R410A 60Hz Top-discharge Outdoor Series Technical Manual Part 1 General Information ......... 1 1. Model Names of Indoor/Outdoor Units ..............2 2. External Appearance....................3 3. Features ........................ 4 Part 2 Indoor Units ..........5 1. Specifications......................6 2. Dimensions ......................7 3.
R410A 60Hz Top-dischargeOutdoor Series Technical Manual R410A 60Hz Top-discharge Outdoor series Part 1 General Information 1. Model Names of Indoor/Outdoor Units ......2 2. External Appearance ............3 3. Features................4...
R410A 60Hz Top-discharge Outdoor Series Technical Manual 1. Model Names of Indoor/Outdoor Units 1.1 Indoor units Model name Dimension (W×H×D) / (mm) Net/Gross weight (kg) Power supply Air-Handler units AHE36-1-C 460×774×520 37/39 208~230V/1Ph/60Hz AHE60-1-C 500×1160×550 45/48 208~230V/1Ph/60Hz AHE60-1-C 500×1160×550 45/48 208~230V/3Ph/60Hz 1.2 Outdoor Units...
R410A 60Hz Top-discharge Outdoor Series Technical Manual 3. Features 3.1 Well-known compressor, LG & Copeland, Highly. High efficiency rotary compressor for 36K model, and scroll compressor for 60K model. 4.2 Universal 24V communication connection for indoor and outdoor units control, 4.3 R410 environmental refrigerant, and it is matched with top-discharge unit and condensing unit.
R410A 60Hz Top-discharge Outdoor Series Technical Manual Part 2 Indoor Units 1. Specifications ..............6 2. Dimensions ................ 7 3. Service Space ..............8 4. Wiring Diagrams .............. 9 5. The Specification of Wiring ......... 10 6. Field Wiring ..............11 7.
R410A 60Hz Top-discharge Outdoor Series Technical Manual 3. Service Space The air-handler unit should be installed in a location that meets the following requirements: INSTALLATION NOTES: . 1. Up-flow discharge , the installation of plug and drain pipe is shown in the left figure. 2.
R410A 60Hz Top-discharge Outdoor Series Technical Manual 5.The Specification of Wiring Single-phase for cooling only type, 220V Capacity(Btu/h) 36000 Btu/h 60000 Btu/h Single Indoor 220-230V,60Hz 1PH Power Single Outdoor 220-230V,60Hz 1PH Input Current Fuse Indoor unit(A) Line Quantity Indoor Unit Power Line Line Diameter(AWG) 18/1.0mm 2 18/1.0mm 2...
R410A 60Hz Top-discharge Outdoor Series Technical Manual 6.Field Wiring 1.To avoid the electric shock, please link the air conditioner with the ground. The plug in the air conditioner has joined the ground wiring, please don't change it freely. 2.The power socket is used as the air conditioner specially. 3.Don’t pull the power wiring hard.
R410A 60Hz Top-discharge Outdoor Series Technical Manual 7. Exploded View Part Name Part Name Chasiss assembly Evaporator Water Baffle #1 Right Volute Wind Wheel Diverter Assembly Fan Motor Fixing plate Lower side plate assembly Wind Wheel Fixed Block Water pan fixed block Electronic Control Fixing Plate Assy Pipe Cover plate assembly ELectronic Control Components...
Page 25
R410A 60Hz Top-discharge Outdoor Series Technical Manual Top net Uniaxial outdoor motor Propeller fan Top cover assembly Condenser assembly Condenser ssembly Condenser input pipe assembly Condenser output pipe assembly Weld assembly for high pressure valve 5.4.1 Block valve body 2 Electronic components Electric install board weld assembly Electric waterproof box...
R410A 60Hz Top-discharge Outdoor Series Technical Manual 8.Sound Levels 36000Btu/h 60000Btu/h Outdoor Unit Microphone 1.0m Note: H= 0.5 × height of outdoor unit Note: The point A is in the middle of the whole outdoor panel. Model Noise level dB(A) CCU36-410-C CCU60-410-C CCU60-410-3-C...
R410A 60Hz Top-discharge Outdoor Series Technical Manual 1.Precaution on Installation 1.1. Measure the necessary length of the connecting pipe, and make it by the following way. Connect the indoor unit at first, then the outdoor unit. Bend the tubing in proper way. Do not harm them. CAUTIONS: ...
R410A 60Hz Top-discharge Outdoor Series Technical Manual 2.Vacuum Dry and Leakage Checking 2.1 Vacuum Dry: use vacuum pump to change the moisture (liquid) into steam (gas) in the pipe and discharge it out of the pipe to make the pipe dry. Under one atmospheric pressure, the boiling point of water(steam temperature) is 100℃.
Page 31
R410A 60Hz Top-discharge Outdoor Series Technical Manual Because nitrogen is for drying gas, it has vacuum drying effect during vacuum destroy. But if the moisture is too much, this method can’t dry thoroughly. So, please pay more attention to prevent water entering and forming condensation water.
R410A 60Hz Top-discharge Outdoor Series Technical Manual 3.Additional Refrigerant Charge Caution ● Refrigerant cannot be charged until field wiring has been completed. ● Refrigerant may only be charged after performing the leak test and the vacuum pumping. ● When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in view of the danger of liquid hammer.
R410A 60Hz Top-discharge Outdoor Series Technical Manual 4.Water Drainage 4.1 Gradient and Supporting 4.1.1 Keep the drainpipe sloping downwards at a gradient of at least 1/100. Keep the drainpipe as short as possible and eliminate the air bubble. 4.1.2 The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be installed to keep the gradient of 1/100 and prevent bending.
Page 34
R410A 60Hz Top-discharge Outdoor Series Technical Manual Ceiling cassette 4.4 Convergent drainage 4.4.1. The number of indoor units should be as small as possible to prevent the traverse main pipe overlong. 4.4.2. Indoor unit with drain pump and indoor unit without drain pump should be in different drainage system. 4.4.3.
Page 35
R410A 60Hz Top-discharge Outdoor Series Technical Manual ③ Stop the air conditioner running, turn off the power, and put back the cover. Stop the air conditioner. After 3 minutes, check if it has abnormity. If the collocation of drainpipes is illogical, the water will flow back overfull, which will cause the alarm lamp flashes, even overflow from the water receipt plate.
R410A 60Hz Top-discharge Outdoor Series Technical Manual 5.Insulation Work 5.1 Insulation material and thickness 5.1.1. Insulation material Insulation material should adopt the material which is able to endure the pipe’s temperature: no less than 70℃ in the high-pressure side, no less than 120℃ in the low-pressure side(For the cooling type machine, no requirements at the low-pressure side.) ...
Page 37
R410A 60Hz Top-discharge Outdoor Series Technical Manual 5.3 Drainage pipe insulation The connection part should be insulated, or else water will be condensing at the non-insulation part. 5.4 Note 5.4.1 The jointing area, expanding area and the flange area should be heat insulated after passing the pressure test 5.4.2 The gas and liquid pipe should be heat insulated individually, the connecting part should be heat insulated individually.
R410A 60Hz Top-discharge Outdoor Series Technical Manual 6.Test Operation The indoor unit and outdoor unit are installed properly. Tubing and wiring are correctly completed. The refrigerant pipe system is leakage-checked. The drainage is unimpeded. The ground wiring is connected correctly. ...