Page 1
INSTALLATION AND OPERATION MANUAL High Efficiency Air Handlers 2-5 Tons Capacity | R454B LCM7 SERIES Original instructions. Please read this manual carefully and keep it for future reference. All the pictures in this manual are for illustrations purpose only.
Page 2
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION WARNING These instructions are intended as an aid to qualified licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service, or maintenance, which could possibly lead to fire, electrical shock, property damage, personal injury, or even death.
CONTENTS 1 SAFETY Safety Signs Safety Precautions 2 ABOUT THE PRODUCT Unit Dimensions Parts Introduction Attached Fittings Refrigerant Sensor 3 INSTALLATION Installation Instructions Vertical Upflow Vertical Downflow Horizontal Installation in an Unconditioned Space Refrigerant Charge and Room Area Limitations 4 REFRIGERANT LINE 5 AIRFLOW PERFORMANCE (AIR HANDLERS ARE SUITABLE FOR MOBILE HOME APPLICATIONS) 6 DUCTWORK...
This document is customer property and is to remain with this unit. These instructions do not cover all the different variations, nor do they provide nor does it provide for every possible contingency to be met in connection with installation. All phases of this installation must comply with national state and local codes.
WARNING 1.2 Safety Precautions DANGER PROPOSITION 65: This appliance contains fiberglass insulation. Respirable particles of fiberglass are known to the State of California to Disconnect all power to unit before installing or cause cancer. servicing. More than one disconnect switch may be required to de-energize the equipment.
Page 6
WARNING WARNING WARNING Only use this unit in a well-ventilated area and When repairing the refrigerating system, comply ensure unit's airflow inlet and outlet would not be with the following precautions prior to conducting impeded by obstructions. Do not use this unit in work on the system: the following locations: –...
Page 7
Leak detection fluids are also suitable for use Refrigerating pipe or components are installed in with most refrigerants but the use of detergents a position where they are unlikely to be exposed containing chlorine shall be avoided as the to any substances which may corrode refrigerant chlorine may react with the refrigerant and containing components, unless the components corrode the copper pipe-work.
Page 8
Prior to recharging the system, it shall be When transferring refrigerant into cylinders, pressure-tested with the appropriate purging ensure that only appropriate refrigerant recovery gas. The system shall be leak-tested on cylinders are employed. Ensure that the correct completion of charging but prior to commissioning. number of cylinders for holding the total system A follow up leak test shall be carried out prior to charge is available.
Page 9
training on the meaning of appropriate safety If electrical appliances are disposed of in landfills signs and the actions that need to be taken in or dumps, hazardous substances can leak into connection with these signs. the groundwater and get into the food chain, harming your health and well-being.
2 ABOUT THE PRODUCT 2.1 Unit Dimensions Note: 25" clearance is required in the front of the unit for filter and coil maintenance. Electrical connections Supply air may exit top or right side Flanges are provided for field installation High voltage connection 7/8", 1-3/8", 1-3/4"...
2.2 Parts Introduction Fig.2-2 Number Parts Control Board DC Motor Blower AL-Evaporator R454B Refrigerant Sensor Table 2-2 2.3 Attached Fittings Name Appearance Quantity Name Appearance Quantity Indoor unit operation Sealing ring and installation manual Accessory package Alarm output wires Seal plug Pipe Joint Hook Table 2-3...
2.4 Refrigerant Sensor 3 INSTALLATION 3.1 Installation Instructions R454B refrigerant leakage sensor is configured for the indoor unit. To meet different installation scenarios, the refrigerant sensor has two installation positions. The The unit can be positioned for bottom return air in the factory set of the refrigerant sensor is applied to the upflow position, left and right return in the horizontal vertical upflow and horizontal right.
Page 13
When the unit is installed in a hot and humid place, If the humidity inside the installation space might exceed 86 ℉ and RH 80 %, it is recommended to insulate the cabinet exterior. Use glass wool or polyethylene foam as insulation so that the thickness is more than 2 inches and fits inside the installation space opening.
Page 14
NOTICE If installed vertically downflow in a hot and humid place that might exceed 86 ℉ and RH 80 %, such as in the basement, the extra drain pan, sponge and sealant shall be installed as shown in Fig.3-7. Sealant must meet the fire rating requirements of 5VA.
