Copeland YAD K1 Series Application Engineering Bulletin

Copeland scroll compressors
Hide thumbs Also See for YAD K1 Series:

Advertisement

Quick Links

SEPTEMBER 2024
Application Engineering
3-15 Ton YAD*K1 and YPD*K1 Copeland Scroll Compressors
BULLETIN NO:
AE4-1491 R2
Contents
Safety
Important Safety Information
Responsibilities, Qualifications and Training
Terminal Venting and Other Pressurized System
Hazards
Flammable Refrigerant Hazards
Electrical Hazards
Hot Surface and Fire Hazards
Lifting Hazards
POE Oil Hazards
Precautions
Signal Word Definitions
INTRODUCTION
Nomenclature
Digital Compressor Operation
How it Works
APPLICATION CONSIDERATIONS
Operating Envelope
Scroll Temperature Protection
Shell Temperature
Pressure Fluctuations
Long Pipe Lengths / High Refrigerant Charge
Suction and Discharge Fittings
System Tubing Stress
Solenoid Valve and Coil
Accumulators
Off-Cycle Migration Control
Crankcase Heaters
Pump Out Cycle
Reversing Valves
Start Up and Shut Down
Discharge Check Valve
Compressor Cycling
Sound Characteristics
3
High Pressure Control
3
Low Pressure Control
Contaminant Control
3
Oil Type
4
Power Factor
4
Manifolded Compressor Replacement
4
Modulation Control
4
APPLICATION TESTS
4
Performance Modeling
4
Refrigerant Flow Control
6
ASSEMBLY LINE PROCEDURES
Assembly Line Brazing Procedure
7
Unbrazing System Components
7
Removing Compressors
7
Pressure Testing
Assembly Line System Charging Procedure
8
'Hipot' (AC High Potential) Motor Testing
8
Final Run Test
8
SERVICE PROCEDURES
8
Field Replacement
9
Removing Oil
9
Electrical
9
Compressor Replacement After a Motor Burn
9
Manifolded Compressor Replacement
9
Start-Up of a New or Replacement Compressor
10
Modulation Troubleshooting
10
Refrigerant Retrofits
10
Modulation Valve Replacement Procedure
10
Modulation Valve Replacement Procedure
11
Copeland Scroll Compressor Functional Check
11
11
BULLETIN AE4-1491 R2
12
12
12
12
13
13
13
13
14
14
15
15
15
15
16
16
16
16
17
17
17
17
17
18
18
18
19
19

Advertisement

loading
Need help?

Need help?

Do you have a question about the YAD K1 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Copeland YAD K1 Series

