U.S. Boiler Company ALTAC-136-1G00 Installation, Operating And Service Instructions

Advertisement

Quick Links

ALTA
Installation, Operating and Service Instructions for
Models:
• ALTAC-136
• ALTAC-200
Manual Contents
1.
Installer Read Before Proceeding . . . . . . . . . . .3
2.
3.
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . .6
4.
How It Works . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
5.
Locating Boiler . . . . . . . . . . . . . . . . . . . . . . . . .10
6.
Preparing Boiler . . . . . . . . . . . . . . . . . . . . . . . .14
7.
General Venting . . . . . . . . . . . . . . . . . . . . . . . . .17
8.
Sidewall Direct Venting . . . . . . . . . . . . . . . . . . .24
9. Vertical Direct Venting . . . . . . . . . . . . . . . . . . .30
10. Heating System Piping . . . . . . . . . . . . . . . . . . .36
11. Domestic Water Piping . . . . . . . . . . . . . . . . . . .39
12. Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
13. Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
14. Condensate Disposal . . . . . . . . . . . . . . . . . . . .46
15. Start-up and Checkout . . . . . . . . . . . . . . . . . .47
16. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
17. Before Leaving Jobsite . . . . . . . . . . . . . . . . . .66
18. Service and Maintenance . . . . . . . . . . . . . . . . .67
19. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . .72
20. Internal Wiring Diagrams . . . . . . . . . . . . . . . . .88
21. Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . .91
Appendix
D. Code Required Text . . . . . . . . . . . . . . . . . . . . . 101
TO THE INSTALLER:
Affix these instructions adjacent to boiler.
Provide model number and serial number when
seeking information and support.
TO THE HOMEOWNER:
Retain these instructions for future reference.
Contact heating installer or technician for all issues
and support.
Version en Español disponible en el web del fabricante.
This boiler must only be installed, serviced, or repaired by a qualified installer, service agency or gas supplier.
Improper installation, adjustment, alteration, service or maintenance can cause severe personal injury, death,
or substantial property damage. For assistance or additional information, consult a qualified installer, service
agency, or the gas supplier. Read these instructions carefully before installing.
110327-05 - 6/22
• Combi Boiler/Water Heater
• Condensing
• Direct Vent
• Gas Fired
Page
www.usboiler.net
!
WARNING

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ALTAC-136-1G00 and is the answer not in the manual?

Questions and answers

Summary of Contents for U.S. Boiler Company ALTAC-136-1G00

  • Page 1: Table Of Contents

    ALTA Installation, Operating and Service Instructions for • Combi Boiler/Water Heater • Condensing • Direct Vent Models: • Gas Fired • ALTAC-136 • ALTAC-200 Manual Contents Page Installer Read Before Proceeding ...3 Homeowner Read Before Proceeding .
  • Page 2 Combi Installation, Operating & Service Instructions ALTA The Massachusetts Board of Plumbers and Gas Fitters has listed the Alta Boiler. See the Massachusetts Board of Plumbers and Gas Fitters website for the latest Approval Code or ask your local Sales Representative. The Commonwealth of Massachusetts requires this product to be installed by a licensed Plumber or Gas fitter.
  • Page 3: Installer Read Before Proceeding

    Combi Installation, Operating & Service Instructions ALTA Installer or Qualified Service Agency Read Before Proceeding NOTICE: Size boiler properly relative to design WARNING heat load or, if using DHW priority, the peak Asphyxiation Hazard, Burn Hazard, Electrical hot water load, whichever is larger. A grossly Shock Hazard.
  • Page 4: Service Record

    Combi Installation, Operating & Service Instructions ALTA SERVICE RECORD DATE SERVICE PERFORMED 110327-05 - 6/22...
  • Page 5: Homeowner Read Before Proceeding

    Combi Installation, Operating & Service Instructions ALTA User/Homeowner Read Before Proceeding DANGER WARNING Asphyxiation Hazard. Fire Hazard. • A qualified installer, service agency or gas supplier should annually inspect boiler including annually inspecting all vent gaskets and replacing any exhibiting damage or deterioration.
  • Page 6: Specifications

    Combi Installation, Operating & Service Instructions ALTA Specifications Table 3-1: Ratings Space Heating Ratings Domestic Hot Water (DHW) Ratings Input (MBH) Input (MBH) Hot Water Draw Limits GPM (L/min) AHRI Model Heating AFUE 70°F 77°F 90°F Number Capacity Rating (39°C) (43°C) (50°C) (MBH)
  • Page 7 Combi Installation, Operating & Service Instructions ALTA Specifications (continued) Table 3-5: Weights and Volume Heat Shipping Empty Boiler Shipping Shipping Shipping Water Exchanger Model Weight Weight Crate D Crate W Crate H Content Surface Number lb (kg) lb (kg) in. (mm) in.
  • Page 8: How It Works

