Page 3
Mono CONTENTS Part 1 General Informa�on ................3 Part 2 Engineering Data ................17 Part 3 Installa�on and Field Se�ngs ............55...
Mono Part 1 General Informa�on 1 Mono System ..................... 4 2 Unit Capaci�es ................... 6 3 Nomenclature .................... 6 4 System Design and Unit Selec�on .............. 7 5 Typical Applica�ons ................... 9...
Mono 1 Mono System 1.1 System Schema�c Figure 1-1.1: System schematic Mono is an integrated air to water heat pump system which is one-stop solu�on for space hea�ng, space cooling and dome- s�c hot water, The outdoor heat pump system extracts heat from the outdoor air and transfers this heat through refrige- rant piping to the plate heat exchanger in the hydronic system.
Page 7
Mono 1.2 System Configura�ons Mono can be configured to run with the electric heater either enabled or disabled and can also be used in conjunc�on with an auxiliary heat source such as a boiler. The chosen configura�on affects the size of heat pump that is required. Three typical configura�ons are described below. Refer to Figure 1-1.2.
Mono 4 System Design and Unit Selec�on 4.1 Selec�on Procedure Step 1: Total heat load calcula�on Calculate condi�oned surface area Select the heat emi�ers (type, quantity, water temperature and heat load) Step 2: System configura�on Decide whether to include AHS and set AHS’s switching temperature Decide whether backup electric heater is enabled or disabled Step 3: Selec�on of outdoor units Determine required total heat load on outdoor units...
Page 10
Mono 4.2 Leaving Water Temperature (LWT) Selec�on The recommended design LTW ranges for different types of heat emi�er are: For floor hea�ng: 30 to 35⁰C For fan coil units: 30 to 45⁰C For low temperature radiators: 40 to 50⁰C 4.3 Op�mizing System Design To get the most comfort with the lowest energy consump�on with Mono heat pump, it is important to take account of the following considera�ons:...
Mono 5 Typical Applica�ons 5.1 Applica�on 1 Indoor Outdoor 14.2 14.1 14.3 Applica�on 1 Figure 1-5.1: Legend Outdoor unit Domes�c hot water tank (Field supply) User interface 14.1 TBH: Domes�c hot water tank booster heater (Field supply) SV1:3-way valve (Field supply) 14.2 Coil 1, heat exchanger for heat pump Balance tank (Field supply)
Page 12
Mono 5.1.1 Space hea�ng The ON/OFF signal and opera�on mode and temperature se�ng are set on the user interface. P_o (6) keeps running as long as the unit is ON for space hea�ng, SV1(4) keeps OFF. 5.1.2 Domes�c water hea�ng The ON/OFF signal and target tank water temperature (T5S) are set on the user interface.
Page 13
Mono 5.2 Applica�on 2 ROOM THERMOSTAT Control for Space hea�ng or cooling need to be set on the user interface. It can be set in three ways: MODE SET/ONE ZONE/DOUBLE ZONE. The indoor unit can be connected to a high voltage room thermostat and a low voltage room thermostat.
Page 14
Mono 5.2.2 Mode set control Indoor Outdoor FCU1 FCU2 FCUn FHL1 FHL2 FHLn Figure 1-5.3: Application 2- Mode set control Legend Outdoor unit Shut-off valve (Field supply) User interface Filling valve (Field supply) Balance tank (Field supply) Drainage valve (Field supply) Automa�c bleed valve Collector/distributor (Field supply) Drainage valve...
Page 15
Mono 5.2.3 Double zone control 15 17 19 19 Figure 1-5.4: Application 2-Double zone control Legend Outdoor unit Shut-off valve (Field supply) User interface Shut-off valve (Field supply) Balance tank (Field supply) Filling valve (Field supply) Automa�c bleed valve Drainage valve (Field supply) Drainage valve Collector/distributor (Field supply) P_o: Zone A circula�on pump (Field supply)
Page 16
Mono 5.3 Applica�on 3 5.3.1 Group control Figure 1-5.5: Application 3- Parallel system control Legend Master unit 11.3 Coil 2: heat exchanger for heat pump 1.2…n Slave unit Filter(Accessory) User interface Check valve (Field supply) SV1: 3-way valve(Field supply) Shut-off valve(Field supply) Balance tank(Field supply) Tap water inlet pipe(Field supply) Automa�c bleed valve...
