Page 1
VX4 Wired Series User Guide Wired Energy Management Thermostat with Built-In Occupancy Sensor...
Page 2
Table of Contents Introduction ........................6 SKUs Referenced in this Manual ...................7-12 Equipment Nomenclature ......................13 Installation Considerations......................14 Network Installation (SKUs ending in ‘XMF’) ............15 Notice ............................... 15 Connecting the Antenna Module..................... 16 Connecting the Ethernet Cable....................16 Powering the Server ......................... 16 Configuring the Online Connection Kit .................
Page 3
Table of Contents Setting the Mesh ID .......................... 32 Entering the Room Number ......................33 Configuring the Equipment Type..................... 34 Configuring Energy Savings Settings ..................35 Setting the Thermostat Clock ....................36 Testing the Thermostat ........................37 Replacing Thermostat Batteries ....................38 Configuration &...
Page 4
Table of Contents Custom Energy Savings Settings ..............53-103 Energy Settings Index ........................53 Using the Thermostat Settings Screens ................. 54-66 01 – FAN CONTROL MODE ........................67 02 – 1 STAGE DIFFERENTIAL - HEAT ....................68 03 – 2 STAGE DIFFERENTIAL - HEAT....................69 04 –...
Page 5
Table of Contents 32 – AUTO FAN SPEED 1ST STAGE DIFFERENTIAL ..............98 33 – AUTO FAN SPEED 2ND STAGE DIFFERENTIAL ..............99 34 – TEMPERATURE CALIBRATION ....................100 35 – AUTOMODE TYPE ..........................101 36 – HUMIDITY CONTROL IN OCCUPIED ROOM ..............102 37 – HEAT EQUIPMENT LOCKOUT ....................103 Troubleshooting ......................104 Restoring Factory Settings ........................104 Specific Applications ....................105...
Page 6
Introduction Verdant VX Series Energy Management Thermostats deliver unprecedented energy savings without compromising the comfort of occupants. An integrated occupancy sensor uses a combination of motion and thermal sensing technologies for accurate occupancy detection. Reliable occupancy detection allows for energy savings when rooms are unoccupied. Energy saving presets eliminate the guesswork and make it easy to adjust the energy saving settings.
Page 7
Introduction SKUs Referenced in this Manual This user guide includes instructions on how to install each of the following compatible SKUs. Product Type SKU(s) Description VX4 Wired Energy Management Thermostat PIR VX4-TR-B Occupancy Detection, Black VX4 Wired Energy Management Thermostat PIR VX4-TVF-B Occupancy Detection, Native VRF Integration, Black VX4 Wired Energy Management Thermostat PIR...
Page 8
Introduction SKUs Referenced in this Manual (cont’d) Product Type SKU(s) Description VX4 Wired Energy Management Thermostat PIR VX4-TVF-B-LG- Occupancy Detection, Native VRF Integration, Black, LG VRF, with Wireless Web Based Remote Management VX4 Wired Energy Management Thermostat PIR NETWORKED VX4 VX4-TVF-B- Occupancy Detection, Native VRF Integration, Black, THERMOSTATS...
Page 9
Introduction SKUs Referenced in this Manual (cont’d) Product Type SKU(s) Description VX4 Wired Smart 7-Day Programmable Thermostat, VX4-NTVF-B-MIE- Native VRF Integration, Black, Mitsubishi & Trane VRF, with Wireless Web Based Remote Management VX4 Wired Smart 7-Day Programmable Thermostat, NETWORKED VX4 VX4-NTVF-B-LG- Native VRF Integration, Black, LG VRF, with Wireless THERMOSTATS...
Page 10
Introduction SKUs Referenced in this Manual (cont’d) Product Type SKU(s) Description Wire Harness for VX3, VX4 & ZX Low Voltage $830-00029-00 Controller Wire Harness & Screw Assembly Kit for VX4 Wired Wire Harnesses 0092 111400 Thermostat White Wire Harness & Screw Assembly Kit for VX4 Wired 0092 111300 Thermostat Black...