    Combi Installation, Operating & Service Instructions ALTA 12. Boiler supply temperature sensor (UL 353 How It Works Listed) Dual element temperature sensor used to monitor 1. Heat exchanger boiler water exiting heat exchanger. Boiler control Water flows through heat exchanger's stainless uses supply temperature to initiate CH burner steel tubes.
  • Page 9 Combi Installation, Operating & Service Instructions ALTA How It Works (continued) Figure 4-1: How it works 110327-05 - 6/22...
  • Page 10: Locating Boiler

    Combi Installation, Operating & Service Instructions ALTA Locating Boiler 4. Locate boiler to avoid water damage in case there is a leak. If boiler must be located in an Code Requirements area sensitive to water damage, install drain WARNING pan underneath boiler and pipe to a suitable drain location.
  • Page 11: Ventilation Air

    Combi Installation, Operating & Service Instructions ALTA Locating Boiler (continued) Ventilation Air 3. If 24 in. clearances described in (2) cannot be maintained, provide two openings into 1. Combustion air must be obtained directly room, one near floor and other near ceiling. from outdoors, however ventilation openings Top of upper opening to be within 12 in.
  • Page 12: Combustion Air And Venting

    Combi Installation, Operating & Service Instructions ALTA Locating Boiler (continued) 4. If boiler is installed in room with other Table 5-2: Corrosive Combustion Air appliances, provide adequate air for combustion Contaminants and Sources and/or ventilation in accordance with other Contaminants to avoid: appliance manufacturer's instructions and applicable code.
  • Page 13: Residential Garage Installation

    Combi Installation, Operating & Service Instructions ALTA Locating Boiler (continued) Connecting New Boiler to Existing Vent 1. Seal any unused openings in the common venting System system. 2. Visually inspect the venting system for proper size WARNING and horizontal pitch and determine there is no Asphyxiation Hazard.
  • Page 14: Preparing Boiler

    Combi Installation, Operating & Service Instructions ALTA Preparing Boiler Unpack Boiler CAUTION Remove boiler and miscellaneous parts carton from Heavy Object. outer shipping carton. Boiler weighs up to 130 lb (59 kg). Two people are required to lift boiler onto wall mounting CAUTION bracket.
  • Page 15 Combi Installation, Operating & Service Instructions ALTA Preparing Boiler (continued) Install Vent Connector Preparing for Fuel Conversion If using LP gas. LP conversion requires (2) 1. Remove vent connector and screws from steps: gas valve setting adjustment and control miscellaneous parts carton. parameter change.
  • Page 16 Combi Installation, Operating & Service Instructions ALTA Preparing Boiler (continued) 3. For wood studs, drill 3/16 in. (4.8 mm) pilot holes Mount Boiler "A" and "B" and attach bracket using provided 1. Wall bracket is designed to mount on studs 5/16 in.
  • Page 17: General Venting

    Combi Installation, Operating & Service Instructions ALTA General Venting Direct Vent Sidewall Termination Options Figure 7-2: Sidewall Low Figure 7-3: Sidewall Figure 7-1: Sidewall Profile Termination - see Concentric Termination - Termination with Fittings - Section 8 for details see Section 8 for details see Section 8 for details Direct Vent Vertical Termination Options Figure 7-4: Vertical...
  • Page 18 Combi Installation, Operating & Service Instructions ALTA General Venting (continued) 1. Min and max lengths are calculated separately for air and vent. For example, max length 135 ft. (41.1 Vent and Air Sizing m) means up to 135 ft. (41.1 m) air piping and up to 135 ft.
  • Page 19: Cpvc/Pvc Venting

    Combi Installation, Operating & Service Instructions ALTA General Venting (continued) 5. Example equivalent length calculation for 2 in. NOTICE: PVC may not be used to penetrate vent: combustible or non-combustible walls unless all A. 1 ft. CPVC straight pipe =1 eq ft. of the following conditions are met.
  • Page 20 Combi Installation, Operating & Service Instructions ALTA 1/8 in. (3.2 mm) hole in air pipe to align with hole General Venting (continued) in connector. Insert pipe into air connector and use #10 x 1 in. sheet metal screw to secure. Seal 6.
  • Page 21 Combi Installation, Operating & Service Instructions ALTA General Venting (continued) Maximum Wall 2"* 6" 12" Thickness ("T") (50mm) (150mm) (305mm) Minimum air space 0"* 1" 1-3/4" around pipe ("C") (0mm) (25mm) (45mm) One end of opening may *Wall must be of non-combustible construction be closed PVC Vent Pipe 66"...
  • Page 22: Polypropylene Venting

