Page 2
Requirements for the location of the UPS power supply............4 Requirements for operating conditions and storage..............4 Service Area Requirements ....................... 6 Electrical Installation Requirements ....................7 General Requirements ......................7 Electrical Installation block diagram with UPS ................8 COMEX S.A. V.1719...
Page 3
Service visits. A poorly executed electrical installation, not in accordance with these Recommendations, can cause damage to the UPS power supply and also pose a risk to the individuals involved in the installation process and those using the device. COMEX S.A.
Page 4
(dotted line in Figure 2-1). In such a configuration, a single- feed power configuration is implemented, where both inputs are powered by a common power line. For full utilization of the UPS power supply's capabilities, it is recommended to use a dual-feed power COMEX S.A.
Page 5
In such a configuration, the bridge connecting both inputs needs to be removed. COMEX S.A.
Page 6
• Permissible humidity range: 0% to 95% (non-condensing). Batteries exhibit optimal performance and lifespan within the operating temperature range of 15°C to 25°C. Operating the batteries at temperatures above 25°C may reduce their lifespan, while operating them at temperatures below 15°C may decrease their capacity. COMEX S.A.
Page 7
Heat emission* UPS without battery UPS with battery charging charging 2105 W (7185 BTU/h) 2526 W (8622 BTU/h) *Maximum values of heat loss emissions depending on UPS power supply parameters and batteries used. COMEX S.A.
Page 8
UPS during maintenance and service operations, it is recommended to leave sufficient clearance on both sides if possible. The recommended minimum dimensions for the service area are shown in Figure 3-1. Fig. 3-1. Recommended dimensions of the service area. COMEX S.A.
Page 9
0.3m above the floor for a 40kVA UPS. The terminal block is equipped with M6 screw terminals (torque 4.9Nm). It is recommended to use copper eyelet terminals with a minimum diameter of 6.5mm for connecting the cables. COMEX S.A.
Page 10
A, B, and C. ▪ In the case of UPS supplying loads with a strongly nonlinear load characteristic, it is recommended to oversize the neutral wire cross-section compared to the phase wires (170%) in circuits A and COMEX S.A.
Page 11
4 x 25 mm 3 x 80 A 3 x 63 A 3 x 63 A 3 x 25 mm 4 x 25 mm +16 (GND) (GND) Tab. 4-2 Table of recommended values for protection and cross-sectional areas of conductors. COMEX S.A.
Page 12
A, B, and D. • In the case of UPS supplying loads with a highly nonlinear load characteristic, it is recommended to oversize the neutral wire cross-section compared to the phase wires (170%) in circuits A, C, D, and E. COMEX S.A.