Page 11
Introduction Equipment Nomenclature Before you begin installing Verdant equipment, we recommend you familiarize yourself with the various components that may be included in your shipment. Online Connection Kit VX Thermostat Door/Window Sensor Occupancy Sensor Adaptor for VRF Systems...
Page 12
Introduction Installation Considerations Selecting the appropriate installation location of the thermostat and any accessories is crucial to the proper operation of your Verdant energy management system. The following guidelines should be adhered to in all cases; THE THERMOSTAT’S OCCUPANCY SENSOR SHOULD FACE THE BED AREA OF THE ROOM OR THE AREA WHERE THE OCCUPANT WILL SPEND THE MOST TIME.
Page 13
Network Installation NOTICE TO ENABLE NETWORKING CAPABILITIES OF THE VX THERMOSTAT, REFER TO THE “NETWORK INSTALLATION” SECTION OF THIS MANUAL. BEFORE STARTING THE INSTALLATION OF THE NETWORKED THERMOSTATS, ENSURE THE ONLINE CONNECTION KIT IS CONNECTED TO THE INTERNET. CONFIRM THE ONLINE CONNECTION KIT IS COMMUNICATING PROPERLY WITH THE CLOUD SERVICE BY CALLING TECHNICAL SUPPORT AT 1 877 318 1823.
Page 14
Network Installation Connecting Wireless Receiver To Power supply To Internet Router/Switch Screw Antenna (1) onto Wireless Receiver (2) Connect Wireless Receiver (2) to Server (4) using supplied USB cable (3) Affix Wireless Receiver (2) to wall with double sided adhesive tape Orient Antenna (1) to point upwards to the closest room in which a thermostat will be installed Connect Server (4) to the LAN port with the supplied RJ-45 cable (5)
Page 15
Network Installation Configuring Online Connection Kit Ensure Online Connection Kit is receiving an IP from a DHCP server. NOTE: it is not recommended to use a public IP Ensure MAC address is properly Whitelisted if it needs to bypass a login (splash) page to reach the internet NOTE: MAC address is printed on a white sticker on bottom of Online Connection Kit.
Page 16
Thermostat Installation Mounting Thermostat to Wall Select appropriate installation location for thermostat per below: THE THERMOSTAT’S OCCUPANCY SENSOR SHOULD FACE THE BED AREA OF THE ROOM OR AREA WHERE OCCUPANT WILL SPEND THE MOST TIME. THE THERMOSTAT MUST NOT BE INSTALLED IN THE VICINITY OF LARGE METAL STRUCTURES OR SURFACES INCLUDING METAL AIR DUCTING.
Page 17
Optional Sensor Installation Select appropriate installation location With faceplate removed, place sensor on wall in installation location and mark location for drilling holes for two mounting screws OCCUPANCY SENSORS SHOULD FACE THE DESIRED OCCUPANCY DETECTION AREA. Drill two 3/16” holes in wall and insert two wall anchors Use two screws to securely mount sensor to the wall Insert one AAA alkaline battery into compartment (wireless sensors only)
Page 18
Thermostat Details Thermostat Buttons SYSTEM MODE ROOM TEMPERATURE / SET POINT Cycle between UP | DOWN AUTO | HEAT | COOL | OFF Increase | Decrease values SETTINGS FAN MODE ROOM TEMPERATURE/ SETPOINT Change F | C Activate Scheduler OCCUPANCY SENSOR *In AUTO Mode, cycle between ON | OFF.
Page 20
Thermostat Configuration Configuring Thermostat Prerequisites: During installation training with your support agent you will be provided with: Mesh ID (provided by Verdant Support), Room Number, Time, and Equipment Code. Note: Press and hold FAN and SYSTEM MODE buttons. Turn on thermostat and HVAC unit to activate setup screen (shown above) and complete the below settings shown the following pages: Set MESH ID Enter room number...