    Combi Installation, Operating & Service Instructions ALTA General Venting (continued) Polypropylene Venting Table 7-16: Listed Polypropylene Vent Materials (ULC-S636 Listed) WARNING Manufacturer Model Asphyxiation Hazard. Polypropylene Single Wall Rigid • Use only vent materials listed in Table 7-16 DuraVent to make vent connections. Consult vent PolyPro Flex manufacturer's instructions for required support InnoFlue Single Wall Rigid...
  • Page 23 Combi Installation, Operating & Service Instructions ALTA General Venting (continued) Table 7-17: Listed Polypropylene Vent Fittings DuraVent Length Centrotherm InnoFlue Selkirk PolyFlue PolyPro 2 in. (60 mm) 2PPS-LC IANS02 PF-LB Joint Connector 3 in. (80 mm) 3PPS-LC IANS03 PF-LB or 4PF-LB 2 in.
  • Page 24: Sidewall Direct Venting

    Combi Installation, Operating & Service Instructions ALTA Sidewall Direct Venting Determine Terminal Location C. Minimum 12 in. (305 mm) from inside corner. 6 ft. (1.8 m) is generally recommended and WARNING required when window and/or air inlet is within Asphyxiation Hazard. 4 ft.
  • Page 25 Combi Installation, Operating & Service Instructions ALTA Sidewall Direct Venting (continued) 110327-05 - 6/22...
  • Page 26 Combi Installation, Operating & Service Instructions ALTA Sidewall Direct Venting (continued) Table 8-3: Polypropylene Sidewall Terminal Fittings CPVC/PVC or Polypropylene Fittings DuraVent Centrotherm Terminal Selkirk PolyFlue PolyPro InnoFlue WARNING UV resistant UV stabilized UV resistant Asphyxiation Hazard. single wall pipe end pipe + two pipe + two 2PF- All CPVC/PVC vent joints must be glued.
  • Page 27 Combi Installation, Operating & Service Instructions ALTA Sidewall Direct Venting (continued) Table 8-7: CPVC/PVC Low Profile Terminal Kits DuraVent & Selkirk: Remove gasket to Length Ipex Diversitech install screen From boiler 2 in. (60 mm) 397984 HVENT-2 Elbow vent connection 3 in.
  • Page 28 Combi Installation, Operating & Service Instructions ALTA Sidewall Direct Venting (continued) CPVC/PVC Concentric Terminal 3. Follow terminal manufacturer's instructions and Figure 8-11 for assembly. WARNING 4. If needed, terminal can be shortened. Follow Asphyxiation Hazard. terminal manufacturer's instructions and Figure All CPVC/PVC vent joints must be glued.
  • Page 29 Combi Installation, Operating & Service Instructions ALTA Sidewall Direct Venting (continued) Kit Size *'A' Manufacturer 7-3/8" (187mm) 1-3/4" (44mm) *Overall length of inner IPEX 3-1/2" (89mm) 2" pipe to be 'A' longer than overall 12-3/16" (310mm) 3/4" (19mm) DIVERSITECH length of outer pipe. 8-3/4"...
  • Page 30: Vertical Direct Venting

    Combi Installation, Operating & Service Instructions ALTA Vertical Direct Venting Determine Terminal Location WARNING WARNING Asphyxiation Hazard. Asphyxiation Hazard. All polypropylene vent systems rely on gaskets Follow these instructions when determining vent for sealing. Ensure gaskets are installed in terminal location. Failure to comply could result each female end of vent pipe or fitting.
  • Page 31 Combi Installation, Operating & Service Instructions ALTA Vertical Direct Venting (continued) Table 9-2: Polypropylene Vertical Terminal Fittings DuraVent & Selkirk: Elbow Remove gasket to DuraVent Centrotherm install screen Joint Selkirk PolyFlue PolyPro InnoFlue Connector Screen UV resistant UV stabilized UV resistant single wall pipe end pipe + pipe + 2PF-...
  • Page 32 Combi Installation, Operating & Service Instructions ALTA Vertical Direct Venting WARNING (continued) Asphyxiation Hazard. CPVC/PVC Concentric Terminal If using stainless steel screw to attach rain cap, always drill clearance hole in rain cap WARNING and pilot hole in vent pipe appropriate for Asphyxiation Hazard.
  • Page 33 Combi Installation, Operating & Service Instructions ALTA Vertical Direct Venting (continued) Abandoned B-vent Chase Polypropylene Concentric Terminal WARNING WARNING Asphyxiation Hazard. • Only abandoned (unused) B-vent may Asphyxiation Hazard. be used as a chase. Failure to comply All polypropylene vent systems rely on gaskets may cause product damage or improper for sealing.
  • Page 34 Combi Installation, Operating & Service Instructions ALTA Centrotherm Innoflue Vertical Direct Venting (continued) IFBK02 or IFBK03 (3.1m) B-Vent Kit Table 9-11: Polypropylene B-vent Chase B-Vent 24" (610mm) Components Flashing 12" (305mm) DuraVent Centrotherm Normal snow Selkirk PolyFlue line on roof PolyPro InnoFlue 2PF-10UV or...
  • Page 35 Combi Installation, Operating & Service Instructions ALTA Vertical Direct Venting Vent (continued) Note: Duravent Polypro Flex Abandoned Chimney Chase components shown. WARNING Asphyxiation Hazard. PPs Flex Only abandoned (unused) masonry chimney may be used as a chase. If chimney contains Clean, tight unused chimney multiple flues, all flues must be abandoned.
  • Page 36: Heating System Piping

