Cooling unit sk 3302 series; sk 3302.3 series; sk 3304 series; sk 3305 series; sk 3328 series; sk 3329 series; sk 3332 series; sk 3303 series; sk 3361 series; sk 3366 series; sk 3377 series; (51 pages)
Page 1
LCU DX 3311.490 So For all units with the following serial numbers: 3311.491 So – 2021HA300S(R)9-0901 – … – 2021HA300S(R)9-0935 Assembly and operating instructions...
Page 2
Foreword Foreword Dear Customer, Thank you for choosing a Rittal Liquid Cooling Unit DX (also referred to hereafter as "LCU DX"). This documentation applies to the following devices in the LCU DX series (DX = Direct Expansion): – LCU DX 3 kW single –...
The declaration of conformity has been issued by the proaches. Also indicates situations which company Rittal GmbH and is included with the supply of may result in material damage. the LCU DX. ...
2 Safety instructions Safety instructions Danger! Risk of poisoning from refriger- The devices in the LCU DX series are developed and ant gases created under the influence of manufactured with due regard for all safety precautions. heat. Nevertheless, the unit still poses a number of unavoida- When carrying out welding and solder- ble dangers and residual risks.
Note: Rittal offers leak testing of the device as a service. Caution! Risk of malfunction or damage! Installation, and in particular the laying 2.3.1...
The LCU DX fulfils the requirements of EU Directive 2011/65/EC on the Restriction of Use of Certain Hazard- ous Substances in Electrical and Electronic Equipment (RoHS) of 8 June 2011. Note: Corresponding information about the RoHS Directive may be found on our website at www.rittal.com/RoHS. Rittal LCU DX...
(U) of the 482.6 mm (19") level must be sealed with blanking plates, which are available as Rittal accessories (see section 13 "Accessories"). If the LCU DX is used to cool a TS IT server enclosure, it is important that this is sealed, by fitting the enclosure with side panels, roof and gland plates.
Tab. 2: Scope of supply of an LCU DX, "redundant" variant – Improper rectification of malfunctions – Use of replacement parts which are not authorised by Rittal GmbH & Co. KG – Non-static use, e.g. on moving or vibrating machines Rittal LCU DX...
Note: Damage and other faults, e.g. incomplete de- livery, should be reported immediately, in writing, to the shipping company and to Rittal GmbH & Co. KG. Place the unit in its intended location. Rittal LCU DX...
If the LCU DX is fitted on difference LCU DX 6.5 kW: 25 m the left-hand side of the enclosure, the refrigerant lines are routed out of the evaporator coil enclosure at the Tab. 3: Distances and height differences bottom. Rittal LCU DX...
– TS punched section with mounting flange 23 x 73 mm for enclosure depth 1000 mm: 8612.500, packs of 4 – TS punched section with mounting flange 23 x 73 mm for enclosure depth 1200 mm: 8612.520, packs of 4 Rittal LCU DX...
Central position on the opposite side Depending on the components installed by the custom- er (thermal loads, outlet direction of hot air etc.), it may also be expedient to position it elsewhere according to the individual case. Rittal LCU DX...
Page 15
Attach the external unit to the base plate to avoid the risk of tipping over. Fig. 8: Attachment points for external unit 4 x M10 plugs per external unit Distance > 600 mm Rittal LCU DX...
(intake gas line). Oil could collect here, or in the case of the liquid line, gas bubbles could form. Rittal LCU DX...
Page 17
The manufacturer must select a test method which al- lows suitable results to be achieved in accordance with the requirements outlined below. Connections must be checked with a detector or using a technique with a detection sensitivity as described in Rittal LCU DX...
4. The additional fill volume or the new total fill volume The unit may only be connected after the should be noted on the rating plate and operating aforementioned personnel have read manual. this information! Use only insulated tools. Rittal LCU DX...
1. Inspect the documents. 2. Check the safety switchgear for pressure limiting to ensure that the safety switchgear for pressure limit- ing is operational and correctly installed. Fig. 10: Dimensions for removing the rubber sheathing and in- sulation Rittal LCU DX...
