EN
Alarm
Description
E127
Overcurrent hardware
E129
Motor 1 phase loss
E131
Zero speed, failed start for compressor • Defective control board
E135
Overcurrent software
E181
No readback signal from the fan.
E201
Communication between the control
board and the communication board is
interrupted.
E217
No Water Flow
E219
Sensor fault, evaporator liquid pipe
sensor (BT39)
CAUTION
For any other error codes not present in
this list, refer to the control module manual.
10 - Accessories
Detailed information about the accessories and complete accessories list available on website. Not all accessories are
available on all markets.
May be due to
• Compressor load too high
• Compressor damaged
One phase of the compressor is not detected at the startup of the
compressor
• Compressor fault
Compressor load too high
• The fan cannot rotate freely
• Defective control board in the heat pump
• Defective fan motor
• Incorrect cable routing
• defective control board
Water fl ow under threshold for more than 15sec for units with
fl owmeter
• Open circuit or short circuit on sensor input
• Sensor does not work (see section "Disturbances in comfort")
• Defective heat pump control board