    Combi Installation, Operating & Service Instructions ALTA Heating System Piping If replaced, replacement must have a setting General System Piping Precautions less than or equal to maximum allowable WARNING working pressure (MAWP) shown on ASME data plate located on left side of heat Asphyxiation Hazard.
  • Page 37 Combi Installation, Operating & Service Instructions ALTA Heating System Piping (continued) 5. Automatic air vent (required) B. This is a water tube boiler and this flow switch A. Factory installed manual air vent is included is therefore only effective way to provide on boiler heat exchanger, to vent heat such protection.
  • Page 38 Combi Installation, Operating & Service Instructions ALTA Heating System Piping (continued) 110327-05 - 6/22...
  • Page 39: Domestic Water Piping

    Combi Installation, Operating & Service Instructions ALTA Domestic Water Piping NOTICE: Elbows pointed toward back of boiler DANGER are recommended to start DHW piping. Scald Hazard. • Under certain conditions this boiler DHW components in this system and their functions are can deliver domestic hot water (DHW) at as follows: temperatures in excess of DHW set point on...
  • Page 40 Combi Installation, Operating & Service Instructions ALTA Domestic Water Piping (continued) 110327-05 - 6/22...
  • Page 41 Combi Installation, Operating & Service Instructions ALTA Domestic Water Piping (continued) 110327-05 - 6/22...
  • Page 42: Gas Piping

    Combi Installation, Operating & Service Instructions ALTA Gas Piping WARNING DANGER Explosion Hazard. Explosion Hazard. • Failure to properly pipe gas supply to boiler Do not use matches, candles, open flames or could cause improper operation or leaks of other ignition sources to check for leaks. Failure flammable gas resulting in severe personal to comply could result in severe personal injury, injury, death or substantial property damage.
  • Page 43: Field Wiring

    Combi Installation, Operating & Service Instructions ALTA Field Wiring Locating Field Connection Terminal Strips DANGER Field connection terminal strip locations are shown in Electrical Shock Hazard. Figure 13-1. To access terminal strips: • Disconnect electrical supply before installing or performing maintenance. 1.
  • Page 44: Low Voltage Connections

    Combi Installation, Operating & Service Instructions ALTA Field Wiring (continued) Low Voltage Connections 1. All low voltage field connections to boiler are made on Low Voltage Connections terminal strip (see Figure 13-3) located on left side of bottom panel. Route all low voltage wiring through conduit knock out holes located on left side in 120V Boiler...
  • Page 45 Combi Installation, Operating & Service Instructions ALTA Field Wiring (continued) 2. External power must not be applied to any low E. Recirculation (Header) Temperature Sensor - voltage terminals - doing so may damage boiler When optional sensor is installed and control.
  • Page 46: Condensate Disposal

    Combi Installation, Operating & Service Instructions ALTA Condensate Disposal C. If point of condensate disposal is above trap, WARNING it will be necessary to use a condensate Asphyxiation Hazard. pump to move condensate from boiler to Failure to install condensate drain in drain.
  • Page 47: Start-Up And Checkout

    Combi Installation, Operating & Service Instructions ALTA Start-Up and Checkout Heating System Cleaning and Treatment Fill Water Quality CAUTION NOTICE: Make sure system is filled with water meeting the following criteria: Component Damage. Proper flushing, cleaning, and water side • Hardness less than 7 grains/gallon. maintenance is highly recommended to protect •...
  • Page 48 Combi Installation, Operating & Service Instructions ALTA Start-Up and Checkout (continued) 4. Eliminate air in boiler by bleeding from heat 3. Inspect all wiring for loose, uninsulated or exchanger manual air vent on top left side of heat miswired connections. exchanger (Figure 15-1).
  • Page 49: High Altitude Conversion

