7 . S p e c i f i c a t i o n s
GENERAL CHARACTERISTICS
CAPACITY*
Dimension,
DXWXH (mm)
Net Weight (kg)
INPUT
Acceptable Voltage
Range
Frequency Range
Voltage Regulation
(normal Mode)
Voltage Regulation
(Batt. Mode)
Frequency Range
(Batt. Mode)
Current Crest Ratio
Harmonic Distortion
Waveform
(Batt. Mode)
EFFICIENCY
Normal Mode
AVR Mode
Battery Mode
BATTERY
Battery Type &
Number
Charging Voltage
Recharge Time
PROTECTION
Full Protection
INDICATORS & ALARM
Indicator
Alarms
ENVIRONMENT
Operating Humidity
Noise Level
MANAGEMENT/COMMUNICATION
Smart RS-232/USB
Optional SNMP
NORMS
Standards
EMC
LVD
SALES INFORMATION
Warranty
PN IEC (HV)
PN IEC (HV)
UK input
PN NEMA (HV)
* Derate capacity to 80% of capacity when the output voltage is adjusted to 208VAC.
Product specifications are subject to change without further notice.
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
52
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 06 17 AA 59 205 11
E3
E3
Performance
Performance
800 RT
1100 RT
800 VA
1100 VA
720W
990 W
425 x 438 x 88 (2U)
12,9
13,4
2% max @ 100% linear load, 5% max @ 100% non-linear load (before low battery alarm)
89%
12 V/7 Ahx2
12 V/9 Ahx2
27.4 VDC ± 1%
Battery Mode, Low Battery, Overload, Battery Replacement, Fault
Supports Windows® 2000/2003/XP/Vista/2008, 7/8/10, Linux, Unix, and MAC
Power management from SNMP (VMWare
EN62040-2: 2006+AC: 2006 (EN 61000-3-2: 2014, EN61000-4-2:2009, EN61000-4-3:2006+A2: 2010,
EN61000-4-4: 2012, EN61000-4-5: 2006, EN61000-4-6: 2014, EN61000-4-8: 2010, EN61000 -2-2: 2002)
67023
67024
67029
67030
68234
68235
E3
Performance
1500 RT
1500 VA
1350 W
525 x 438 x 88 (2U)
19,5
162-290 VAC
60/50 Hz (auto sensing)
OUTPUT
208/220/230/240 VAC
±1.5%(before battery alarm)
50 Hz or 60 Hz ± 1 Hz
3:1
Pure Sine Wave
97%
95%
91%
12 V/7 Ahx4
54.8 VDC ± 1%
4 hours recover to 90% capacity
Overload, short, discharge, and overcharge protection
LCD screen
0-90 % RH @ 0- 40°C (non-condensing)
Less than 45dB at 1 meter
CE RoHS
EN62040-1:2008+A1:2013
2 years
67025
67031
68236
E3
E3
Performance
Performance
2000 RT
2500 RT
2000 VA
2500 VA
1800 W
2250 W
21.5
26
12 V/9 Ahx4
12 V/7 Ahx6
©
compatible) manager and web browser
67026
67027
67032
67033
68237
68238
E3
Performance
3000 RT
3000 VA
2700 W
645 x 438 x 88 (2U)
29.3
92%
12 V/9 Ahx6
82.1 VDC ± 1%
67028
67034
68239
Need help?
Do you have a question about the E3 PERFORMANCE RT 800 VA and is the answer not in the manual?
Questions and answers