Page 21
Thermostat Configuration Set MESH ID For networked installations, a unique MESH ID is associated to each Online Connection Kit and is provided by your technical support agent during the installation training (also be found labeled on device). For properties using a single Online Connection Kit, each thermostat may be linked to MESH ID 0001.
Page 22
Thermostat Configuration Entering Room Number Enter room number by changing characters on screen. Available characters include digits 0-9 and letters A-F. To distinguish between two or more thermostats in the same unit, enter as follows: Thermostat 1: 00100 Thermostat 2: 0100A Press UP | DOWN buttons to increase or decrease the value Press FAN button to advance to the next digit Press SETTINGS button to advance to next menu...
Page 23
Thermostat Configuration Configuring Equipment Settings Enter equipment code by changing digits on the screen. Press UP | DOWN buttons to increase or decrease the value Press FAN button to advance to next equipment setting Press SETTINGS button to advance to next menu NOTE: *default setting Digit Digit #1...
Page 24
Thermostat Configuration Configuring Energy Saving Settings Press UP | DOWN buttons to increase or decrease energy savings preset Press SETTINGS button to advance to next menu *default setting Preset Energy Savings Presets E-0* Energy Savings Off - No Temperature Setback Lowest Energy Savings Lower Energy Savings Standard Energy Savings...
Page 25
Thermostat Configuration Set Thermostat Clock Set thermostat clock to current time in 24h format. Press UP | DOWN buttons to increase or decrease digits Press FAN button to advance to next digit Press SETTINGS button once to go to current room temperature screen. Setup is now complete SETTING CORRECT TIME IS CRUCIAL FOR PROPER OPERATION OF THERMOSTAT.
Page 26
Thermostat Configuration Testing Thermostat Following thermostat configuration, test if the thermostat is controlling the HVAC unit. Ensure thermostat is powered and faceplate is affixed Press DOWN button to change temperature set point below current room temperature to confirm thermostat initiates cooling Press UP button to change temperature set point above current room temperature to confirm thermostat initiates heating Change fan speed by touching FAN button to verify thermostat is controlling...
Page 27
Configuring & Managing Accessories Activating a Sensor Remove faceplate from sensor (s) to be paired Insert two AAA alkaline batteries into each sensor Press button inside sensor to make sensor discoverable Navigate to “Pairing a Sensor” on page 39 NOTE: The sensor(s) will remain discoverable for five (5) minutes after pressing the button inside the device.
Page 28
Configuring & Managing Accessories Pairing a Sensor Ensure thermostat and HVAC unit are powered and thermostat faceplate is removed. The thermostat configuration screens have a 30-second time-out. If no action is taken within this time, the thermostat exits configuration settings. Press and hold SYSTEM MODE and FAN buttons on thermostat to access Mesh ID screen Press and hold SYSTEM MODE and FAN buttons again until type appears...
Page 29
Configuring & Managing Accessories Verifying Sensor Connection Status and Unlinking Sensors NOTE: Thermostat and HVAC unit must be powered Remove faceplate from thermostat Press and hold SYSTEM MODE and FAN buttons until MESH ID appears on the screen Press and hold SYSTEM MODE and FAN buttons again until type appears on screen Press SETTINGS button again until SENS appears on the screen Press SETTINGS button.
Page 30
Configuring & Managing Accessories Configuring Functionality of Sensor The thermostat allows the user to choose the functionality of a sensor. Use the table below to configure the desired functionality. For example, if sensor is intended to be used as Occupancy Sensor, OCC value must be set to 1. NOTE: OCC default setting = 0 Press SETTINGS button to select sensor Press SETTINGS button to move to Occupancy Sensor configuration screen...
Page 31
Configuring & Managing Accessories Press SETTINGS button to configure Door Switch functionality (dsx). Door switch functionality should be set to Normally Open (NO) or Normally Closed (NC) depending on reed switch Press SETTINGS button to configure Temperature Sensor functionality (rtx) Press SETTINGS button to move to ADD screen Press FAN button to finalize pairing...
