Bodine BLK1000FL Installation Instructions Manual

1000 lumen emergency led retrofit kit

Advertisement

BLK1000FL
Installation Instructions
1000 Lumen Emergency LED Retrofit Kit
! IMPORTANT SAFEGUARDS !
1.
WARNING - Risk of fire or electrical shock. Luminaire wiring and electrical parts may be damaged when
drilling for installation of LED retrofit kit. Check for enclosed wiring and components.
2.
WARNING - Risk of fire or electrical shock. LED retrofit kit installation requires knowledge of luminaires
electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician.
3.
WARNING - Risk of fire or electric shock. Install this kit only in luminaires that have the construction
features and dimensions shown in the drawings and where the input rating of the retrofit kit does not
exceed the input rating of the luminaire.
4.
WARNING - To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other
sharp objects.
5.
WARNING - Only those open holes indicated in the photographs and/or drawings may be made or altered as
a result of kit installation. Do not leave any other open holes in a wiring enclosure or electircal components.
6.
This product is for use with an emergency LED lighting load in compliance with NFPA-101 and NEC 700.12.
7.
Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical Code
and any local regulations.
8.
To reduce the risk of electric shock, disconnect both normal and emergency power supplies before
servicing. Follow the instructions in the OPERATION section to disable the output of this LED driver.
9.
This emergency driver is intended to be mounted and enclosed within a luminaire and is suitable for both
factory or field installation. For field installation, please see "Step #1 Determine Suitability" on Page 2 of
these instructions.
10. This product is suitable for use in damp locations where the luminaire's ambient temperature is 0ºC
minimum, +30ºC maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product
is not suitable for heated air outlets and wet or hazardous locations. Maximum allowable case temp is 65ºC.
See unit label for Tcase measurement location.
11. An unswitched AC power source is required (120-277 VAC, 50/60 Hz).
12. Do not install near gas or electric heaters.
13. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field
replaceable. Contact the manufacturer for information on service.
14. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
15. Do not use this product for other than intended use.
16. Servicing should be performed by qualified service personnel.
17. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by
unauthorized personnel.
18. For Canadian application, the output terminals should be in compliance with the accessibility requirement of
the Canadian Electrical Code.
19. This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1)
this device may not cause harmful interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
20. This product must be grounded. See the wiring diagrams for details.
21. The retrofit kit is accepted as a component of a luminaire where the suitability of the combination shall
be determined by authorities having jurisdiction. Product must be installed by a qualified electrician in
accordance with the applicable and appropriate electrical codes. The installation guide does not supersede
local or national regulations for electrical installations.
22. This LED retrofit kit shall only be used with UL Listed recessed or surface mounted, closed type luminaires
with frosted or clear lens with minimum dimensions W=3.5", L=24", D=4.75".
23. This LED Retrofit kit has a maximum mounting height of 21.88 feet.
Li - ion
Collierville, TN, USA • Tech Support Phone: 888-263-4638 • Email: BodineTech@Signify.com • www.bodine.com
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
THIS PRODUCT CONTAINS A RECHARGEABLE LITHIUM-ION BATTERY.
THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.
Bodine © 2024 Signify Holding. All rights reserved.
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY
PRECAUTIONS SHOULD ALWAYS BE FOLLOWED,
INCLUDING THE FOLLOWING:
442296606062

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BLK1000FL and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Bodine BLK1000FL

  • Page 1 THIS PRODUCT CONTAINS A RECHARGEABLE LITHIUM-ION BATTERY. THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY. Li - ion Bodine © 2024 Signify Holding. All rights reserved. Collierville, TN, USA • Tech Support Phone: 888-263-4638 • Email: BodineTech@Signify.com • www.bodine.com 442296606062...
  • Page 2: Installation

    > Ensure all parts listed for the emergency LED retrofit kit are within the kit before beginning installation. Parts in the kit include the following: > One BLK1000FL driver > One 1000 lumen LED module > One black 18AWG wire for AC mains hot connection >...
  • Page 3 Remove AC mains from the luminaire. Verify power is disconnected. If the lamp has a lens/cover, remove it to access the internals of the luminaire. If lamps are connected to the luminaire, remove them. Remove the driver/ballast cover. For the installation of the emergency driver and LED module, you will need to drill holes in the positions illustrated in Figure 2 (two 1/8"...
  • Page 4 STEP 3 - INSTALLING THE ILLUMINATED TEST SWITCH AND COMMUNICATION NODE Option 1: Using the Illuminated Test Switch/ Communication Node Bracket. > The illuminated test switch / communication node mounting bracket comes preassembled from the factory. The bracket can be mounted either through a 2”...
  • Page 5: Operation

    COMMUNICATION NODE WARNINGS • FirstLink communication node to be used only with FirstLink drivers, exit signs, and unit equipment. • Do not apply mains power directly to the node. • Do not cover the sensor during operation or mount the sensor internal to the luminaire. •...
  • Page 6: Troubleshooting Guide

    Commissioning: After the emergency driver has been charged for one hour, an automatic commissioning test will be performed. The emergency driver will switch to the emergency mode for 30 seconds and store in its memory the current level of the connected load. If, during future self-tests, this level deviates by more than 25%, an error will be triggered.
  • Page 7: Wiring Diagram

    (30 seconds every month) and duration tests (90 minutes every year) will be conducted automatically and the results stored in the unit awaiting download from the app. Test reports, in the form of Excel “.csv” files, are available through the app as well. See Bodine FirstLink App Guide (FirstLink App...