Summary of Contents for ECR International freewatt FW95V
Page 1
MODEL FW95V NATURAL AND PROPANE GAS TWO STAGE HIGH EFFICIENCY (CONDENSING) WARM AIR FURNACE ® Manufactured by: ECR International, Inc. 2201 Dwyer Avenue, Utica NY 13501 web site: www.ecrinternational.com P/N 240007583, Rev. D [04/2012]...
MODEL FW95V WARM AIR FURNACE INSTALLATION MANUAL AND OPERATING INSTRUCTIONS TABLE OF CONTENTS vent furnace, all combustion air is supplied to the furnace burners through the air intake system. (See 1 - Introduction...........2 Section 7, “Ventilation and Combustion Air.”) 2 - Safety Symbols and Warnings .....2 All models may be fi...
Page 3
WARNING WARNING IF THE INFORMATION IN THESE INSTRUC- THESE INSTRUCTIONS ARE INTENDED AS TIONS IS NOT FOLLOWED EXACTLY, A FIRE AN AID TO QUALIFIED SERVICE PERSON- OR EXPLOSION MAY RESULT, CAUSING NEL FOR PROPER INSTALLATION, ADJUST- PROPERTY DAMAGE, PERSONAL INJURY MENT AND OPERATION OF THIS FURNACE.
Page 4
8. A gas-fi red furnace for installation in a residential National Fire Protection Association garage must be installed so that the burners and ig- 1 Batterymarch Park nitor are no less than 18” above the fl oor. The fur- Quincy, MA, 02169-7471 nace must be located, or protected to avoid physical Phone: (617) 770-3000 damage by vehicles.
Page 5
WARNING WHEN THIS FURNACE IS INSTALLED IN A RESIDENTIAL GARAGE, IT MUST BE INSTALLED SO THE BURNERS AND IGNITION SOURCE ARE LOCATED NO LESS THAN 18” ABOVE THE FLOOR TO PREVENT THE RISK OF IGNITING FLAMMABLE VAPORS WHICH MAY BE PRES- ENT IN THE GARAGE.
INSTALLATION REQUIREMENTS SPECIFIC TO THE STATE OF MASSACHUSETTS FOR DIRECT VENT, MECHANICAL VENT, AND DOMESTIC HOT WATER APPLIANCES. 3. SIGNAGE: For all side wall horizontally vented gas fueled A metal or plastic identifi cation plate shall be per- equipment installed in every dwelling, building or manently mounted to the exterior of the building at structure used in whole or in part for residential pur- a minimum height of eight (8) feet above grade di-...
6(B) MANUFACTURER REQUIREMENTS - GAS FIGURE 2 – FURNACE COMPONENTS EQUIPMENT VENTING SYSTEM NOT PROVID- ED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the fl ue gas- es, but Identifi...
TABLE 1A - RANGE OF TEMPERATURE RISE 3 - FURNACE SIZING Furnace Model Temperature Rise The maximum hourly heat loss for each heated High Fire (HF) 35 - 65°F space shall be calculated in accordance with the 60, 80, 100, 120 procedures described in the manuals of the Heat- Low Fire (LF) 25 - 55°F ing, Refrigeration and Air Conditioning Institute of...
f. The furnace should be installed on a fi rm base 4 - LOCATION OF UNIT when installed in the upfl ow position. This would typically be the concrete fl oor if installing the fur- 1. GENERAL GUIDELINES nace in a basement. a.
Page 10
• Ammonia, as is commonly found in perma- 3. INSTALLATION IN UPFLOW, DOWNFLOW OR HORIZONTAL POSITIONS nent wave solutions used in women’s hair dressing salons UPFLOW INSTALLATION: Vent positioning, • Anti-static fabric softeners used in clothes pressure switch location and drain locations shall dryers be performed in accordance with instructions in •...
WARNING IMPORTANT: If the furnace and air conditioner is above a fi nished space, install a drain pan THIS FURNACE IS DESIGN CERTIFIED FOR underneath the unit. INSTALLATION ON COMBUSTIBLE FLOORS. THIS SHALL BE INTERPRETED AS A WOOD NOTE: It is not permissible to use a rear return on this FLOOR ONLY.
