Operating Instructions Acond Aconomis Acond Aconomis S, N, R Heat Pump - air - water Operating Instructions Date of last change: 09.08.2024 Page 1/47 AC-A037-EN-R01 For customers...
Page 2
Operating Instructions Acond Aconomis IN BRIEF: To turn on/off the heat pump: • If the symbol lights up on the display , the heat pump is switched off. • To switch on the TC, press the ✓ button. A confirmation dialog will appear, go to YES and confirm with the ✓...
Operating Instructions Acond Aconomis Explanation of symbols, validity of 3.1.4 Main panel ............17 documentation ..........5 3.1.5 Display control ..........17 Symbols used on labels ........5 3.1.6 How to switch on the heat pump: ....17 Symbols used in the instructions ...... 5 3.1.7...
Page 4
Operating Instructions Acond Aconomis Alarms, malfunctions and their Cleaning filters in the heating system ..... 38 elimination………........... 33 6.5.1 Filter cleaning procedure......... 39 Confirmation of failure ........33 6.5.2 Magnetic filter cleaning procedure ....39 Storage vessels and hot water storage System venting ..........
!! Do not disconnect the heat pump from the power supply for an extended period of time (several days) !!! The backup battery may be discharged, the control software deleted and data lost. Any technician call-out will be charged according to the current ACOND a.s. price list.
Operating Instructions Acond Aconomis No handling of open flames near the outdoor unit! 2.1.3 Treatment of the device Do not use chlorine to treat stainless steel surfaces and avoid abrasive materials and wire cloths! You can treat stainless steel surfaces: •...
Operating Instructions Acond Aconomis • Only carry out all electrical installation work and electrical connections in accordance with national and local regulations. Electric shock warning! • The connection to the mains must be made as a fixed connection only. •...
1,45 2.3.2 Stainless steel water tanks The ACOND heating system can be equipped with a stainless steel vessel for heating water accumulation or a stainless steel hot water tank (hereinafter referred to as vessels). Although these are they are stainless steel vessels, they are not maintenance-free! Instructions for installation and maintenance of the vessels are given in in the documentation Storage Vessels, Hot Water Storage Tanks, which is included in the delivery of the vessels.
Operating Instructions Acond Aconomis Technical data The following technical data and performance parameters are for the average climate and for the unit with clean heat exchangers! Table 2: Technical data Model Acond Aconomis Acond Aconomis Acond Aconomis Supply voltage code;...
Page 11
Operating Instructions Acond Aconomis Table 3: Performance parameters of EN 14 511 nominal conditions Model Acond Aconomis S Acond Aconomis N Acond Aconomis R Heating power A7/W35 [kW] 2,740 4,758 COP A7/W35 [1] 5,080 4,952 Heating power A7/W55 [kW] 2,350...
Operating Instructions Acond Aconomis Table 5: Flow rates for nominal conditions according to EN 14 511 Model Acond Aconomis S Acond Aconomis N Acond Aconomis R Fan speed [1/min] A7/W35 Water flow [m 0,8318 Pressure difference [kPa] -3,442 Fan speed [1/min]...
Description of the heat pump operation 2.5.1 Heating The ACOND® heat pump generates heat energy for the house according to the actual need. Hot water is heated continuously, or according to a DHW heating schedule. If the average outdoor temperature (average over 3 days, temperature measured in the morning, noon and evening) rises above the "End of...
Operating Instructions Acond Aconomis 2.5.4 Adverse climatic conditions High humidity and temperatures just below zero for very long periods of time can cause the grille and fan surroundings to freeze. This is not a malfunction but a physical phenomenon. It may be necessary to temporarily stop the heat pump with the main circuit breaker and very carefully remove the frost mechanically.
Operating Instructions Acond Aconomis Heat pump control Control of the heat pump is possible: using a web browser via www.ACOND.cz if the heat pump control is connected to the Internet - chapter 3.2 via a direct connection at the installation site on the local network - chapter 0 via the indoor unit in the reference room - chapter 3.1...
Page 16
Operating Instructions Acond Aconomis C-ID Symbol Description If the symbol is lit, a high electricity tariff is HDO vt in effect The outdoor temperature has reached the end of heating - summer operation parameter Winter operation If there is a fault on the device, the display will show a panel with a description of the fault.