  • Page 1 BULLETIN AE4-1491 R2 SEPTEMBER 2024 Application Engineering 3-15 Ton YAD*K1 and YPD*K1 Copeland Scroll Compressors BULLETIN NO: AE4-1491 R2 Contents Safety Sound Characteristics Important Safety Information High Pressure Control Responsibilities, Qualifications and Training Low Pressure Control Terminal Venting and Other Pressurized System...
  • Page 2 BULLETIN AE4-1491 R2 SEPTEMBER 2024 Figures & Tables Figure 1 - Scroll Tube Fitting Brazing Figure 2 - Digital Modulation Cycle Figure 3 - Compressor Capacity Graph Figure 4 - Digital Scroll Cross Section: YAD32-115 & YPD76-129 Figure 5 - Digital Scroll Cross Section: YAD130-174 & YPD145-192 Figure 6 - Operating Envelope: YAD32-50 Figure 7 - Operating Envelope: YAD57-86...
  • Page 3 Additionally, a compressor’s refrigerant lines keep refrigerant and oil under pressure. When removing or recharging refrigerant from this component during service, this can pose a pressurized fluid hazard. © 2024 Copeland LP www.copeland.com...
  • Page 4 - IMMEDIATELY GET AWAY if you hear unusual sounds in the compressor. They can indicate that terminal pin ejection may be imminent. This may sound like electrical arcing (sizzling, sputtering or popping). However, terminal venting may still occur even if you do not hear any unusual sounds. © 2024 Copeland LP www.copeland.com...
  • Page 5 POE lubricant. Handle POE oil with care. Refer to the Safety Data Sheet (SDS) for further details. • Before energizing the system: 1. Securely fasten the protective terminal cover or molded plug to the compressor, and 2. Check that the compressor is properly grounded per the applicable system and compressor requirements. © 2024 Copeland LP www.copeland.com...
  • Page 6 WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION, used with the safety alert symbol, indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. © 2024 Copeland LP www.copeland.com...
  • Page 7 5/6 of this capacity or 100,000 Btu/hr when operated on 50 Hz power. The digital scroll compressor unloads by taking Please refer to Figure 20 for a breakdown of Copeland advantage of the Copeland Scroll compressor's axial Digital Nomenclature.
  • Page 8 For the Copeland Digital Controller to operate properly Please refer to Figures 4 and 5 for cross sectional an NTC sensor must be attached to the compressor pictures of the two digital modulation mechanisms.
  • Page 9 20 pounds of refrigerant is as follows: The external solenoid valve and coil specified by Copeland must be used since this is a critical Single compressor application: 0.5 fluid ounce of oil per component...
  • Page 10 Since Copeland scroll compressors have very high Crankcase Heaters WARNING © 2023 Copeland LP 8 AE4-1491 volumetric efficiency, their displacements are lower than those of A crankcase heater is required when the system charge comparable capacity reciprocating compressors exceeds the values listed in Table 3.
  • Page 11 (available from compressor to slowly rotate backwards until the Copeland) and install it in a system with the longest pressures equalize. This condition does not affect connecting lines and highest internal volume that the compressor durability but can cause unexpected sound system may have.
  • Page 12 A cut out components or reliability. setting no lower than 20 psig (1.4 bar) is recommended. The Copeland controllers unload the compressor a Contaminant Control fraction of a second before shutting down allowing the scroll set to unload, ensuring a relatively quiet Manufacturing processes have been designed to shutdown.
  • Page 13 (118-177ml) less than the compressors. Note that only one compressor in the nameplate value. Please refer to Copeland Mobile for tandem assembly is a digital scroll compressor. model specific oil charge and recharge values. If...
  • Page 14 The system designer is responsible for testing the system to ensure it operates as designed. These tests should be performed during system development and Copeland Climate Technologies, Inc. is not responsible are dependent on the system type and amount of or liable for incorrect energy use predictions.
  • Page 15 The pressure used on the line to meet the U.L. burst pressure requirement must not be higher than 475 psig (33 bar). Higher pressure may result in permanent deformation of the compressor shell and possible misalignment, bottom cover distortion and/or shell rupture. © 2024 Copeland LP www.copeland.com...
  • Page 16 When Systems should be charged with liquid on the high side Copeland scroll compressors are hipot tested with liquid to the extent possible. Most of the charge should be refrigerant in the shell, they can show higher levels of...
  • Page 17 This will vacuum. Internal arcing may occur when any type result in starvation of oil to the replacement compressor of compressor is started in a vacuum which may and a second failure. result in terminal venting. © 2024 Copeland LP www.copeland.com...
  • Page 18 Do not operate with a restricted suction or use will void the compressor UL recognition. For a liquid line. Do not operate with the low pressure cut-out list of Copeland approved refrigerants please refer disabled. Allowing suction pressure to drop below 55 Form...
  • Page 19 Ensure that scroll compressor. The following diagnostic procedure the black o-ring and white PTFE gasket are should be used to evaluate whether a Copeland Scroll removed with the valve and do not remain on compressor is working properly.
  • Page 20 Hipot, winding resistance, and ability to start before returning. More than one- third of compressors returned to Copeland for warranty analysis are determined to have © 2024 Copeland LP...
  • Page 21 The compressor should be disconnected using a tubing cutter. • To reconnect: ✓ Recommended brazing materials: Silfos with minimum 5% silver or silver braze material with flux. ✓ Insert tubing stubs into fitting and connect to the system with tubing connectors. © 2024 Copeland LP www.copeland.com...
  • Page 22 BULLETIN AE4-1491 R2 SEPTEMBER 2024 ✓ Follow New Installation brazing instructions above. Figure 2 - Digital Modulation Cycle Figure 3 - Compressor Capacity Graph © 2024 Copeland LP www.copeland.com...
  • Page 23 BULLETIN AE4-1491 R2 SEPTEMBER 2024 Figure 4 - Digital Scroll Cross Section: YAD32-115 & YPD76-129 Figure 5 - Digital Scroll Cross Section: YAD130-174 & YPD145-192 © 2024 Copeland LP www.copeland.com...
  • Page 24 BULLETIN AE4-1491 R2 SEPTEMBER 2024 Figure 6 - Operating Envelope: YAD32-50 © 2024 Copeland LP www.copeland.com...
  • Page 25 BULLETIN AE4-1491 R2 SEPTEMBER 2024 Figure 7 - Operating Envelope: YAD57-86 Figure 8 - Operating Envelope: YAD98-115 © 2024 Copeland LP www.copeland.com...
  • Page 26 BULLETIN AE4-1491 R2 SEPTEMBER 2024 Figure 9 - Operating Envelope: YAD130-174 Figure 10 - Operating Envelope: YPD76 © 2024 Copeland LP www.copeland.com...
  • Page 27 BULLETIN AE4-1491 R2 SEPTEMBER 2024 Figure 11 - Operating Envelope: YPD110-145 Figure 12 - Operating Envelope: YPD163-192 © 2024 Copeland LP www.copeland.com...
  • Page 28 BULLETIN AE4-1491 R2 SEPTEMBER 2024 Figure 13 - Crankcase Heater Location: YAD32-50 Figure 14 - Crankcase Heater Location: YAD57-115 & YPD76-129 Figure 15 - Crankcase Heater Location: YAD130 & YPD145 © 2024 Copeland LP www.copeland.com...
  • Page 29 BULLETIN AE4-1491 R2 SEPTEMBER 2024 Figure 16 - Crankcase Heater Location: YAD147-174 & YPD163-192 © 2024 Copeland LP www.copeland.com...
  • Page 30 BULLETIN AE4-1491 R2 SEPTEMBER 2024 Figure 17 - Oil Dilution Chart Figure 18 - Tandem Piping Example: YAD32-115 & YPD76-129 © 2024 Copeland LP www.copeland.com...
  • Page 31 BULLETIN AE4-1491 R2 SEPTEMBER 2024 Figure 19 - Modulation Troubleshooting © 2024 Copeland LP www.copeland.com...
  • Page 32 Table 1 - Torque Values Model Torque ft-lb in-lb Modulation Valve (YAD130-174 & 25.8-27.7 310-332 35.0-37.5 YPD145-192) Solenoid Screw Schrader Valve 3.3-5.0 40-60 4.5-6.8 Terminal Block Screws 10-32 Green Ground Screw Sight Glass 74-81 885-975 100-110 © 2024 Copeland LP www.copeland.com...
  • Page 33 YAD130 YPD145 YAD147-174 YPD163-192 Revision Tracking R2 The document format has been updated to the new Copeland format All occurrences of "Emerson" have been removed A note regarding A3 and R290 venting has been updated © 2024 Copeland LP www.copeland.com...