6 - DUCTWORK WARNING Proper airfl ow is required for the correct operation NEVER ALLOW THE PRODUCTS OF COM- of this furnace. Insuffi cient airfl ow may cause er- BUSTION FROM THE FLUE TO ENTER THE ratic operation, could cause the furnace to cycle on RETURN AIR OR SUPPLY AIR DUCTWORK.
to prevent entraining combustion gases from an ad- IMPORTANT: Some high effi ciency fi lters have jacent fuel burning appliance, or entraining combus- a greater than normal resistance to airfl ow. This tion air for this furnace or adjacent fuel burning ap- can adversely affect furnace operation.
Remove the vent connector of the furnace being re- 4. Follow the lighting instructions of the appli- placed, seal off the inlet to the vent from that furnace, ance being tested and turn it on to continuous then test the remaining appliances connected to the operation.
The optional Concentric Vent Termination Kits are The combustion air piping does not have fl ue gas- certifi ed for use until July 1, 2008. Use the ap- es traveling through it and may be installed with proved transition cement certifi ed by the ULC S636 common ABS, PVC or CPVC piping or fi...
10 - DETERMINING COMBUSTION AIR CASE 1 - FURNACE LOCATED IN AN UNCON- FIGURE 4 - COMBUSTION/DILUTION AIR FROM FINED SPACE HEATED INSIDE SOURCES (CASE 2) Unconfi ned space does not necessarily mean that ventilation will not have to be introduced from the outdoors, particularly in airtight homes.
The other opening may communicate freely with a IMPORTANT: If the attic has an exhaust fan ventilated the attic. If using the attic air, ensure that (power vent), it may create a negative pres- the opening is ducted from the ceiling high enough sure suffi...
FIGURE 6 - OUTDOOR AIR FOR COMBUSTION, WARNING HORIZONTAL (CASE 4) READ AND FOLLOW ALL INSTRUCTIONS IN THIS SECTION. FAILURE TO PROPERLY VENT THIS FURNACE CAN CAUSE CARBON MONOXIDE POISONING OR AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAM- AGE, PERSONAL INJURY OR LOSS OF LIFE. NOTE: Combustion air intake and exhaust termination should be inspected periodically to ensure they are clear of obstructions.
Page 19
All exhaust piping must be installed in accordance FIGURE 8 - STANDARD (STRAIGHT) HORIZON- with CAN/CGA-B149.in Canada; the latest edition TAL VENT DETAIL of National Fuel Gas Code, NFPA 54 / ANSI Z223.1 in the United States, as well as in accordance with local codes.
Page 20
Exterior vent pipe greater than 24” should be insu- FIGURE 9 - PERISCOPED VENT DETAIL lated with ½” insulation to prevent moisture from freezing within the pipe and accumulating. Size the exhaust pipe as specifi ed in Table 4 - Di- rect and Non-Direct Vent Lengths.
• Within 6 feet of any service regulator vent • The vent shall not terminate over public walk- outlet; ways or over an area where condensate or • Less than 12” above grade level or anticipat- vapor could create a nuisance or hazard. ed snow level;...
Page 22
IMPORTANT: The supplied adapter is made of IMPORTANT: If the furnace is to be installed in PVC. If planning to use ABS pipe, use an all- the vicinity of other fuel burning appliances, ad- purpose cleaner and ABS to PVC transition ce- equate combustion air must be available for the ment.
Do not locate the terminal on the side of the build- CONCENTRIC VENTING KIT ing facing the prevailing winter winds. Concentric venting terminal kits may be used for CAUTION this series furnace. They provide a means of ob- taining combustion air and exhausting products of Improper location or installation can result in combustion utilizing a single penetration through structural damage to the building, damage to...
Page 24
IN CANADA FIGURE 12 - MULTIPLE VENTING (STANDARD HORIZONTAL) In addition to the general guidelines, both non-di- rect and direct vent exhaust shall not terminate: • Directly above a paved sidewalk or paved driveway which is located between two single- family dwellings and serves both dwellings;...
• Locate the vent terminal 3 feet horizontally WARNING from the vent of any side wall vented fuel gas appliance or electric clothes dryer, except in THE VENT MUST BE CLAMPED TO THE the case where two or more of these furnaces FURNACE PANEL USING THE GASKET AND are multi-vented.
10. Complete the venting as installation requires. If exiting the top panel, use two street elbows IMPORTANT: Keep pressure switch hose above to route the vent. One elbow secured to the in- heat exchanger drain. ducer, will angle toward the front of cabinet with ORIENTATION ROTATE RECOMMEND...