    Combi Installation, Operating & Service Instructions ALTA Start-Up and Checkout (continued) LP Conversion 3. Use keypad to enter adjust mode and change parameter A06 from "0" to "1". WARNING Press and hold "menu" for 3 seconds. • Asphyxiation Hazard. Press "" or "" buttons until PAS is visible •...
  • Page 50 Combi Installation, Operating & Service Instructions ALTA Start-Up and Checkout (continued) Final Check Before Starting Boiler (continued) 1. Start boiler using lighting instructions in Figure 15-10. With boiler powered up, and with no call for heat, display should look like Figure 15-5. Once a call for heat is present, it will look like Figure 15-6.
  • Page 51 Combi Installation, Operating & Service Instructions ALTA Start-Up and Checkout (continued) 9. Check inlet gas pressure (Figure 15-9). B. Measure carbon monoxide (CO) level after Verify inlet gas pressure is between upper and 5 minutes of operation above 50% firing rate. lower limits shown on rating label with all gas This can be done by providing DHW demand.
  • Page 52 Combi Installation, Operating & Service Instructions ALTA 10.00 Start-Up and Checkout (continued) FOR YOUR SAFETY READ BEFORE OPERATING/POUR VOTRE × × × × SECURITE LISEZ AVANT DE METTRE EN MARCHE WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
  • Page 53: Boiler Sequence Of Operation

    Combi Installation, Operating & Service Instructions ALTA Start-Up and Checkout (continued) Boiler Sequence of Operation Table 15-11: Boiler Sequence of Operation Status Screen Display Description Burner - Off Pump(s) - Off Three Way Valve - DHW Priority: Standby There is no call for heat, boiler is not firing and priority is "standby". Boiler is ready to Status: respond to a call for heat.
  • Page 54: Operation

    Combi Installation, Operating & Service Instructions ALTA Operation User Display Overview reset – Figure 16-1: Display Icons Table 16-2: Display Descriptions When not flashing or alternating display temperature is: 120°F • DHW outlet temperature during DHW priority. • Boiler supply temperature at all other times. Visible when Central Heat demand is present.
  • Page 55: Operating Mode

    Combi Installation, Operating & Service Instructions ALTA Operation (continued) Operating Mode The STA (status) display code contains below listed Basic boiler status is displayed and DHW setpoint values. may be adjusted. Table 16-5 Managing of Status Numbers Description (see Section 19 reset Display Troubleshooting for explanation)
  • Page 56 Combi Installation, Operating & Service Instructions ALTA Operation (continued) Adjust Mode Menu Diagnostic information and Quick Menu parameters are available without entering a password. Press and Hold “menu” button for 3 seconds to access Adjust Mode. reset Press Press buttons buttons to view next to adjust...
  • Page 57: Navigating Menus

    Combi Installation, Operating & Service Instructions ALTA Operation (continued) Accessing Password Protected Menus Password protected parameters are available by entering a password. Press and hold the "menu" for 3 seconds, reset Press "" or "" buttons until PAS is visible and press "enter". Press "enter"...
  • Page 58 Combi Installation, Operating & Service Instructions ALTA Operation (continued) Table 16-11: Menu A A , Quick Menu (items A06, A07, A08 and A09 visible only after password entered) Range/ Default Parameter and Description Choices A01 Boiler On/Off Switch On/Off Boiler switch allows an installer to prevent boiler starts while boiler powered and reviewing boiler settings.
  • Page 59 Combi Installation, Operating & Service Instructions ALTA Operation (continued) Table 16-12: Menu FR FR, Firing Rate (visible only after password entered) Range/ Default Parameter and Description Choices F01 Manual Modulation Enable Setting to "On" allows technician to fire at rate specified in F02. To return to Auto change setting to "Off".
  • Page 60 Combi Installation, Operating & Service Instructions ALTA Operation (continued) Table 16-13: Menu 5P 5P, , Setpoint Menu (visible only after password entered) Range/ Default Parameter and Description Choices 501 Temperature Units Sets display temperature in degrees Fahrenheit or Celsius. 0, 1 Fahrenheit Celsius 502 DHW Priority Time...
  • Page 61 Combi Installation, Operating & Service Instructions ALTA Operation (continued) Table 16-15: Menu PU PU, Pump Menu (visible only after password entered) Range/ Default Parameter and Description Choices P01 System Pump Output Select: Activates System Pump output according to selected function. System Pump Any Pump Runs during any call for heat.
  • Page 62 Combi Installation, Operating & Service Instructions ALTA Operation (continued) Table 16-16: Menu LL LL, Lead Lag Menu (visible only after password entered) Range/ Default Parameter and Description Choices L01 Lead Lag Master Enable [NOT FOR COMBI BOILERS] Used to "turn on" Multiple Boiler Controller On/Off Sequencer Master is Enabled.
  • Page 63: Control System Overview

