Copeland scroll compressors
Crankcase heaters
1. Crankcase heater usage
IMPORTANT
Oil dilution! Bearing malfunction! Turn the crankcase heater on 12 hours before starting
the compressor.
A crankcase heater is used to prevent refrigerant from migrating into the shell during standstill periods. Due to
Copeland scroll's inherent ability to handle liquid refrigerant in flooded conditions a crankcase heater is not required
when the system charge does not exceed the charge limits shown in Table 1.
system type and configuration.
Family
Product
ZR18K5E
ZR24KRE to ZR48KRE
ZR22K* to ZR81K*
ZRD42K* to ZRD81K
ZR(D)61KRE to ZR(D)92KRE
ZR94KCE to ZR190KCE
ZP90KCE, ZP103KCE,
Scroll A/C
ZR108KRE to ZR144KRE
ZRD94K* & ZRD125K*
ZR160KRE to ZR190KRE
ZR250KCE
ZR310KCE, ZR380KCE
ZH04KCU to ZH08KCU
ZH09KCU to ZH16KCU
ZH12K4E
ZH15K4E to ZH26K4E
Scroll Heat
ZH30K4E to ZH45K4E
Pump
ZH06K1P to ZH19K1P
ZHI27K1P to ZHI46K1P
ZH56K4E to ZH11M4E
ZH100K*
ZH125K*, ZH150*
ZB07KAU to ZB14KAU
YBV(H)021*U to YBV(046)*U
ZB12KCU to ZB20KCU
ZB25KCU to ZB49KCU
ZB15KCE to ZB29KCE
ZBD21K* & ZBD29K*
Scroll Ref
ZB30KCE to ZB48KCE,
ZB57KCE
YB56K1U to YB97K1U
ZB50KCE, ZB56KCE,
ZB11MCE
ZB220KCE
Table 1: Refrigerant charge limit
NOTE: A crankcase heater is always required for ZO/ZOD* compressors (CO
Application Engineering Europe
ZP24K5E to ZP31K5E
ZRD36KRE, ZRD48KRE
ZP23K3E to ZP41K3E
ZP36K5E to ZP83KCE,
ZP91/104/122/143KCE*
ZPD104K, ZPD122K*
ZP120KCE, ZP137K*E
ZP154K*E, ZP182K*E
ZPD103K* to ZPD182K*
ZP232KZE, ZP292KZE
ZP235KCE
ZP295KCE, ZP385K*E
ZP485K*E
ZH06KVE to ZH09KVE
ZH13KVE to ZH18KVE
ZHI05K1P to ZHI23K1P
ZH40K* to ZH75K*
ZH24KVE to ZH48KVE
ZS09KAE to ZS13KAE
ZF06K*E to ZF11K*E
ZF13K*E & ZF18K*E
ZFD13K* to ZFD25K*
ZB66K* to ZB114K*
ZBD58K* to ZBD114K*
1/4
TECHNICAL INFORMATION
This requirement is independent from
ZPD34K* to ZPD91K
ZRH72KTE to ZRH116KTE
YRH72KT*, YRH81KT*
YP195KPT, YP195KNT
YP310KZT
YP515KPT
YH04K1E to YH09K1E
YH11K1E to YH16K1E
ZH04K1P & ZH05K1P
YBVH029*
YB12K1E to YB24K1E
YB31K1E to YB45K1E
YBD17K1E, YBD24K1E
ZBD30K* to ZBD57K*
YBD31K1E to YBD45K1E
ZF24K* to ZF54K*
ZFD41K5E
refrigerant).
2
Charge
limit
2.7 kg
3.6 kg
4.5 kg
5 kg
7.0 kg
7.3 kg
7.7 kg
8.2 kg
9 kg
11.3 kg
13.6 kg
16 kg
1.54 kg
1.93 kg
2.7 kg
3.6 kg
4.5 kg
7 kg
7.5 kg
11.3 kg
13.6 kg
0.5 kg
1.2 kg
1.54 kg
1.93 kg
3.6 kg
4.5 kg
5.5 kg
7.5 kg
11.3 kg

Advertisement

loading
Need help?

Need help?

Do you have a question about the ZB66K Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Copeland ZB66K Series

  • Page 1 A crankcase heater is used to prevent refrigerant from migrating into the shell during standstill periods. Due to Copeland scroll’s inherent ability to handle liquid refrigerant in flooded conditions a crankcase heater is not required when the system charge does not exceed the charge limits shown in Table 1.
  • Page 2 NOTE: This overview presents the crankcase heaters for 240 V and 400 V. Crankcase heaters are also available for 120 V, 230 V, 480 V and 575 V. For other voltage options please refer to the spare parts and accessories software available at www.copeland.com/en-gb. Application Engineering Europe...
  • Page 3 Crankcase heaters to be used in ATEX Zone 2 locations must comply with the ATEX Directive requirements. Non ATEX-certified crankcase heaters shall NOT be used in ATEX Zone 2 locations. NOTE: The crankcase heater presently available from Copeland is not ATEX-certified and can only be used in non-flammable environments.
  • Page 4 Electrical security and safety measures are to be provided on site. DISCLAIMER: The Copeland logo is a trademark and service mark of Copeland LP or one of its affiliates. Copeland Europe GmbH shall not be liable for errors in the stated capacities, dimensions, etc., as well as typographic errors. Products, specifications, assumptions, designs and technical data contained in this document are subject to modification by us without prior notice.