Easy to Maintain maintenance costs, and high metering devices to provide opti- reliability. Easy access door handles by Carrier mum operation through the entire provide quick access to all normally operating range. These MZ-VAV models not only pro- serviced components.
Page 3
45°F (7°C). An economizer shall be the source of - Integrated system control - Linkage to required Carrier i-Vu ® cooling in low ambient conditions. required Carrier i-Vu VAV zon- VAV zoning controls for single ®...
Page 4
TYPICAL VAV RTU-OPEN SYSTEM LAYOUT AND COMPONENTS...
S = Cu/Cu — Cu/Cu — Louvered Hail Guard NOTE: Not all possible options can be displayed above. Refer to other support material or your local Carrier Expert. Vertical air flow economizer factory option, must be field installed for horizontal air flow models.
Sound power values are independent of the environment and therefore more accurate. c. A-weighted sound ratings filter out very high and very low frequencies, to better approximate the response of “average” human ear. A-weighted measurements for Carrier units are taken in accordance with AHRI.
Page 9
Physical data (cont) PHYSICAL DATA (HEATING) 6 TO 10 TONS 48LC*B07 48LC*B08 48LC*B09 48LC*B12 GAS CONNECTION No. of Gas Valves Natural Gas Supply Line Press. (in. wg)/(psig) 4-13/0.18-0.47 4-13/0.18-0.47 4-13/0.18-0.47 4-13/0.18-0.47 Propane Supply Line Press. (in. wg)/(psig) 11-13/0.40-0.47 11-13/0.40-0.47 11-13/0.40-0.47 11-13/0.40-0.47 HEAT ANTICIPATOR SETTING (AMPS) First Stage...
Page 10
Open (BACnet MS/TP) equipment controller. Includes built-in temperature and humidity sensor. i-Vu System Touch; Carrier brand 4.3 in. color touch screen user interface connects to a network of up to 60 Open (BACnet MS/TP) equipment controllers. Includes built-in temperature and humidity sensor.
Trust the experts. Smoke detectors make your application Allows access to the unit’s major components with specifi- safer and your job easier. Carrier smoke detectors immedi- cally designed hinged access panels. Panels are: filter, con- ately shut down the rooftop unit when smoke is detected.
Page 12
Flue Discharge Deflector Zone Terminal Sensors The flue discharge deflector is a useful accessory when flue A full range of Carrier zone air terminal space sensors are gas recirculation is a concern. By venting the flue discharge available with capabilities combining: upwards, the deflector minimizes the chance for a neigh- •...
Page 13
Options and accessories (cont) OPTIONS AND ACCESSORY WEIGHTS WEIGHTS IN LB OPTION/ACCESSORY 48LC*B07 48LC*B08 48LC*B09 48LC*B12 Medium Gas Heat High Gas Heat Medium Heat with Stainless Steel Exchanger High Heat with Stainless Steel Exchanger Return Smoke Detector Supply Smoke Detector RA and SA Smoke Detector Sensor RA Smoke Detector and CO...
Page 17
THIRD ANGLE DIMENSIONS ARE IN INCHES PROJECTION TOLERANCES ON: THIS DOCUMENT AND THE INFORMATION CONTAINED THEREIN IS PROPRIETARY TO CARRIER CORPORATION AND SHALL NOT 1 DEC 2 DEC 3 DEC BE USED OR DISCLOSED TO OTHERS, IN WHOLE OR IN PART, MATERIAL WITHOUT THE WRITTEN AUTHORIZATION OF CARRIER CORPORATION.
Variable-speed motors are exempt from binations would work, Carrier recommends the lower EPACT compliance requirements. horsepower option. 5. For information on the electrical properties of Carrier motors, please see the electrical information section of this book. 48LC*B07 — 6 TON HORIZONTAL SUPPLY AVAILABLE EXTERNAL STATIC PRESSURE (in.