Operating Instructions Acond Aconomis 3.1.3 Basic view - saver In the basic view, the display shows the current temperature in the room, the type of control, the current mode, or the symbol for a fault. Press any button on the display to switch to the to the main panel.
Operating Instructions Acond Aconomis 3.1.7 How to set the desired room temperature: To set the desired room temperature, go to the main panel by holding down the x button and pressing the > arrow, +/- or ✓ buttons. The display will show the current room temperature setpoint. Press the + or - button to increase or decrease the setpoint temperature by 0.1 °C.
Operating Instructions Acond Aconomis 3.1.11 How to set the outlet water temperature for cooling……… The panel Water temperature for chlorine can only be set with the up and down arrows in cooling mode, which can only be set in summer mode.
The connection of the heat pump to the internet will be made by a service technician when the heat pump is installed or later via the ACOND service phone line. When logging in, users access to a web server with a heat pump database.
Page 21
Operating Instructions Acond Aconomis Fig 1: ACOND a.s. website with heat pump login (Link top right) Click on the ACONDTHERM LOGIN sign in the upper right and a page with a login table will appear, see Fig 2. Fig 2: TecoRoute login page The login details (username and password) will be supplied by the installer when the heat pump is handed over.
Page 22
The heat pump login page appears (see Fig 4). Fig 4: Heat pump login Enter ACOND in the User name and Password fields (factory default - you can change the name and password on the Information page, see chap. 3.2.12 on page 30).
(Google Chrome, FireFox, Internet Explorer, etc.). A login web page will appear - see Fig 4. Enter ACOND in the User name and Password fields (factory default - you can change the name and password on the Information page, see chap. 3.2.12 on page 30).
Page 24
Operating Instructions Acond Aconomis Table 6: Meaning of pictograms used on the heat pump main page pictogram Status pictogram Status Description Inactive Active Heat pump compressor Inactive Active Heat pump fan Inactive Active Circulator Heat Pump Inactive Active Defrosting the heat pump...
The ACOND Therm® control normally maintains the set room temperature within a tolerance of +/- 0.5°C. This tolerance is only exceeded in exceptional cases (e.g. after a system restart, after a change in the desired temperature, after ventilation, etc.).
Operating Instructions Acond Aconomis When ANTISEPSE OPTION is selected, the boiler is disinfected once a week by heating to 60°C. Antisepsis can also be triggered once by clicking on the START sign if antisepsis is enabled. Fig 8: TUV antisepsis When selecting the QUIET MODE of the CHP, it is possible to specify the time when the fan speed will be reduced due to the noise of the heat pump.
Operating Instructions Acond Aconomis 3.2.7.1 Automatic selection - AUT button Automatic system selection favours the operation of the heat pump. If necessary, a bivalent source of heat energy is attached - electric heating rods. 3.2.7.2 Heat pump - DH button With this option, only the heat pump can be operated.
Operating Instructions Acond Aconomis 3.2.10 Fault display Fig 11: Fault display on web page In the event of a fault, an exclamation mark appears next to the ACONDTherm logo on a red background. After clicking on the exclamation mark icon, a description of the fault is displayed with an OK button that can be used to confirm the fault after it has been corrected (if the cause of the fault has passed) (Fig 11).
Page 29
Operating Instructions Acond Aconomis 3.2.11.1 Circuit1, Circuit2, Heating water For each day it is possible to enter 2 time periods in which the room temperature (heating water temperature) will be in STANDARD control) will be controlled to the value in the white oval below the corresponding times in this table.
Operating Instructions Acond Aconomis 3.2.12 Information The Information page contains basic information about the heat pump and its user, installation location and other information entered by the technician during installation. At the bottom of the page you can change the username and password to access the heat pump website and the system time. The username and password can contain a maximum of 10 characters, do not use diacritical marks (hooks, commas).
Operating Instructions Acond Aconomis 3.2.13 Equithermal curve Clicking on the link in the Equithermal Curve menu will display the table with the equithermal control settings (see Fig 15). The numbers below the horizontal axis indicate the outdoor temperature of the breaks (points) of the equithermal curve, the numbers above the graph indicate the heating water temperature corresponding to these breaks (points).
3.3.3 User login To monitor and control your ACOND heat pump via your mobile phone, you must first log in to the app. On the login page, enter the same username (Login) and password that you use to access the web app (i.e.