Page 32
Configuring & Managing Accessories Completing Sensor Setup The thermostat will countdown from thirty (30) seconds. If the sensor has successfully paired, the thermostat will display SUCC. If the sensor did not pair successfully, the display will read FAIL, and the prodecure must be repeated. Press SYTEM MODE button to exit senor setup screen Repeat Sensor setup as many times as necessary...
Page 33
Application Notes A comprehensive list of published application notes can be found at www.verdant.co/resources/application-notes. Applications include (among others): Energy Savings Settings Scheduler Door-lock ZigBee Integrated Solution Demand Response Hilton Connected Room IHG Studio Occupancy Based Lighting Control Advanced Lighting Application: ZigBee Controlled Switch and socket from LEVITON...
Page 34
Custom Energy Savings Settings If you do not want to use one of the energy saving presets detailed in Appendix 1, you can enter the custom energy savings settings. Accessing Custom Energy Savings Settings Ensure thermostat is powered and faceplate removed Press and hold SYSTEM MODE button to access Mesh ID screen Press SETTINGS button to navigate to Energy Saving Settings screen From Energy Savings Settings screen, press and hold SYSTEM MODE and...
Page 35
Custom Energy Savings Settings Using Thermostat Settings Screens SETTING VALUE SETTING INDEX Use UP | DOWN buttons to select desired index setting Press SYSTEM MODE and FAN buttons to edit value of index setting Use the UP | DOWN buttons to change setting value (see Custom energy saving settings section for more info and Min-Max values) Press FAN button to temporarily store setting value Press FAN button to save profile and exit Custom Energy Savings Settings...
Page 36
Custom Energy Savings Settings Default value: enabled Allows for setting of cooling and heating set points at Range: 7 days varying times throughout the day. The scheduler is enabled by default and let’s the user set cooling and heating setpoints for different times for each day of the week.
Page 37
Custom Energy Savings Settings Scheduler Firmware version 1130 and higher is required for Scheduler feature. Ensure thermostat is powered and operational NOTE: Below illustration is an example. Temperature and fan mode can differ. Press SETTINGS button until temperature value shows Press SETTINGS again to activate scheduler and show current status ( n or y) Use the UP | DOWN button to select desired status...
Page 38
Custom Energy Savings Settings Press SETTINGS button to navigate to first event of the week. Use Up / Down arrows to set event time. NOTE: below example shows setting for second event. Press SETTINGS button to display Set and press Fan button to select necessary day of the week.
Page 39
Custom Energy Savings Settings Use UP | DOWN buttons to set cooling temperature to desired setpoint and press SETTINGS button. Use UP | DOWN arrows to set heating setpoint. NOTE: press ON | OFF button at anytime to exit scheduler menu. Repeat Step 5 until all desired events are scheduled...
Page 40
Custom Energy Savings Settings Door Lock Integration Door Lock integration can be via 1-Way Communication or 2-Way Communication. • 1-Way application: Door locks must be networked and communicating with a Door Lock Management System for thermostat integration • 2-Way application: thermostat acts as the network. Door locks are not required to be networked.
Page 41
Custom Energy Savings Settings Press DOWN button to display Add and then press SETTINGS button to display select list. Press DOWN button until desired lock platform shows (oni or kaba) and then press SETTINGS (below example only) Allow countdown to complete until screen displays Found[1-8].
Page 42
Custom Energy Savings Settings Use DOWN button to scroll through found devices with EuI_[lockid]_255 format. NOTE • Dorma locks display as lock’s respective short ZigBee ID • Onity locks display as lock’s respective serial number. Press SETTINGS to select and display -cFg_[lockid]_255 Press DOWN one time to display the 1tag screen.
Page 43
Custom Energy Savings Settings Use UP | DOWN buttons to select a tag number (typically 001) and then press SETTINGS to set and display cfg_[lockid]_[tag] 10. Press DOWN button 2 times to display Acc and then press SETTINGS to accept and re-display Found screen 11.
