks.
Note on Adding Refrigerant Some systems require additional charging depending on pipe lengths. The standard pipe length varies according to local regulations. For example, in North America, the standard pipe length is 7.5m (25’). In other areas, the standard pipe length is 5m (16‘). The refrigerant should be charged from the service port on the outdoor unit’s low pressure valve.
Test Run f. Check to see that the drainage system is Before Test Run unimpeded and draining smoothly. A test run must be performed after the entire g. Ensure there is no vibration or abnormal system has been completely installed. Confirm noise during operation.
Packing and unpacking the unit Instructions for packing/unpacking the unit: Unpacking: Indoor unit: 1.Cut the sealing tape on the carton with a knife. 2.Take off the carton. 3.Remove the upper packaging foam. 4.Untie the packaging bag. 5.Take out the indoor unit. Outdoor Unit 1.Cut the packing belt.
Page 40
The design and specifications are subject to change without prior notice for product improvement. Consult with the sales agency or manufacturer for details. Any updates to the manual will be uploaded to the service website, please check for the latest version. CF002UI-GA(B)
Need help?
Do you have a question about the FIP-600M and is the answer not in the manual?
Questions and answers