    Combi Installation, Operating & Service Instructions ALTA Operation (continued) This section covers control features available via local display. For additional control features available via our App, see Extended Features Manual available on our website or in our App. Control System Overview 6.
  • Page 64: Boiler Protection Features

    Combi Installation, Operating & Service Instructions ALTA Operation (continued) 12. Priority Demand 2. High Differential Temperature Limit Control accepts a call for heat from multiple Control monitors temperature difference between places and responds to its "Priority". When more return and supply sensors. If this difference than one demand is present, higher priority exceeds 58°F (32°C) control begins to reduce demand is used to determine active boiler...
  • Page 65 Combi Installation, Operating & Service Instructions ALTA Operation (continued) Boiler Protection Features (continued) 11. Central Heating System Frost Protection 7. Flue High Limit Frost Protection starts boiler and system pump Control monitors flue gas temperature sensor and fires boiler when low outdoor air, low supply located at top of heat exchanger.
  • Page 66: Before Leaving Jobsite

    Combi Installation, Operating & Service Instructions ALTA Before Leaving Jobsite Before leaving jobsite Installed ASSE 1017 or 1070 tempering valve  Installed wall retaining clips (bottom)  Flushed heating system  Boiler and system filled with water  Air purged from boiler system ...
  • Page 67: Service And Maintenance

    Combi Installation, Operating & Service Instructions ALTA Service and Maintenance Important Product Safety Information: Refractory Ceramic Fiber Product WARNING Some boiler components use materials that contain refractory ceramic fibers (RCF). RCF has been classified as a possible human carcinogen. When exposed to elevated temperatures, RCF may change into crystalline silica, a known carcinogen.
  • Page 68: Monthly Inspections

    Combi Installation, Operating & Service Instructions ALTA Service and Maintenance (continued) Monthly Inspections: WARNING 1. Inspect vent piping and air intake piping to Asphyxiation Hazard. Fire Hazard. Explosion verify it is free from leakage and deterioration. Hazard. Also verify vent and air intake terminals are •...
  • Page 69: Inspect Burner

    Combi Installation, Operating & Service Instructions ALTA Service and Maintenance (continued) 7. Inspect ignitor/flame sensor. A. Clean off any deposits found with steel wool. Do not use sand paper or Emory cloth for this cleaning. B. Inspect ceramic portion for cracks and replace ignitor/flame sensor if any are found.
  • Page 70 Combi Installation, Operating & Service Instructions ALTA Service and Maintenance (continued) 9. Inspect and clean condensate trap. WARNING A. Place bucket under condensate clean out Component Damage. cap on bottom of boiler (Figure 18-5) to catch Do not over tighten burner door mounting nuts. water in trap as well as ball and support.
  • Page 71 Combi Installation, Operating & Service Instructions ALTA Service and Maintenance (continued) 14. Inspect safety relief valve. WARNING Explosion Hazard. Safety relief valves require periodic maintenance. Refer to relief valve manufacturer's instructions for frequency and proper procedure. Any testing or maintenance shall be done by a qualified installer, service agency or gas supplier..
  • Page 72: Troubleshooting