Page 44
Custom Energy Savings Settings Demand Response Demand Response (DR) is a resource for balancing power supply and demand by allowing consumers options to reduce or shift their energy consumption away from peak periods. How it works • Enroll: Tenant or Property owner opt in to recieve DR events •...
Page 45
Custom Energy Savings Settings Lighting Integration The thermostat uses built-in infrared motion sensors in conjunction with a wired occupancy sensor to scan a room for occupancy. An auxiliary output provides a binary signal according to real-time occupancy status in the room. The auxiliary output is wired to a 24VAC relay installed on the lighting circuit;...
Page 46
Custom Energy Savings Settings Setting Index...
Page 47
Custom Energy Savings Settings Setting Index...
Page 48
Custom Energy Savings Settings 01 – FAN CONTROL MODE Default value: 00 00: AUTOMATIC - fan runs only when Range: 00-01 there is a demand for heating or air conditioning 01: CONTINUOUS - fan runs continuously when thermostat is on...
Page 49
Custom Energy Savings Settings 02 – 1 STAGE DIFFERENTIAL - HEAT Default value: 0.5F Select number of degrees thermostat Range: 0.2F - 3.0F has to sense between automatic changeover temperature for heat and room temperature before a call for 1st stage heating is initiated.
Page 50
Custom Energy Savings Settings 03 – 2 STAGE DIFFERENTIAL - HEAT Default value: 2.0F Select difference between 1st stage Range: 1.0F - 2.0F heating and 2nd stage heating initiation. This also applies as the 3rd and 4th stage differential on top of the 2nd when there are more than 2 stages.
Page 51
Custom Energy Savings Settings 04 – 1ST STAGE DIFFERENTIAL - COOL Default value: 0.5F Select number of degrees thermostat Range: 0.2F - 3.0F has to sense between automatic changeover temperature for cool and room temperature before a call for 1st stage cooling is initiated.
Page 52
Custom Energy Savings Settings 05 – INCIDENTAL OCCUPANCY THRESHOLD Default value: 5 minutes Select minimum period of time (in minutes) for which Range: 0 - 60 minutes occupancy needs to be detected to enter guest occupancy mode. When occupancy is detected, thermostat will switch to occupied mode for a duration of Incidental Occupancy Threshold selected.
Page 53
Custom Energy Savings Settings 06 – NIGHT OCCUPANCY THRESHOLD Default value: 1 minute Select minimum period of time (in minutes) for Range: 0 - 60 minutes which occupancy needs to be detected to consider the room occupied during the Night Occupancy period.
Page 54
Custom Energy Savings Settings 07 – FORCED 2ND STAGE HEATING Default value: 30 minutes Select a number of minutes 1st stage heating will run Range: 0 - 60 minutes before 2nd stage heating is automatically initiated if the guest set point is not reached and the 2nd stage heating is not initiated through differential settings.
Page 55
Custom Energy Savings Settings 08 – NIGHT OCCUPANCY START Default value: 21 hours Select the start time (24-hour clock) for Night Range: 0 - 23 hours Occupancy If occupancy is detected for a period of time longer than the Night Occupancy Threshold during Night Occupancy period, the thermostat will disable the occupancy sensor and consider the room occupied until the end of the Night Occupancy period.
Page 56
Custom Energy Savings Settings 09 – NIGHT OCCUPANCY END Default value: 9 hours Select time (24-hour clock) for Night Occupancy to Range: 0 - 23 hours end. The time of day the Night Occupancy ends and the thermostat switches back to the room sensing settings chosen in the other occupancy modes.
Page 57
Custom Energy Savings Settings 10 – TEMPERATURE RECOVERY TIME Default value: 25 minutes Select the maximum time allowed for a HVAC unit Range: 0 - 60 minutes to attain temperature as defined by Heat and Cool Recovery Temperature; Temperature Recovery Time selected and the actual temperature recovery ability of the HVAC unit are used to calculate setback temperatures.
