UP or DOWN key to modify the set value.
For example: if the limits are default value, the set temperature can be adjusted between 0~50℃; if the high
limit is 30C, low limit is 10C, the set temperature can only be adjusted between10℃ - 30℃.
Controlling function :
Heat controlling function :
Heating systems works in below situation:
the measuring temperature ≤ the set temperature - the temperature difference
Heating systems stops working in below situation:
the measuring temperature ≥ the set temperature
Cool controlling function :
Cooling systems works in below situation:
the measuring temperature ≥ the set temperature + the temperature difference
Cooling systems stops working in below situation:
the measuring temperature ≤ the set temperature
Timing controlling function:
FROM: timing of turning on light; TO: timing of turning off light
If the system time is during FROM time and TO time, the light will light when the timing setting has been
adjusted and saved. For example, the original timing starting time is 8:30, original timing ending time is 18:30,
new timing starting time is 6:00, new timing ending time is 18:00, the system time is 7:00, you will see the light
is on. If not, the light is off.
Others:
Over temperature alarm:
upper part of icon rapid flashing with "drops" alarm sounds and display the measuring temperature in below
situation:
- the measuring temperature ≥ the set temperature + Alarm over temperature
- the measuring temperature ≤ the set temperature - Alarm over temperature
Exceed temperature measuring limits alarm: with "drops" alarm sounds at the same time.
- the measuring temperature <0.0℃, display LLL: super low temperature;
- the measuring temperature >50.0℃, display HHH: super high temperature;
Probe fault alarm: when probe have open circuit or short circuit faulty, display error message of probe faulty
"ERR"
Mute alarming manually:
The 1st and 2nd alarm can be muted by pressing any key, but probe fault alarm sound cannot be eliminated.
Press UP or DOWN key at the same time for 3 sec or more, the menu is available to choose whether to
eliminate alarm sound, AL: have alarm sounds, NO: have no alarm sounds.
You can choose one and press SET to save and exit.
Socket output control load:
I: heat/cool output; II: timer output, such as lighting or oxygen pump.
Safety regulations:
Dangers: Please avoid overload, load short circuit, misuse, human damage etc., which is not covered
by the warranty.
DO NOT connect the wire terminals without electricity cut-off.
Warning: DO NOT use the machine under the environment of over damp, high temp, strong electromagnetic
interference or strong corrosion.
Notes: The power supply should conform to the voltage value indicated in the instruction and keep stability
To avoid the interference, the sensor down-lead and power wire should be kept a distance.