Operating Instructions Acond Aconomis Alarms, malfunctions and their elimination………. Each alarm is signalled simultaneously via the web interface and on the indoor unit. If a fault occurs on the heat pump, an exclamation mark appears in the red box on the home page (see Fig 11). The fault panel...
Page 35
Operating Instructions Acond Aconomis Code ALARM Cause Removing HIGH COMPRESSOR Call technical support. Overheated outdoor unit. DISCHARGE PRESSURE Check that the fan is not mechanically blocked - dirt, frost... If possible, remove WALK-IN VALVE The fan isn't spinning. dirt/frost when the heat pump circuit breaker is blown.
Storage vessels and hot water storage tanks…….. The ACOND heating system can be equipped with a stainless steel vessel for heating water accumulation or a stainless steel hot water storage tank (hereinafter referred to as vessels), which must be installed and operated in accordance with the instructions in this documentation.
Operating Instructions Acond Aconomis Regular checks Checking the intake and exhaust grilles and vents………… Check the front grille and evaporator at regular intervals for leaves, papers or other debris. Clean if necessary with the heat pump switched off. Never stick foreign objects into the outdoor unit of the heat pump! The heat pump operates in intermittent automatic operation, the fan runs at high speed and injury may result.
Operating Instructions Acond Aconomis 6.4.1 Procedure for checking system and expansion vessel pressure..When draining water from the expansion tank, have a large enough container on hand, as more water may flow out (depending on the size of the expansion tank).
Operating Instructions Acond Aconomis 6.5.1 Filter cleaning procedure Have a rag handy when opening the filter cover, usually a small amount of water will come out. To clean the filter: • switch off the heat pump, disconnect the heat pump from the power supply (drop the circuit breaker of the heat pump) •...
Safety valve The ACOND heating system can be equipped with a container for heating water storage or a hot water tank with a safety valve. Each safety valve must be checked regularly at least once every six months (by manually draining the water) and replaced in the event of a fault.
Page 41
Declared load profile Energy efficiency of water heating η Daily electricity consumption Daily fuel consumption fuel elec Contact details ACOND a.s., Štěrboholská 1434/102a, 102 00 Prague 10 - Hostivař, Czech Republic Date of last change: 09.08.2024 Page 41/47 AC-A037-EN-R01 For customers...
Page 42
Declared load profile Energy efficiency of water heating η Daily electricity consumption Daily fuel consumption fuel elec Contact details ACOND a.s., Štěrboholská 1434/102a, 102 00 Prague 10 - Hostivař, Czech Republic Date of last change: 09.08.2024 Page 42/47 AC-A037-EN-R01 For customers...
Page 43
Declared load profile Energy efficiency of water heating η Daily electricity consumption Daily fuel consumption fuel elec Contact details ACOND a.s., Štěrboholská 1434/102a, 102 00 Prague 10 - Hostivař, Czech Republic Date of last change: 09.08.2024 Page 43/47 AC-A037-EN-R01 For customers...
Page 44
Declared load profile Energy efficiency of water heating η Daily electricity consumption Daily fuel consumption fuel elec Contact details ACOND a.s., Štěrboholská 1434/102a, 102 00 Prague 10 - Hostivař, Czech Republic Date of last change: 09.08.2024 Page 44/47 AC-A037-EN-R01 For customers...
Page 45
Declared load profile Energy efficiency of water heating η Daily electricity consumption Daily fuel consumption fuel elec Contact details ACOND a.s., Štěrboholská 1434/102a, 102 00 Prague 10 - Hostivař, Czech Republic Date of last change: 09.08.2024 Page 45/47 AC-A037-EN-R01 For customers...
Page 46
Declared load profile Energy efficiency of water heating η Daily electricity consumption Daily fuel consumption fuel elec Contact details ACOND a.s., Štěrboholská 1434/102a, 102 00 Prague 10 - Hostivař, Czech Republic Date of last change: 09.08.2024 Page 46/47 AC-A037-EN-R01 For customers...
Operating Instructions Acond Aconomis 9 Links In the event of a heat pump fault, visit https://ACOND.cz/tepelna-cerpadla/servis/ Date of last change: 09.08.2024 Page 47/47 AC-A037-EN-R01 For customers...