Page 27
FIGURE 21A - DIRECT VENT TERMINAL CLEARANCES...
Page 29
FIGURE 22 - UPFLOW VENT AND DRAINING OPTION Instructions for Upfl ow with Top Venting Connect two (2) 2” Street elbows (in parts bag) to the coupler on the ex- hauster (Add 2” nipple for 120K BTU units). Ensure exhauster coupler drain outlet is facing downward 15°.
Page 30
Instructions for Upfl ow with Right Side Venting Remove 2.5” knockout and connect 2” nipple approximately 2.5” long (fi eld supplied) to the coupler on the exhauster. Ensure exhauster coupler drain outlet is facing downward 15°. Connect 2” elbow and 2” vent pipe (fi eld supplied) Install gasket on panel then vent bracket, use three (3) self tapping screws (all parts from parts bag).
Page 31
FIGURE 24 - HORIZONTAL RIGHT VENT AND DRAINING OPTION Instructions for Horizontal Right with Right Side Venting Connect two (2) 2” Street elbows (in parts bag) to the coupler on the exhauster Remove two (2) 7/8” knockouts and install the condensate trap bracket by (Add 2”...
Page 32
FIGURE 25 - DOWNFLOW VENT AND DRAINING OPTION Instructions for Downfl ow with Left Side Venting Remove 2.5” knockout and connect 2” nipple approximately 2.5” long (fi eld supplied) to the coupler on the exhauster. Ensure exhauster coupler drain outlet is facing downward 15°. Connect 2”...
13 - CONDENSATE DRAINS The furnace may condense as much as a 4½ ½” drain tube on the exhauster coupling drain. Fasten by tightening the tube clamp approxi- pounds of water per hour (approximately 2 imperial mately ⅛” from the end of the tube. quarts, 2½...
IMPORTANT: If an air conditioning evapora- FIGURE 27 - CONDENSATE BYPASS tor coil drain is to share the furnace drain line, it should be connected with a tee fi tting down- stream from the trap. Do not connect the evapo- rator coil condensate drain upstream of the fur- nace drain trap assembly.
14 - GAS SUPPLY AND PIPING FIGURE 28 - FURNACE GAS PIPE CONNECTIONS GAS SUPPLY (NOTE RUBBER GROMMET) WARNING THIS FURNACE IS FACTORY EQUIPPED TO BURN NATURAL GAS ONLY. CONVERSION TO LP GAS REQUIRES SPECIAL NATURAL GAS TO LP CONVERSION KIT. FAILURE TO USE THE PROPER CONVERSION KIT CAN CAUSE FIRE, EXPLOSION, CARBON MONOXIDE POISONING, PROPERTY DAM-...
Gas piping that has not been pressure tested, from GAS INLET PRESSURE the manual shut-off valve to the furnace gas valve for example, should be leak tested using an elec- The natural gas inlet supply pressure should be 5” tronic combustible gas detector, a commercially to 7”...
13. Replace the High regulator adjustment 5. Measure furnace gas inlet pressure with screw and adjust approximately 12 turns to the burners fi ring. Inlet pressure must be within the range specifi ed on the furnace rating plate. bottom. 5-7” w.c (Natural Gas) or 11-14” w.c. (LP). If the inlet pressure differs from the rating plate, 14.
If problems were encountered with obtaining enough FIGURE 34 - REGULATOR ADJUSTMENT pressure on the manifold, fi rst examine the gas pip- ing system to ensure that it is correctly sized. Pipe sizing is specifi ed in CAN/CGA-B-149.1 & 2, and in NFPA 54 / ANSI Z223.1.
16 - ELECTRICAL SPECIFICATIONS Although a suitably located circuit may serve as ELECTRICAL WIRING & CONNECTIONS a service switch, a separate service switch is rec- ommended. A separate service switch is necessary Before proceeding with the electrical connections, if the circuit breaker is in a location where access- ensure that the available electrical supply is com- ing it would require getting close to the furnace, or patible with the voltage, frequency and phase listed...
be moved to the right hand side. The junction box 4. Fasten the junction box to the right hand panel. contains a BLACK wire to be connected with L1 NOTE: L1 (hot) and L2 (neutral) polarity must be (hot), a WHITE wire to be connected with L2, the observed when making fi...
uous low heat operation. Once high heat is started THERMOSTAT LOCATION from automatic staging, the demand for high heat remains until the heat call is satisfi ed. The thermostat should be located approximately 5 * Factory Setting feet above the fl oor, on an inside wall where there is good natural air circulation, and where the thermostat TWO STAGE THERMOSTAT will be exposed to average room temperatures.
