Series. Surface Mounted Range INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS English Scan to download the user guide and App T9901009-2-2T UK (v10) Page | 1...
SAFETY Electrical Supply and Wiring to the Air Curtain All electrical wiring and connections MUST be carried out by a competent qualified electrician in accordance with the latest edition of national and local wiring regulations and/or local statutory regulations. “Danger: Disconnect electrical supply before servicing” A 1 phase or 3 phase local isolator having a contact separation of at least 3mm on all poles •...
INTRODUCTION Established in the 1960s, Thermoscreens is a leading air curtain manufacturer that exports to over 60 countries worldwide. As with all our products, the T range of air curtains is designed with energy efficiency in mind. T models suffixed E, W or A are designed to be surface mounted inside a building and located horizontally over a doorway.
DELIVERY CONTENTS The following items are supplied in the box at delivery. NOTE: If any parts are missing or damaged contact your place of purchase. Ambient Remote Switch T Surface Mounted Air Curtain Touch Remote Control (for Ambient units) (for Electric and Water Heated units) Note: End caps are supplied loose to Supplied with 6m RJ be fitted during installation...
INSTALLATION The air curtain is designed to be located horizontally over a doorway. It must not be installed outside of the building. Location Mount the air curtain above and as close to the doorway as possible, with: 100mm the discharge grille not more than 3m above floor level •...
Water flow rates and pressure drops at different water temperatures can be calculated using the Thermoscreens coil calculation programme. Visit the Thermoscreens website for details. T9901009-2-2T UK (v10)
The installer must connect the 3-port valve in the heating pipework as shown in Figure 4 below: 22mm pipe 22mm pipe 22mm pipe 22mm pipe wire valve to pcb inside air curtain Fig 4 ACCESS FOR ELECTRICAL CONNECTION How to access terminals To gain access to the air curtain for connection and commissioning, remove air inlet grilles and bottom access panel as explained below.
REMOTE CONTROL INSTALLATION Mount the Touch Controller in a convenient position directly to the wall or onto a switch box. Wall mounting Step 1 Press release button on side of Controller case and pull the back case away (see Fig 7). Step 2 Feed one end of the RJ control cable through the back case, secure it, then screw the back case to the wall using suitable fixings (not...
NOTE: The Controller must stay plugged-in for the air curtain to keep working. An optional plug-in EEPROM is available from Thermoscreens so the Remote Control can be un- plugged and the air curtain stay working. Visit the Thermoscreens website for details.
To promote increased energy saving a more advanced weather compensation control strategy is available from Thermoscreens. Using a heating curve, the discharge air temperature of the airstream coming from the air curtain is controlled against the outside air temperature. Visit the Thermoscreens website for details.
NOTE: Black rectangle is moveable head of DIP switch. NOTE: A range of advanced factory fitted and plug-in control options are available from Thermoscreens to enhance the performance of the CCS PCB controller inside the air curtain. These include advanced ®...
14. FAN SPEED SELECTION If required, select fan speed at commissioning to suit outdoor environmental conditions and indoor noise levels. Factory settings for the 3 fan speeds are as follows: • HIGH fan speed (black wire) is wired into motor tapping •...
15. REMOTE CONTROL OPERATION 15.1 Remote Control Switch (for Ambient units) 1 On/Off Turns the air curtain fans On or Off. 2, 3 & 4 Fan speed Switch fan speed between Low, Medium and High respectively. T9901009-2-2T UK (v10) Page | 14...
Page 15
15.2 Touch Controller (for Electric and Water Heated units) Please scan QR code and follow links to access the user guide and download App. Home Speed Up Down Controller connected via RJ communications lead to CCS PCB with Home, Speed, Up and Down touchpads below the LCD screen as detailed above.
Fan speed Short press Switch touchpad to switch and cycle fan speed: • low • Medium • High Date and Time Settings Configure Date and Time settings either via App or on Controller as below. Turn Controller ON and hold Speed touchpad for 2 seconds Follow instructions on LCD screen with: Tap Up touchpad to increase value •...
Recommend that the doorway should be closed whenever possible but that during times of high pedestrian use it will become an ‘open doorway’. The air curtain then serves an essential purpose by saving energy and providing comfort to occupants. Explain that the inlet grilles and air filters (if fitted) must be cleaned regularly and the unit serviced at schedule intervals –...
19.2 Every 3 months WARNING: Before servicing, isolate and disconnect the air curtain from the electrical power. WARNING: The following servicing and maintenance must be carried out by a competent electrician or a Thermoscreens appointed technician. T9901009-2-2T UK (v10) Page | 18...
Failing this please contact the Thermoscreens warranty department. Care has been taken in compiling these instructions to ensure they are correct. Thermoscreens disclaims all liability for damage resulting from any inaccuracies and/or deficiencies in this documentation. Thermoscreens retain the right to change the specifications stated in these instructions.
21. DECLARATION OF CONFORMITY Carver International Ltd T/A Thermoscreens St Mary’s Road Nuneaton Warwickshire CV11 5AU United Kingdom Telephone: +44 (0)24 7638 4646 www.thermoscreens.com EC DECLARATION OF CONFORMITY as defined by the EC Council Directive on Machinery 2006/42/EC, the Low Voltage Directive 2014/35/EC, Electromagnetic Compatibility Directive 2014/30/EC,...