Page 58
Custom Energy Savings Settings 11 – RECOVERY TEMPERATURE - HEAT Default value: 67F Select room temperature in °F that a HVAC unit Range: 62F - 82F will have to attain within the selected Temperature Recovery Time when there is a need for heating. If recovery is disabled (Temperature Recovery Time set to 0) or if setback temperatures have not yet been calculated, the Recovery Temperature - Heat value...
Page 59
Custom Energy Savings Settings 12 – TEMPERATURE SETBACK DELAY Default value: 20 Select the time delay (in minutes) for which the minutes room that is in the guest occupancy mode needs to Range: 0 - 120 minutes be unoccupied before the temperature setback is initiated.
Page 60
Custom Energy Savings Settings 13 – MINIMUM SETBACK TEMPERATURE - HEAT Default value: 64F Select Minimum Setback Temperature in °F. Range: 52F - 72F Setback temperature is calculated by measuring HVAC unit’s ability to attain Recovery Temperature - Heat”within Temperature Recovery Time. If recovery is disabled (Temperature Recovery Time is set to 0) or if setback temperatures have not yet been calculated, the Recovery Temperature - Heat value...
Page 61
Custom Energy Savings Settings 14 – MAXIMUM SETBACK TEMPERATURE Default value: 78F Select the Maximum Setback Temperature in °F. Range: 72F - 92F Setback temperature is calculated by measuring HVAC unit’s ability to attain Recovery Temperature - Cool within Temperature Recovery Time. If recovery is disabled (Temperature Recovery Time is set to 0) or if setback temperatures have not yet been calculated, the Maximum Setback Temperature value...
Page 62
Custom Energy Savings Settings 15 – RECOVERY TEMPERATURE - COOL Default value: 74F Select the room temperature in °F that a HVAC unit Range: 62F - 82F will have to attain within the selected Temperature Recovery Time when there is a need for air conditioning.
Page 63
Custom Energy Savings Settings 16 – MINIMUM SET POINT Default value: 66F Select the minimum set point in °F that a guest can Range: 64F - 84F select.
Page 64
Custom Energy Savings Settings 17 – MAXIMUM SET POINT Default value: 78F Select the maximum set point in °F that a guest can Range: 60F - 82F select.
Page 65
Custom Energy Savings Settings 18 – TEMPERATURE CONTROL MODE Default value: AUTOMATIC Select Temperature Control Mode: Range: 00 - 01 00: MANUAL - Allows users to select HEAT only or COOL only temperature control mode to maintain the room temperature 01: AUTOMATIC - Thermostat automatically turns on heating or air conditioning to maintain the room temperature at the selected temperature set point...
Page 66
Custom Energy Savings Settings 19 – AUTO CHANGEOVER SET POINT OFFSET Default value: 1F Select the difference between the guest-selected set Range: 1F - 4F point and the heat and the cool set point when the thermostat is in the automatic temperature control mode.
Page 67
Custom Energy Savings Settings 20 – SETBACK SET POINTS Default value: 01 00: When room is unoccupied and the thermostat is Range: 00 - 01 in the setback mode or turned off, it will NOT maintain the temperature between heat and cool setback set points.
Page 68
Custom Energy Savings Settings 21– AUTO-RESTORE Default value: 01 00: When guest enters the room, the thermostat will Range: 00 - 01 be turned off - it will not automatically restore the most recent guest settings 01: When guest enters the room, the thermostat will automatically restore the most recent guest settings...
Page 69
Custom Energy Savings Settings 22 – PLACEHOLDER SCREEN NOTE: for future use.
Page 70
Custom Energy Savings Settings 23 – SETPOINT OVERSHOOT Default value: 0.6F Select the °F of overshoot above or below the setpoint Range: 4F - 20F on the thermostat before the thermostat stops the call for cooling or heating.