Page 65
Fan data (cont) PULLEY ADJUSTMENT — FAN RPM AT MOTOR PULLEY SETTINGS MOTOR PULLEY TURNS OPEN (RPM) 48LC*B MOTOR/DRIVE UNIT COMBO Standard Static — — 3 Phase Medium Static — — High Static — — 1150 1120 1089 1059 1029 Standard Static —...
Electrical data ELECTRICAL INFORMATION VOLTAGE RANGE COMP 1 COMP 2 OFM (ea) 48LC*B V-Ph-Hz UNIT WATTS TYPE EFF AT FULL LOAD 208-3-60 13.2 81.5% 81.5% HIGH 84.5% 230-3-60 13.2 81.5% 81.5% HIGH 84.5% 460-3-60 81.5% 81.5% HIGH 84.5% 575-3-60 81.5% 81.5% HIGH 84.5%...
Page 67
Electrical data (cont) UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA (6 TO 10 TONS, NO CO) NO CO OR UNPWRD CO NO PE WITH PE (PWRD FR/UNIT) NOM. UNIT SIZE V-Ph-Hz TYPE DISC. SIZE DISC. SIZE FUSE OR FUSE OR HACR BRKR HACR BRKR 48LC*B07...
Page 68
Electrical data (cont) UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA (6 TO 10 TONS, WITH POWERED CO) WITH PWRD CO NO PE WITH PE (PWRD FR/UNIT) UNIT NOM. SIZE V-Ph-Hz TYPE DISC. SIZE DISC. SIZE FUSE OR FUSE OR HACR BRKR HACR BRKR 48LC*B07 208/230-3-60...
Page 69
Electrical data (cont) UNIT WIRE SIZING DATA WITH FACTORY-INSTALLED HACR BREAKER (6 TO 10 TONS, NO CO) NO CO OR UNPWRD CO NO PE WITH PE (PWRD FR/UNIT) UNIT NOM. SIZE V-Ph-Hz TYPE DISC. SIZE DISC. SIZE HACR BRKR HACR BRKR 48LC*B07 208/230-3-60 35/35...
Page 70
Electrical data (cont) UNIT WIRE SIZING DATA WITH FACTORY-INSTALLED HACR BREAKER (6 TO 10 TONS, NO CO) WITH PWRD CO NO PE WITH PE (PWRD FR/UNIT) UNIT NOM. SIZE V-Ph-Hz TYPE DISC. SIZE DISC. SIZE HACR BRKR HACR BRKR 48LC*B07 208/230-3-60 39/39 50/50...
Page 71
Electrical data (cont) 3-STAGE COOLING W/3-SPEED INDOOR FAN MOTOR, SIZES 07-12 (6-10 TONS) — HIGH SCCR VOLTAGE COMP 1 COMP 2 OFM (ea) HIGH MODEL V-Ph-Hz RANGE SCCR EFF at WATTS TYPE Full Load 48LCB*07 208-3-60 13.2 81.5% 81.5% HIGH 84.5% 230-3-60 81.5%...
Page 72
Electrical data (cont) UNIT WIRE/FUSE OR HACR BREAKER SIZING DATA, 3-SPEED INDOOR FAN MOTOR, SIZES 07-12 (6 TO 10 TONS) — HIGH SCCR NO CO OR UNPWR CO HIGH NO PE WITH PE (PWRD FR/UNIT NOM. MODEL SCCR FUSE or DISC.
Page 73
Electrical data (cont) Legend and Notes for Electrical Data NOTES: 1. In compliance with NEC requirements for multimotor and combina- Tables, pages 66-72. tion load equipment (refer to NEC Articles 430 and 440), the over- current protective device for the unit shall be fuse or HACR LEGEND breaker.
Page 74
48LC*B07 VAV-RTU OPEN CONTROL WIRING DIAGRAM...
Page 75
48LC*B08-12 VAV-RTU OPEN CONTROL WIRING DIAGRAM...
The VAV-RTU Open control is designed to provide VAV system operation when using a 48LCB chassis small pack- Occupied Heating aged rooftop and Carrier i-Vu ® Open VAV terminal con- Optionally, the user may enable occupied heating, which trols.