Green LED will fl ash. If the High pressure switch NOTE: On initial startup, the drain trap assembly will be is closed the Green LED will be on. High gas dry. A dry trap will allow fl ue gases to fl ow through the re- covery coil drain, which will prevent the condensate from valve drops out while High pressure switch is draining from the recovery coil.
Any adjustments to the burner manifold pressure Heating Value of Gas x 3600 Input = should be carried out with the use of a manometer Time in Sec. for 1 cu. ft. or calibrated magnehelic gauge. Do not adjust the where: gas valve pressure regulator more than ±0.3”...
2. Insert a duct thermometer in the return air Output duct as close to the furnace as practical. Ensure CFM = ∆T 1.085 x that the thermometer location will be unaffected by humidifi er bypass ducts, etc. Choose a loca- where: tion well within the main air stream.
Additional dehumidifi cation can be achieved by CONTINUOUS FAN OPERATION connecting a humidistat to the DEHUM and R ter- minals on the integrated furnace control board. In When the thermostat continuous fan (G) switch is this setup, the variable speed motor will operate at on without a call for heat or cooling, the indoor fan a 10% reduction in the normal cooling airfl...
Some paper media high effi ciency fi lters, some- TERMINATIONS times identifi ed as HEPA fi lters can do an effective The combustion air and exhaust terminals should and excellent fi ltration of the air; however, some be inspected occasionally to ensure that they are models may also cause a large pressure drop free of obstructions and debris.
BURNERS - The burners should be inspected doors closed to reduce the heating load on the to ensure that they are free of deterioration, dust system. and debris, and properly aligned with the heat ex- 3. Avoid excessive use of kitchen exhaust hoods changer.
TROUBLESHOOTING FLOWCHART SEQUENCE OF OPERATION Troubleshouting Flowchart Apply Power To Furnace Thermostat Calls For Heat Wait For Limit Circuit Air Proving Switches Wait For Air Proving Switch to Close and/or Reset Proved Open & Limit to Open. Flash(3) of Flame Rollout. Circuit Closed Flash(1) Combustion Air Blower On...
DIAGNOSTIC CODES FOR STATUS LED A RED LED is provided to indicate furnace operating status LED Condition Fault Condition Check LED ON Normal operation No action required. Control OK. LED OFF No power to control or Line voltage input power at L1 and Neutral control connectors control board.
DIAGNOSTIC CODES FOR STATUS LED A RED LED is provided to indicate furnace operating status LED Condition Fault Condition Check 6 Flashes Not Used 7 Flashes Pressure switch cycle Pressure switches operation, tubing and wiring. lockout Obstruction or restrictions in venting preventing proper air fl...
VENTING CHECKLIST Vent pipe must be sloped to drain from outlet back to furnace. Exposed vents and drains must be heat traced. Vents exiting house must be well sealed to prevent exhausts from re-enter- ing the house. Vents and intake must be 12” above grade. For Massachusetts see page 6. In Canada all venting material must be identifi...
24 - REPLACEMENT PARTS LIST REPLACEMENT PARTS LIST HIGH EFFICIENCY TWO STAGE GAS FURNACE Replacement Parts List Item Kit Number Repair Parts List for 95% Two Stage High Effi cient Furnace 550001515 FLAME ROLLOUT SWITCH 350F, ALL MODELS 550001528 FLAME SENSOR, ALL MODELS 550001656 TWO STAGE GAS VALVE 36G54, ALL MODELS 550001514...
Page 56
Replacement Parts List Item Kit Number Repair Parts List for 95% Two Stage High Effi cient Furnace 550001515 KIT,FLAME ROLLOUT SWITCH 350F, ALL MODELS 550001528 KIT,FLAME SENSOR, ALL MODELS 550001656 KIT,GAS VALVE, HIGH 2ST, ALL MODELS White Rodgers 36G54 Two Stage 24V gas valve set for NG 550001514 KIT,LIMIT SWITCH 160F 100-5, 120-5 550001525...
Need help?
Do you have a question about the freewatt FW95V and is the answer not in the manual?
Questions and answers