Page 71
Custom Energy Savings Settings 24 – AUTOMATIC HUMIDITY CONTROL Default value: 00 00: Disable automatic humidity control Range: 00 - 01 01: Enable automatic humidity control When Automatic Humidity Control is enabled, thermostat will turn on air conditioning in an unoccupied room when humidity raises above 60% and room temperature is above 72°F until either room humidity is below 55% or room temperature is below...
Page 72
Custom Energy Savings Settings 25 – 2ND STAGE COOL DIFFERENTIAL Default value: 2F Select the °F differential required to trigger 2nd stage Range: 5F - 30F cooling (if applicable). This also applies as the 3rd and 4th stage differential on top of the 2nd when there are more than 2 stages.
Page 73
Custom Energy Savings Settings 26 – SMART SETBACK Default value: 00 Smart setback reduces the excessive heating Range: 00 - 01 or cooling that may occur when occupants set their thermostats to setpoints outside of the norm. Occupant setpoint that is greater than Cool Setback or less than Heat Setback will be respected during setbacks to save energy.
Page 74
Custom Energy Savings Settings 27 – HUMIDITY CONTROL THRESHOLD Default value: 60F Select the relative humidity level that automatic Range: 55F - 70F humidity control will attempt to control in conjunction with the humidity cut-off temp.
Page 75
Custom Energy Savings Settings 28 – HUMIDITY CUTOFF TEMPERATURE Default value: 72F Select the temperature at which humidity control will Range: 65F - 75F shut off.
Page 76
Custom Energy Savings Settings 29– PLACEHOLDER SCREEN NOTE: for future use...
Page 77
Custom Energy Savings Settings 30– ENERGY MANAGEMENT ON/OFF Default value: 01 00: Energy management disabled Range: 00 - 01 01: Energy management enabled...
Page 78
Custom Energy Savings Settings 31– DOOR/WINDOW SHUT OFF DELAY Default value: 2 Select the time delay (in minutes) before the Range: 1 - 60 thermostat disables air conditioning when a door or window sensor has been installed.
Page 79
Custom Energy Savings Settings 32– AUTO FAN SPEED 1ST STAGE DIFFERENTIAL Default value: 2F Select the °F differential between Low Fan and 2nd Range: 1F - 8F stage fan (Medium or High) when Auto-Fan Speed is selected.
Page 80
Custom Energy Savings Settings 33– AUTO FAN SPEED 2ND STAGE DIFFERENTIAL Default value: 4F Select the °F differential between Medium and High Range: 2F - 10F Fan when Auto-Fan Speed is selected (only active if 3 fan speeds are available).
Page 81
Custom Energy Savings Settings 34 – TEMPERATURE CALIBRATION Default value: 0F Calibrate the temperature display Range: -5F - 5F...
Page 82
Custom Energy Savings Settings 35 – AUTOMODE TYPE Default value: 01 01: Standard Auto Mode - The thermostat will apply Range: 01 - 02 the deadband on the guest setpoint and control temperature with the guest setpoint as the median 02: Changeover Auto Mode - The thermostat will apply the deadband as a changeover limit where the deadband is crossed triggering a change in heating...
Page 83
Custom Energy Savings Settings 36 – HUMIDITY CONTROL OCCUPIED ROOM Default value: 00 00: Humidity control OFF - The thermostat will disable Range: 00 - 01 humidity control when the room is occupied 01: Humidity control ON - The thermostat will enable humidity control even when the room is occupied...
Page 84
Custom Energy Savings Settings 37 – HEAT EQUIPMENT LOCKOUT Default value: 00 00: Compressor lockout - If set to 1, the thermostat will Range: 00 - 02 only allow electric heat 01: Electric heat lockout - If set to 2, the thermostat will only allow compressor heat.
Page 85
Troubleshooting Restoring Factory Settings For reported errors or configuration issues, restore settings to thermostat default parameters. Press and hold the fan and power buttons together for 3 seconds Press and hold SYSTEM MODE and FAN buttons to move to MESH ID screen Press F I C to reach thermostat equipment type configuration screen Press and hold SYSTEM MODE and FAN buttons until thermostat displays RST, then press the F I C button...