Page 17
Mono water outlet pipe. Space hea�ng All salve units can operate in space hea�ng mode. The opera�on mode and se�ng temperature are set on the user interface(2). Due to changes of the outdoor temperature and the required load indoors, mul�ple outdoor units may operate at different �mes.
Page 23
Mono Outdoor unit model name KHC-12RY3-B KHC-14RY3-B KHC-16RY3-B Air side heat exchanger Finned tube Refrigerant R32 1.75kg Unit dimension (W × H× D) 1385×865×523 Packing dimension (W × H× D) 1465×1035×560 Net/Gross weight 149/177 Cooling Outdoor air -5~43 °C temperature Hea�ng -25~35 °C...
Mono 2 Electrical characteris�cs O utdoor unit P ower current C ompressor F an S ystem Voltage Min. Max. T OCA R LA KHC-06RY1-B 220~240 13.5 0.10 KHC-08RY3-B 380~415 14.5 0.17 KHC-10RY3-B 380~415 15.5 0.17 KHC-12RY3-B 380~415 9.15 0.17 KHC-14RY3-B 380~415 10.15...
Mono 3 Dimensions and Center of Gravity 6kW models Figure 2-3.1: KHC-06RY1-B dimensions and center of gravity (unit: mm) unit: mm Model 8/10/12/14/16kW models Figure 2-3.2: KHC-08RY3-B, KHC-10RY3-B, KHC-12RY3-B, KHC-14RY3-B, KHC-16RY3-B dimensions and center of gravity (unit: mm) unit: mm...
Mono 5 Opera�ng Limits Figure 2-5.1: Heating operating limits Figure 2-5.2: Cooling operating limits Figure 2-5.3: Domestic hot water operating limits Abbrevia�ons: T4: Outdoor temperature(°C) T1: Leaving water temperature (°C) IBH: Backup electric heater AHS: Addi�onal heat source Notes: IBH/AHS only Water flow temperature drops or rises interval If IBH/AHS se�ng is valid, only IBH/AHS turns on;...
Mono 7 Sound Levels 7.1 Overall Table 2-7.1: Sound pressure levels Model name KHC-06RY1-B 47.5 KHC-08RY3-B 48.5 KHC-10RY3-B 50.5 KHC-12RY3-B 53.5 KHC-14RY3-B 54.0 KHC-16RY3-B 58.0 Notes: Sound pressure level is measured at a posi�on 1m in front of the unit and (1+H)/2m (where H is the height of the unit) above the floor in a semi- anechoic chamber.
Page 53
Mono 7.2 Octave Band Levels Figure 2-7.2: KHC-06RY1-B octave band levels Cooling in rated frequency Outdoor air temperature 35⁰C DB; EWT 12⁰C, LWT 7⁰C Cooling in rated frequency NR-90 Outdoor air temperature 35⁰C NR-80 DB; EWT 23⁰C, LWT 18⁰C NR-70...
Page 54
Mono Figure 2-7.4: KHC-10RY3-B octave band levels Cooling in rated frequency Outdoor air temperature 35⁰C DB; EWT 12⁰C, LWT 7⁰C NR-90 Cooling in rated frequency NR-80 Outdoor air temperature 35⁰C NR-70 DB; EWT 23⁰C, LWT 18⁰C NR-60 Heating in rated frequency NR-50 Outdoor air temperature 7⁰C DB, NR-40...
Page 55
Mono Figure 2-7.6: KHC-14RY3-B octave band levels Cooling in rated frequency Outdoor air temperature 35⁰C DB; EWT 12⁰C, LWT 7⁰C NR-90 Cooling in rated frequency NR-80 Outdoor air temperature 35⁰C NR-70 DB; EWT 23⁰C, LWT 18⁰C NR-60 Heating in rated frequency NR-50 Outdoor air temperature 7⁰C DB, NR-40...