3.2 Vertical Upflow Vertical Upflow configuration is the factory set on all models. See Fig.3-8. 2-3/4 If return air is to be ducted, install duct flush with floor. Use fireproof resilient gasket 1/8 to 1/4 in. thick between the ducts, unit and floor. Set unit on floor over opening. 1-9/16 IMPORTANT NOTE Torque applied to drain connections should not exceed...
Page 16
Steps for Changing Cabinet Orientation to Vertical Downflow or Horizontal Left Orientation 1. Remove the screws and front panel and disconnect the refrigerant sensor from the control board. 2. Pull out the coil with refrigerant sensor (Figure 3-10, Step 2). 3.
Page 17
When installing the evaporator, ensure the retaining channel is fully engaged with the coil rail. Ensure the retaining channel is fully engaged with the coil rail. Detail A Rails AIRFLOW Rails Fig.3-11 Vertical Downflow & Horizontal Left Applications Conversion in Horizontal Direction: NOTICE Horizontal right-hand supply can be changed to horizontal left-hand supply by removing the indoor coil...
3.5 Installation in an Unconditioned For determination of room area (A) when used to calculate the refrigerant charge limit, the following shall Space apply. The room area (A) shall be defined as the room area enclosed by the projection to the base of the walls, NOTICE partitions and doors of the space in which the appliance is installed.
Page 19
3.6.2. The allowed maximum refrigerant The minimum opening for natural ventilation (Anv ) in connected rooms is related to the room area (A), the charge and required minimum room actual refrigerant charge of refrigerant in the system (m area and the allowable MAXIMUM REFRIGERANT CHARGE in the system (m ), Anv can be determined according to...
Page 20
The minimum circulation airflow Installation scheme flow chart Check if the minimum room area meets the requirements lb-oz lb-oz 10-2 10-9 Determine the room size and the 11-0 refrigerant system configuration 11-7 3-15 11-14 12 -5 Calculate the total refrigerant 4-13 12-12 charge...
4 REFRIGERANT LINE Field-made refrigerant joints indoors shall be tightness tested. The test method shall have a sensitivity of 5 grams per year of refrigerant or better under a pressure The suction pipe and liquid pipe of the indoor unit need of at least 0.25 times the maximum allowable pressure.
Page 22
5. AIRFLOW PERFORMANCE (AMERISTAR AIR HANDLERS ARE SUITABLE FOR MOBILE HOME APPLICATIONS) Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for appropriate unit size. External static applied to unit allows operation within the minimum and maximum limits shown in table below for both cooling and electric heat operation.
Page 23
Outdoor CFM Wet Coil without filter and Electric Heat Motor Model Unit External Static Pressure (in w.c) Speed Number Size (Tons) Current / A 2.92 2.99 3.07 3.14 3.19 3.25 3.35 3.49 3.50 Power / W 1560 1520 1480 1442 1403 1378 1323...
NOTES: Airflow based upon cooling performance at 230V with no electric heat and no filter. Airflow at 208V is approximately the same as 230V because the mult-tap ECM motor is a constant torque motor. The torque doesn’t drop off at the speeds in which the motor operates.
7 ABOUT THE AIR FILTER IMPORTANT: Do not double filter the return air duct system. Do not filter the supply air duct system. This will change the performance of the unit and reduce airflow. 7.1 Air Filter (Not Factory-Installed) WARNING External filter or other means of filtration is required.
AIR FILTER REMOVAL 1. Remove bolts manually, remove air filter recover. See in Fig.7-1. 2. Hold the edge of the air filter and extract out. 3. Clean the air filter (Vacuum cleaner or pure water may be used to clean the air filter. If the dust accumulation is too heavy, use soft brush and mild detergent to clean it and dry out in cool place).
9 ELECTRICAL WIRING Power cords conventional 24VAC non-communicating thermostat control wires must In the U.S.A., wiring must conform with current local be separated from each other with a distance of codes and the current National Electric Code (NEC). In more than 2 inches. Otherwise, the communication Canada, wiring must conform with current local codes may be abnormal.