Page 86
APPENDIX 1 - Energy Saving Presets Bolded values below indicate the factory default profile* Level Level Level Level Level Level Fan Control Mode AUTO AUTO AUTO AUTO AUTO AUTO 1st Stage Differential Heat 2nd Stage Differential Heat 1st Stage Differential Cool Guest Occupancy Threshold Night Occupancy Threshold Force 2nd Stage Heating After...
Page 87
APPENDIX 1 - Energy Saving Presets Level Level Level Level Level Level Setback Set Points Auto Restore Setpoint Overshoot Automatic Humidity Control 2nd Stage Cool Differential Smart Setback Humidity Control Threshold Humidity Cutoff Temperature Energy Management On/Off Door/Window Shutoff Delay Auto Fan Speed 1st Stage Differential Auto Fan Speed 2nd Stage Differential Temperature Calibration...
Page 88
APPENDIX 2 - Equipment Codes Outputs EQPT Code Color White Yellow Orange Purple Green Brown Blue 0101 0102 0103 0302 WCCW 0303 WCCW 1001 1002 1011 1012 1101 1102 1111 1112 1201 WAUX 1202 WAUX 1211 WAUX 1212 WAUX 2001 2002 2003 2100...
Page 89
APPENDIX 2 - Equipment Codes Outputs EQPT Code Color White Yellow Orange Purple Green Brown 2102 2103 2106 2502 5501 5502...
Page 90
APPENDIX 3 - Glossary “Automatic Fan Control Mode” - fan runs only when there Incidental Occupancy Threshold - the minimum period is a demand for heating or cooling; of time (in minutes) for which occupancy needs to be detected in order to enter the “Guest Occupancy” mode; “Manual Fan Control Mode”...
Page 91
Warranty Information Refer to www.verdant.co/verdant-warranty information.
Page 92
Technical Specifications Product Type Thermostat White Model White Model Black Model Black Model Description Description VX4-TR-W VX4-TR-W VX4-TR-B VX4-TR-B Relay outputs Relay outputs VX4-NTR-W VX4-NTR-W VX4-NTR-B VX4-NTR-B Relay outputs with no occupancy detection Relay outputs with no occupancy detection VX4-TVF-W VX4-TVF-W VX4-TVF-B VX4-TVF-B...
Page 93
Technical Specifications Technical Specifications for Thermostats (cont’d) Product Type Thermostat Control Outputs (24VAC) (1.5A maximum per C, R, W, Y, O/B/GL, GH, OCC terminal, 2.5A maxi- mum all terminals combined) Power Supply Outlet Occupancy Sensor Horizontal (FOV 100°) Detection Range Temperature Ac- ±1°F curacy...
Page 94
Technical Specifications Technical Specifications for HVAC Controller (cont’d) Gateway Product Type Control Outputs (24VAC) (1.5A maximum per terminal, 2.5A maximum all terminals combined) Power Supply Outlet Occupancy Sensor Beam Width Temperature Accuracy Enclosure Material Extruded Aluminum Ambient Operating Temp 32°F -105°F | 0 - 41°C Internet Connectivity 100M/1000M Base-T Ethernet FCC ID...
Page 95
Technical Specifications Root Node Sensors Product Type ZX-AOS-868 ZX-AOS SKU(s) ZX-RN-868 ZX-RN ZX-DWS-868 ZX-DWS ZX-TSW-868 ZX-TSW 863-870MHz 902-928MHz Wireless Frequency 863-870MHz (EU) 902-928MHz (NA) (EU) (NA) 2.4” x 1.54” x 0.78” 1.82” x 2.4” x 0.74” Case Dimensions 46mm x 61mm x 19mm 46mm x 61mm x 19mm 2 1.5VDC AAA Alkaline Non-rechargeable Operating Voltage...