BULLETIN AE4-1387 R11 MAY 2024 Application Engineering Application Guidelines for ZS**KAE and YS**KAE Refrigeration Copeland Compressors 1.3-4.5 HP BULLETIN NO: AE4-1387 R11 Contents Safety Connection Fittings Important Safety Information Three-Phase Rotation Direction Responsibilities, Qualifications and Training Brief Power Interruptions Terminal Venting and Other Pressurized System...
Page 2
BULLETIN AE4-1387 R11 MAY 2024 Figure 6 - ZS*KAE and YS**KAE Application Envelope for R-407A/407C/R-448A/R-449A R-454A, Figure 7 - Capacitor Start - Capacitor Run Motor Figure 8 - Permanent Split Capacitor Motor (PSC) Figure 9 - Compressor Wiring Diagram Single Phase Motor with Internal Protection Figure 10 - ZS09KAE to ZS20KAE Refrigeration Scroll 53 Frame Condensing Unit Mounting...
In order to assure that liquid refrigerant does not return to Operating Envelope the compressor during the running cycle, attention must be given to maintaining proper superheat at the compressor suction inlet. Copeland recommends a minimum of 20°F ZS**KAE YS**KAE refrigeration...
120 or 240-volt control circuits and are available with or difference. without an alarm circuit capability. See Table 7 for a list of Contact your Copeland representative regarding any discharge line thermostat kit numbers. exceptions to the above requirements. Pressure Controls...
Fusite pin molded orientation for single-phase and three- compressor is to be used with HFC refrigerants. phase refrigeration scroll compressors are shown in Figure Form 93-11 for a complete list of all Copeland Shell Temperature approved lubricants System component failure may cause the top shell and discharge line to briefly reach temperatures above 300°F.
BULLETIN AE4-1387 R11 MAY 2024 See section on New Installation for suggestions on how to Copeland strongly encourages the use of a timer which properly braze these fittings. can sense brief power interruptions and lock the compressor out of operation for two minutes. A typical Three-Phase Rotation Direction timer circuit is shown in Figure 14.
The following diagnostic procedure sometimes possible for the scrolls to seal, should be used to evaluate whether a Copeland Scroll preventing pressure equalization compressor is functioning properly. Verify proper unit voltage.
Be sure process tube fitting I.D. and process tube envelope (available online at Copeland.com/OPI) comes O.D. are clean prior to assembly. from the 2 main windings. The larger ZS21-33KAE and YS21-30KAE compressors have conventional three-phase •...
Do not overheat joint. Figure 2 - Scroll Tube Brazing General Guidelines and More For general Copeland Scroll compressor please log in to Online Product Information at Copeland.com/OPI, refer to the Application Engineering bulletins listed below, or contact your Application Engineer.