TS frame using an angle grinder or other suitable tool. sure with an air baffle plate (see section 13 "Accesso- ries"). Fig. 12: Cut-out in the air baffle plate TS frame Cut-out for TS frame Air baffle plate Rittal LCU DX...
Page 21
LCU DX. Cut the foamed plastic to the required size. Fig. 14: Partitioning with foamed plastic pieces on the side of the LCU internal unit Partitioning above Partitioning inside Partitioning below Rittal LCU DX...
In the "single" version, there is one ing a power failure or if the minimum cooling load is un- such control and display device installed, and in the "re- dercut. dundant" version there are two. Rittal LCU DX...
Observe the manufacturer's information on temperature settings for the components built into the server enclo- sure. We recommend a setting within the range 22 °C– 25 °C. Because the LCU DX cannot actively regulate hu- Rittal LCU DX...
The corresponding fault code may be read from the 2-digit LCD display. Note: For technical queries, or if servicing is re- quired, please contact Rittal using the ad- dresses shown in section 15 "Customer service addresses". List of error messages 8.2.1...
F-gas regulation (see section 2.3.3 "F-gas regulation" and section 2.3.4 "Chemicals – Climate Protection Ordinance"). Note: At an ambient temperature of 40 °C, the nominal service life of the built-in fan is 40,000 operating hours. Rittal LCU DX...
+50 °C during stor- age. During storage, both the internal as well as the external unit must stand upright. Disposal can be performed at the Rittal plant. Please contact us for advice. Caution! Risk of environmental contami- nation!
IP protection category IEC 60529 IP 20 IP X4 Noise level [dB (A)] 65 (distance 1 m) 40 (Open air above reflective flooring, distance 10 m) Colour RAL 7035 White Tab. 6: Technical specifications for the LCU DX 3 kW Rittal LCU DX...
IP protection category IEC 60529 IP 20 IP X4 Noise level [dB (A)] 66 (distance 1 m) 40 (Open air above reflective flooring, distance 10 m) Colour RAL 7035 White Tab. 7: Technical specifications for the LCU DX 6.5 kW Rittal LCU DX...
-3 K and +4 K. A fluctuation period lasts one to two min- utes. On average, the temperatures at the air outlet of To avoid damage to the device, Rittal prescribes the use the internal unit are within the tolerance of ±2 K.
Fig. 20: Overview drawing of internal unit LCU DX 3 kW and 6.5 kW ("redundant" version) Insert for data and supply cables Refrigerant line for "single" version (1 pair) Refrigerant line for "redundant" version (2 pairs) Condensate discharge Rittal LCU DX...
11 Technical specifications 11.7.3 Circuit diagram, external unit SK 3311.490 and SK 3311.491 Fig. 25: Circuit diagram, external unit SK 3311.490 and SK 3311.491 Rittal LCU DX...
11 Technical specifications 11.7.4 Circuit diagram, external unit SK 3311.492 and SK 3311.493 Fig. 26: Circuit diagram, external unit SK 3311.492 and SK 3311.493 Rittal LCU DX...
LCU DX unit in the cooling zone, at mid-height (fig. 6). It can be fastened to the 482.6 mm (19") mounting angle or to the frame of the TS IT server enclosure. This sensor is responsible for controlling the server inlet air temperature. Rittal LCU DX...
Page 40
11 Technical specifications Fig. 27: Overview diagram of the sensor positions Rittal LCU DX...
Item Qty. / Packs of Evaporator coil control board Display Compressor Inverter motherboard Electronic expansion valve Evaporator coil fan Dixell (evaporator coil) Temperature sensor hot/cold air Refrigerant filter Tab. 21: List of spare parts – LCU DX Rittal LCU DX...
Multiple servers normally communicate with one an- other and in the network using switches. Because as many inputs as possible are located on the front side of switches, they frequently have an air- flow from the side, not "front to back" cooling. Rittal LCU DX...
Page 48
◾ Climate Control ◾ IT Infrastructure ◾ Software & Services You can find the contact details of all Rittal companies throughout the world here. www.rittal.com/contact RITTAL GmbH & Co. KG Auf dem Stuetzelberg · 35745 Herborn · Germany Phone +49 2772 505-0...