Page 79
SA temperature, the first cooling stage will be disabled. The control will support Airside Linkage to accommodate Minimum Ventilation system operation using Carrier VAV terminal controls. The VAV-RTU Open will receive zone information (occupancy The economizer minimum position will be adjusted as status, occupied and unoccupied zone temperatures, occu- required based on the supply fan speed.
Motor Limits, Break Horsepower (bhp) not be required to run, which will provide exceptional Due to the internal design of Carrier units, the air path, energy savings due to less power draw, improved system and specially designed motors, the full horsepower (maxi-...
“safety factors” life, and maintains even, comfortable temperatures. Please to the calculated load are signs of oversizing air condition- contact your local Carrier representative for assistance. ers. Oversizing the air conditioner leads to poor humidity SYSTEM OVERVIEW...
A. 23 09 13.23.A. Space terminal sensors indicate GO operation as well as a fault LED indicator for thermostat mis-wiring, no fan 1. Carrier zone air terminal space sensors shall be operation and safety switches. available with capabilities of combining: 4.
Page 83
Guide specifications (cont) technician to correctly wire and or trouble- Morning Warm-up above, except it will not be limited shoot the rooftop unit. by the transition into an occupied period. 4. Automatic reset, motor thermal overload E. 23 09 93.13 E. Heating and Cooling Setpoint Sepa- protector.
Page 84
I. 23 09 93.13 I. Minimum Ventilation — The econo- trol will support Airside Linkage to accommodate sys- mizer minimum position will be adjusted as required tem operation using Carrier VAV terminal controls. based on the supply fan speed. Two user configurable The VAV-RTU Open will receive zone information minimum economizer positions will be provided.
Page 85
10,000 hours of data and time clock retention during power outages. 6.01 23 40 13.13 Packaged VAV, Rooftop Units: l. Shall have built-in support for Carrier techni- A. 23 40 13.13.A. Standard filter section cian tool. 1. Shall consist of factory-installed, low velocity, m.
Page 86
Guide specifications (cont) when temperature and/or humidity are b. Integrated Ultra Low Leak Models: below setpoints. 1) Integrated, gear driven opposing modu- 5) Shall be equipped with gear driven lating blade design type capable of simul- dampers for both the outdoor ventilation taneous economizer and compressor air and the return air for positive air operation.
Page 87
Guide specifications (cont) 15) Economizer controller shall accept a 14. High efficiency motors listed shall meet 2 to 10 vdc CO sensor input for section 313 of the Energy Independence and IAQ/DCV control. In this mode, damp- Security Act of 2007 (EISA 2007). ers shall modulate the outdoor air C.
Page 88
Guide specifications (cont) 4. Base of unit shall have a minimum of 4 locations b. Unit shall have one factory installed, tool- for thru-the-base gas and electrical connections less, removable, filter access panel. (factory installed or field installed), standard. c. Panels covering control box, indoor fan, 5.
Page 89
Guide specifications (cont) 4. Optional Stainless Steel Heat Exchanger e. Corrosion durability of fin stock shall be con- construction. firmed through testing to have no visible corrosion after 48 hour immersion in a a. Use energy saving, direct-spark ignition room temperature solution of 5% salt, system.
Page 90
Guide specifications (cont) allow change out of power element and bulb safely diverting harmful shaft voltages and without removing the valve body. bearing currents to ground. b. Refrigerant filter drier. Solid core design. 2. Variable Frequency Drive (VFD). For indoor fan motor controlled by duct static pressure c.
Page 91
Guide specifications (cont) natural gas unit for use with liquefied pro- 2) A transformer shall not be included. pane, up to 2000 ft (610 m) elevation. 3) Outlet shall be factory-installed and b. Additional accessory kits may be required for internally mounted with easily accessible applications above 2000 ft (610 m) elevation.
Page 92
208/230-v and 460-v units. interface with rooftop unit or other equipment. Carrier Corporation • Syracuse, New York 13221 6-22 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.