1. Important Safety Warning Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully 1-1.
1-5. Maintenance, Service And Faults The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel. Caution - risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
2. Installation And Setup NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. 2-1. Rear Panel View 3K IEC Type 2K IEC Type 1.
2-2. Install The UPS For safety consideration, the UPS is shipped out from factory without connecting battery wires. Before install the UPS, please follow below steps to re-connect battery wires first. Step 1 Step 2 Step 3 Remove front panel. Connect the AC input and Put the front panel back to the re-connect battery wires.
Page 7
Step 3: Communication connection Communication ports: USB port RS-232 port Intelligent slot To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC.
Step 7: Turn on the UPS Press the ON/Mute button on the front panel for two seconds to power on the UPS. Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during this initial charge period. Step 8: Install software For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown.
2-5 Battery Kit Assembly (option) NOTICE: Please assemble battery kit first before installing it inside of UPS. Please select correct battery kit procedure below to assemble it. 2-battery kit Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below chart.
Page 10
6-battery kit Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below chart. Tapes Tapes Step 3: Put assembled battery packs on Step 4: Cover the other side of plastic shell as one side of plastic shells. below chart.
3. Operations 3-1. Button Operation Button View Button Function Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS. Mute the alarm: After the UPS is turned on in battery mode, press and hold this button for at least 3 seconds to disable or enable the alarm system.
Display Function Backup time information Indicates the estimated backup time. H: hours, M: minute Configuration and fault information Indicates the configuration items, and the configuration items are listed in details in section 3-5. Indicates the warning and fault codes, and the codes are listed in details in section 3-7 and 3-8.
3-4. LCD Display Wordings Index Abbreviation Display content Meaning Enable Disable Escape Charger current Boost Buck Temperature Charger EEPROM error Battery Replacement 3-5. UPS Setting There are three parameters to set up the UPS. Parameter 3 Parameter 1: It’s for program alternatives. Refer to below table.
Page 14
02: Programmable outlets enable/disable Interface Setting ENA: Programmable outlets enable (Default) DIS: Programmable outlets disable 03: Programmable outlets setting Interface Setting Setting the backup time limits in minutes from 0-999 for programmable outlets which connect to non-critical devices on battery mode.
Page 15
08: EPO logic setting Interface Setting Set up the EPO function control logic. AO: Active Open (Default). When AO is selected as EPO logic, it will activate EPO function with Pin 1 and Pin 2 in open status. AC: Active Close. When AC is selected as EPO logic, it will activate EPO function with Pin 1 and Pin 2 in close status.
Step 3: Press the “Up“ button (ON/MUTE) to switch to "02" of program list. Then press “Enter“ button to enter value setting of parameter 2. Press the “Up” button to change the value to “ENA” to enable the programmable outlet function. Then press “Enter”...
Boost mode When the input voltage is lower than the when AC is voltage regulation range but higher than normal. low loss point, the boost AVR will be activated. Battery mode When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 10 seconds, UPS will backup power from battery.
3-8. Warning Indicator Warning Icon (flashing) Alarm Sounding every 2 seconds Low Battery Sounding every second Overload Sounding every 2 seconds Battery is not connected Sounding every 2 seconds Over Charge Sounding every 2 seconds Site wiring fault Sounding every 2 seconds EPO enable Sounding every 2 seconds Over temperature...
4. Troubleshooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause Remedy No indication and alarm even The AC input power is not Check if input power cord though the mains is normal. connected well.
Symptom Possible cause Remedy Fault code is shown as 01, 02, 03, A UPS internal fault has Contact your dealer 11, 12, 13 and 41 on LCD display occurred. and alarm is continuously sounding. Battery backup time is shorter Batteries are not fully Charge the batteries for at than nominal value charged...