    Combi Installation, Operating & Service Instructions ALTA Troubleshooting WARNING Electrical Shock Hazard. Turn off power to boiler before working on wiring. A. Troubleshooting with No Active Fault Code Displayed Table 19-1: Troubleshooting with No Active Fault Code Indication Possible Causes Corrective Action Display Completely Check breaker and wiring between breaker panel and...
  • Page 73 Combi Installation, Operating & Service Instructions ALTA Troubleshooting (continued) Table 19-1: Troubleshooting with No Active Fault Code (continued) Indication Possible Causes Corrective Action Draw rate exceeds combi's rated Verify draw rate and temperature rise are both at capacity. or below ratings shown in Table 3-1. Verify there is no debris or build up in flow limiter DHW flow limiter is dirty or clogged.
  • Page 74 Combi Installation, Operating & Service Instructions ALTA Troubleshooting (continued) In event of high CO (CO air free greater than 200 ppm for 0-2,000 ft. (0-610 m) or greater than 300 ppm for above 2,000 ft. (610 m)) follow below steps in specified order: 1.
  • Page 75 Combi Installation, Operating & Service Instructions ALTA Troubleshooting (continued) B. Troubleshooting with Status Numbers In Operating Mode, use arrow keys ("" or "") to reach "StA". Display will then alternate between "StA" and number shown below. Table 19-2: Status Number Explanation Display Description Explanation...
  • Page 76 Combi Installation, Operating & Service Instructions ALTA Troubleshooting (continued) C. Troubleshooting with Diagnostic Codes In Diagnostic and Quick Menu Mode, use the arrow keys ("" or "") to reach "c" menu and press "enter" button to view diagnostic codes. Table 19-3: Diagnostic Menu Display Name Description...
  • Page 77 Combi Installation, Operating & Service Instructions ALTA Troubleshooting (continued) D. Troubleshooting with Active Fault Code. Control uses following codes to describe abnormal operation: Table 19-4: Lockout/Hold/Warning Symbol Description Code Type Boiler Status Description When a lockout occurs, boiler will shut down and event is stored in history, b, menu.
  • Page 78 Combi Installation, Operating & Service Instructions ALTA Troubleshooting (continued) Table 19-5: Active Fault Code and Corrective Actions (continued) Detailed Fault Code found on "b" and "c" menus in brackets, e.g. [1.0]. Code Name Possible Cause Corrective Action Verify the system is full of water and the air has been properly purged.
  • Page 79 Combi Installation, Operating & Service Instructions ALTA Troubleshooting (continued) Table 19-5: Active Fault Code and Corrective Actions (continued) Detailed Fault Code found on "b" and "c" menus in brackets, e.g. [1.0]. Code Name Possible Cause Corrective Action Inspect heat exchanger and clean flue side of heat Heat exchanger dirty.
  • Page 80 Combi Installation, Operating & Service Instructions ALTA Troubleshooting (continued) Table 19-5: Active Fault Code and Corrective Actions (continued) Detailed Fault Code found on "b" and "c" menus in brackets, e.g. [1.0]. Code Name Possible Cause Corrective Action • Remove jumper from air proving switch. Defective air proving •...
  • Page 81 Combi Installation, Operating & Service Instructions ALTA Troubleshooting (continued) Table 19-5: Active Fault Code and Corrective Actions (continued) Detailed Fault Code found on "b" and "c" menus in brackets, e.g. [1.0]. Code Name Possible Cause Corrective Action [18.0] Application Normal condition following a parameter download, set Factory parameters are not valid.
  • Page 82 Combi Installation, Operating & Service Instructions ALTA Troubleshooting (continued) Table 19-5: Active Fault Code and Corrective Actions (continued) Detailed Fault Code found on "b" and "c" menus in brackets, e.g. [1.0]. Code Name Possible Cause Corrective Action No gas, insufficient gas supply Verify no air in gas line.
  • Page 83 Combi Installation, Operating & Service Instructions ALTA Troubleshooting (continued) Table 19-5: Active Fault Code and Corrective Actions (continued) Detailed Fault Code found on "b" and "c" menus in brackets, e.g. [1.0]. Code Name Possible Cause Corrective Action Hardware Fault Control damaged. Check control, cycle power, replace if necessary.
  • Page 84 Combi Installation, Operating & Service Instructions ALTA Troubleshooting (continued) Table 19-6: Detailed Fault Code (found on"c" and "b" menus) Detailed Code Type Condition Code Anti-short cycle boiler start delay, while thermostat demand present, boiler has H01.0 Warning cycled off and restart is delayed. Urgent calibration cooling delay.
  • Page 85 Combi Installation, Operating & Service Instructions ALTA Troubleshooting (continued) Table 19-6: Detailed Fault Code (found on"c c " and "b b " menus, continued) Detailed Code Type Condition Code H17.0 Hold Control in program mode. H17.1 Hold Internal Safety Core error. E17.2 Lockout Parameter CRC error.
  • Page 86 Combi Installation, Operating & Service Instructions ALTA Troubleshooting (continued) Table 19-6: Detailed Fault Code (found on"c c " and "b b " menus, continued) Detailed Code Type Condition Code H24.0 Warning Flame signal loss in operation. H24.1 Hold Flame signal loss in stabilization phase. H24.2 Hold Flame signal loss in safety time.
  • Page 87 Combi Installation, Operating & Service Instructions ALTA Troubleshooting (continued) Table 19-7: Supply, DHW, Return Header and Table 19-8: Outdoor Air Temperature Sensor Flue Temperature Sensor Temperature versus Temperature versus Resistance (10 kOhm) Resistance (10 kOhm) Outdoor Temperature Ohms of Temperature Ohms of Resistance °F...
  • Page 88: Internal Wiring Diagrams

    Combi Installation, Operating & Service Instructions ALTA Internal Wiring Diagrams 110327-05 - 6/22...
  • Page 89 Combi Installation, Operating & Service Instructions ALTA Internal Wiring Diagrams (continued) 110327-05 - 6/22...
  • Page 90 Combi Installation, Operating & Service Instructions ALTA Internal Wiring Diagrams (continued) Figure 20-2: Ladder Diagram 110327-05 - 6/22...
  • Page 91: Service Parts