Page 29
2. Low voltage wires connections with outdoor unit. 2.1 Wires connections diagram. THERMOSTAT Terminal TO THERMOSTAT INDOOR UNIT OUTDOOR UNIT Fig.9-2 2.2 Connect the conventional 24VAC non-communicating thermostat control wires to the field supplied wires. The wires unused should be insulated Multicore wires used for 24VAC non-communicating thermostat control wires Connect the...
Page 30
3. Low voltage wires connections with thermostat. 3.1 Connect the Control communication cables by wire nut. The unused wires should be insulated Connect the wires by wire nut THERMOSTAT Fig.9-4 3.2 Wiring diagram of the thermostat. Support 3H and 2C thermostat Y EL LO W R E D B L AC K...
Page 31
Wiring for 4H and 2C thermostat Y E L LO W R ED BL A C K G R E E N P U R PL E H/DH G R A Y THERMOSTAT B L U E W H ITE B R O W N Note: Any time the electric heat elements are active, the indoor fan...
Page 32
Wiring for 2H and 2C thermostat Y E L LO W R ED BL A C K GR E E N H/DH P U R PL E G R AY THERMOSTAT BL U E W H ITE BR O W N INDOOR UNIT Fig.9-8 Wiring for 1H and 1C thermostat...
Page 33
Wiring for 2H and 1C thermostat Y EL LO W R E D B LA C K G R EE N P U R PL E H/DH G R A Y THERMOSTAT B LU E W H I TE B R OW N INDOOR UNIT Note: W1 and W2 are jumped, so Electric Heat will only function in...
9.2 Power Wiring NOTICE In the U.S.A., wiring must conform with current local Electrostatic discharge can affect electronic codes and the current National Electric Code (NEC). In components. Take care during unit installation Canada, wiring must conform with current local codes and service to protect the unit’s electronic and the current Canadian Electrical Code (CEC).
9.3 Alarm Wiring 9.3.1 Wiring Diagram Alarm output CN34 wires Ext output wiring Control board Central monitor Fig.9-12 Note: The remote control of the internal circuit is for reference only, the user can change the wiring mode according to the actual situation.
9.4 Electric Heater Kit 9.4.1 Electric heater kit breaker information Breaker Ref.Air Handler Use Description CHE7A-05B 5 kW Heater Max. 240 V, 30 A, 2 P 24,36,48,60,61 CHE7A-08B 7.5 kW Heater Max. 240 V, 50 A, 2 P 24,36,48,60,61 CHE7A-10B 10 kW Heater Max.
Page 37
9.4.2 Electric Heater Kit Electrical Data (only Eletric Heat) Min. Circuit Max. Fuse or Breaker Minimum Heating Blower Heater Kit Electric Ampacity (HACR) Ampacity Handler Speed Model Heat (kW) Model Used 240 V 208 V 240 V 208 V • •...
Page 38
9.4.3 Electric Heater Kit Electrical Data (Eletric Heat combines with Indoor motor) Min. Circuit Max. Fuse or Breaker Minimum Heating Blower Heater Kit Electric Ampacity (HACR) Ampacity Handler Speed Model Heat (kW) Model Used 240 V 208 V 240 V 208 V •...
11 SERVICE 10 SETTING 11.1 Error Code and Troubleshooting Check whether the DIP switch is correct according to the wiring nameplate after the electrical wiring is complete. The unit LED will flash when the unit is abnormal. SW6-1,2 is used to set the blower speed. The factory Security consideration, the outdoor unit shutdown until default settings of different models as shown in the table the abnormal condition is corrected.
11.3 TXV Replacement Information A TXV may be required to achieve minimum efficiency ratings or for long refrigerant line set applications. (for 61K) Reference AHRI for system combination ratings. Factory installed piston size for each model. Additional NOTICE piston sizes are provided in the ship with literature bag as necessary.
Al-copper Transition Section Vapor Line Connection Equalization Pipe Copper Straps Refrigerant sensor Bulb Liquid Line Connection Tighten Torque T2 Sensor 22 (±2) ft-lb Mounting Plate Table 11-4 . TXV specification. Model R454B TXV 5 Ton 12 DISPOSAL Comply with national regulations. Components and accessories from the units are not part of ordinary domestic waste.
Need help?
Do you have a question about the LCM7 Series and is the answer not in the manual?
Questions and answers