Page 4
Nothing contained in this document shall increase the liability or extend the warranty obligations of the manufacturer Arcteq Relays Ltd. The manufacturer expressly disclaims any and all liability for any damages and/or losses caused due to a failure to comply with the instructions contained herein or caused by persons who do not fulfil the aforementioned requirements.
Page 8
Figure. 4 - 1. Arc protection device AQ-110PLV. The AQ-110PLV is designed according to the latest protection relay standards and is therefore suitable for installations in rough environments. These include utilities and power plants (both traditional and renewable), various heavy industry applications (off-shore, marine, oil, gas, mining, steel, etc.) as well as commercial and institutional electrical systems.
Page 9
5 Device features AQ-110PLV is an arc flash protection device which can be applied to a variety of applications. The device can be used on their its own as a stand-alone device, or as a part of a more complex arc protection system by using binary inputs and outputs to connect multiple AQ 100 series devices together.
Page 10
Version: 2.05 6 Connections The figure below depicts the connections of AQ-110PLV. Please note that the SF relay is in the de- energized position; also note that the device has been halved for the image to allow for space for all connector descriptions.
Page 16
No external mounting plates are needed regardless of the mounting type. However, you can use mounting brackets, such as Arcteq's sensor bracket accessory, for installation. See the Using the sensor bracket chapter for more information.
Page 17
No external mounting plates are needed regardless of the mounting type. However, you can use mounting brackets, such as Arcteq's sensor bracket accessory, for installation. See the Using the sensor bracket chapter for more information.
Page 18
If necessary, the ends of an AQ-07 cable can be ordered with heat shrinking tubing to avoid light detection outside the protected zone. The covered area can be one (1) or two (2) meters by default; if other lengths are required, please consult the Arcteq sales team. You can find the Contact and reference information chapter at the end of this manual.
Page 21
"100 ms / 150 ms" DIP switch. CBFP logic depends on the selected logic scheme. See Circuit breaker failure protection chapter for more information. Figure. 8.2 - 18. DIP switch diagram for AQ-110PLV. Table. 8.2 - 4. DIP switch settings for SW1 group. ON (le ON (left ft...
Page 22
The schemes described below are the most commonly used ones for this device. However, additional schemes are also available; please contact your nearest Arcteq representative for more information on those schemes. The schemes are configured using the first DIP switch group (SW1) and its switches numbered 1…4 ("Scheme selection") and 5 ("a or b").
Page 24
The logic scheme SS:0a is designed for selective incoming feeder arc protection. It can be used for substations with one or more incoming feeders. Figure. 8.3.1 - 20. Example application with AQ-110PLV (SS:0a). If a fault is detected in the incoming feeder cable compartment (S1), circuit breakers on both sides of the transformer will be tripped with T1 and T2.
Page 27
AQ-110 devices installed to other incoming feeders. Figure. 8.3.2 - 23. Example application with AQ-110PLV (SS:0b). If a fault is detected in the incoming feeder cable compartment (S1), circuit breakers on both sides of the transformer will be tripped with T1 and T2.
Page 29
This scheme is a modification of SS:0a. AQ-1000 arc quenching device is not tripped from S1 channel in this scheme. Figure. 8.3.3 - 26. Example application with AQ-110PLV (SS:1a). If a fault is detected in the incoming feeder cable compartment (S1), circuit breakers on both sides of the transformer will be tripped with T1 and T2.
Page 31
BI1 is used for receiving overcurrent signals AQ-110 devices installed to other incoming feeders. Figure. 8.3.4 - 29. Example application with AQ-110PLV (SS:1b). If a fault is detected in the incoming feeder cable compartment (S1), circuit breakers on both sides of the transformer will be tripped with T1 and T2.
Page 33
Figure. 8.3.5 - 32. Example application with AQ-110PLV (SS:2a). If a fault is detected in the incoming feeder cable compartment (S1), circuit breakers on both sides of the transformer will be tripped with T1 and T2 and the tie breaker will be tripped with T3 (if applicable).
Page 35
BI1 is used for receiving overcurrent signals AQ-110 devices installed to other incoming feeders. Figure. 8.3.6 - 35. Example application with AQ-110PLV (SS:2b). If a fault is detected in the incoming feeder cable compartment (S1), circuit breakers on both sides of the transformer will be tripped with T1 and T2 and the tie breaker will be tripped with T3 (if applicable).
Page 38
8.6 LED indicator functions The AQ-110PLV device has nineteen (19) indication LEDs on the device's front panel. Apart from the "Power" and "Error" LEDs, the user can write their own identifications for each of the remaining LEDs on the text insert located in the transparent pocket next to the LEDs.
Page 50
If you want to have more information of these tests, please refer to the routine test reports sent with the AQ-110 device and/or consult your nearest Arcteq representative for the type test reports.
Need help?
Do you have a question about the AQ-110PLV and is the answer not in the manual?
Questions and answers