    All service parts may be obtained through your local U.S. Boiler Company Wholesale distributor. Should you require assistance in locating a U.S. Boiler Company Distributor in your area, or have questions regarding the availability of U.S. Boiler Company products or service parts, please contact us at 1-888-432-8887 or Fax (717) 481- 8408 or at www.usboiler.net.
  • Page 92 X.X ±.1 X.XXX ±.005 FIRST USE: X.XX ±.03 ANGLE ±1° ALTA PROPERTY OF TITLE: U.S. Boiler Company, Inc. SERVIC LANCASTER, PA PIPING, GASKETS THIS DOCUMENT CONTAINS CONFIDENTIAL INFORMATION AND ITS CONTENTS ARE THE SOLE PROPERTY OF U.S. BOILER COMPANY, INC. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF U.S.
  • Page 93 Combi Installation, Operating & Service Instructions ALTA Service Parts (continued) UNLESS OTHERWISE NOTED: ALL DIMENSIONS IN INCHES. TOLERANCES: X.X ±.1 X.XXX ±.005 X.XX ±.03 ANGLE ±1° PROPERTY OF U.S. Boiler Compa LANCASTER, PA THIS DOCUMENT CONTAINS CONFIDENTIA AND ITS CONTENTS ARE THE SOLE PROPER Part Number COMPANY, INC.
  • Page 94 Combi Installation, Operating & Service Instructions ALTA Service Parts (continued) Part Number Key No. Description 136 Combi 200 Combi 31A, 31B, 31C, 31D, 31E, 31F, Condensate Trap 110589-01 31G, 31H Front Door 110595-01 Vent connector 107160-01 Side panel 110725-01 111565-01 45, 46 Wall brackets 110882-01...
  • Page 95 Key No. Description 136 Combi 200 Combi Control Enclosure 111597-01 Boiler Control 111759-01 Contact U.S. Boiler Company; Provide boiler serial number Model Key 120 VAC Connection Board 110726-01 Low Voltage Connection Board 110594-01 Fuse, 0.5A, 5 x 20mm, 250V, Slow Blow Fuse, 1.0A, 5 x 20mm, 250V, Slow Blow...
  • Page 96 Combi Installation, Operating & Service Instructions ALTA Service Parts (continued) Part Number Key No. Description 136 Combi 200 Combi Ignition Harness 110598-01 Main Control Harness 110599-01 Power Harness Part Number Accessories Description 136 Combi 200 Combi 2 in. CPVC/PVC Vent Kit 107039-01 3 in.
  • Page 97: Combination Refrigeration/Heating System

    Combi Installation, Operating & Service Instructions ALTA Appendix A. Combination Refrigeration/Heating System 2. If boiler is connected to heating coils located in 1. If boiler is used in connection with refrigeration air handling units where they may be exposed to systems, boiler must be installed with chilled refrigerated air, boiler piping must be equipped medium piped in parallel with the heating boiler...
  • Page 98: Water Quality And Boiler Additives

    Combi Installation, Operating & Service Instructions ALTA Appendix B. Water Quality and Boiler Additives Other non-metallic tubing is equipped with an The heat exchanger used in this boiler is made oxygen barrier to prevent migration of oxygen from stainless steel coils having relatively narrow into water.
  • Page 99: Special Requirements For Side-Wall Vented Appliances In The Commonwealth Of Massachusetts

    Combi Installation, Operating & Service Instructions ALTA Appendix C. Special Requirements For Side-Wall Vented Appliances In The Commonwealth of Massachusetts IMPORTANT The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 4.00 and 5.00 for installation of side-wall vented gas appliances as follows: (a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) ft.
  • Page 100 Combi Installation, Operating & Service Instructions ALTA Appendix C. Special Requirements For Side-Wall Vented Appliances In The Commonwealth of Massachusetts (continued) (c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:1.
  • Page 101: Code Required Text

    Combi Installation, Operating & Service Instructions ALTA Appendix D. Code Required Text See Section 5 Locating Boiler: Remove Existing Boiler 6. Une fois qu'il a été déterminé, selon la méthode indiquée ci-dessus, que chaque for context of following text: appareil raccordé au système d'évacuation Les instructions doivent comprendre le mode est mis à...
  • Page 102: Service Record

    Combi Installation, Operating & Service Instructions ALTA SERVICE RECORD DATE SERVICE PERFORMED 110327-05 - 6/22...
  • Page 103 Combi Installation, Operating & Service Instructions ALTA SERVICE RECORD DATE SERVICE PERFORMED 110327-05 - 6/22...
  • Page 104 Combi Installation, Operating & Service Instructions ALTA U.S. Boiler Company, Inc. P.O. Box 3020 Lancaster, PA 17604 1-888-432-8887 www.usboiler.net 110327-05 - 6/22...

This manual is also suitable for:

Altac-200Altac-136

Table of Contents