Installation and owner’s Mono manual(this book) Wired controller Technical data manual 8 Accessories Operation manual Thermistor for domestic hot water tank or zone2 8.1 Standard accessories Y-shape filter water flow or balance tank Table 2-8.1: Standard accessories Technical data manual Name Shape Quan�ty...
Page 57
Mono Part 3 Installa�on and Field Se�ngs 1 Preface to Part 3 .................. 56 2 Installa�on ..................57 3 Water Pipework .................. 62 4 Electrical Wiring .................. 65 5 DIP Switch Se�ngs ................68 6 Internal Circula�on Pump ..............68 7 User Interface Field Se�ngs ..............
Mono 1 Preface to Part 3 Notes for Installers Boxes The informa�on contained in this Engineering Data Book may primarily be of use during the system design stage of a Mono project. Addi�onal important informa�on which may primarily be of use during field installa�on has been placed in boxes, such as the example below, �tled “Notes for installers”.
Mono 2 Installa�on Acceptance and Unpacking Notes for installers When units are delivered check whether any damage occurred during shipment. If there is damage to the surface or outside of a unit, submit a wri�en report to the shipping company. ...
Page 60
Mono Outdoor units should be installed in well-drained, well-ven�lated posi�ons. Outdoor units should be installed in posi�ons that are as close as possible to the heat emi�ers. Outdoor units should be installed in posi�ons that are sufficiently close to the desired posi�on of the wired controller that the controller’s wiring length limita�on will not be exceeded.
Page 61
Mono Cold Climate Installa�on In cold climate loca�ons installa�on should take account of the following considera�ons: Figure 3-2.4: Snow shielding Never install the unit at a site where the suc�on side may be exposed directly to wind. To prevent exposure to wind, install a baffle plate on the air discharge side of the unit. To prevent exposure to wind, install the unit with its suc�on side facing the wall.
Page 62
Mono Drainage Drainage ditch should be provided to allow drainage of condensate that may form on the air side heat exchanger when the unit is running in hea�ng mode or domes�c hot water mode. The drainage should ensure that condensate is directed away from roadways and footpaths, especially in loca�ons where the climate is such that condensate may freeze.
Page 63
Mono Figure 3-2.9: Installation with obstacles behind the unit 2.9.2 Installa�on in Rows Figure 3-2.10: Multi-row installation Table 3-2.3: Multiple row installation spacing requirements Model A (mm) B1 (mm) B2 (mm) C (mm) 6 kW ≥ 2500 ≥ 1000 ≥ 300 ≥...
Mono 3 Water Pipework Water Circuit Checks Mono units are equipped with a water inlet and outlet for connec�on to a water circuit. Mono units should only be connec- ted to closed water circuits. Connec�on to an open water circuit would lead to excessive corrosion of the water piping. Only materials complying with all applicable legisla�on should be used.
Page 65
Mono Water Circuit Connection Water connec�ons must be made correctly in accordance with the labels on the outdoor unit, with respect to the water inlet and water outlet. If air, moisture or dust gets in the water circuit, problems may occur. Therefore, always take into account the following when connec�ng the water circuit: Use clean pipes only.
Mono As a result, the hydraulic components might freeze up a�er all. Take preven�ve ac�ons to ensure a minimal exposure of the glycol to air. Due to the presence of glycol, corrosion of the system is possible. Uninhibited glycol will turn acidic under the influence of oxygen.
Mono 4 Electrical Wiring General Notes for installers Cau�on All installa�on and wiring must be carried out by competent and suitably qualified, cer�fied and accredited professionals and in accordance with all applicable legisla�on. Electrical systems should be grounded in accordance with all applicable legisla�on. ...
Mono Make sure no external pressure is applied to the terminal connectors. When installing the ground fault circuit interrupter make sure that it is compa�ble with the inverter (resistant to high frequency electrical noise) to avoid unnecessary opening of the ground fault circuit interrupter This unit is equipped with an inverter.
Page 69
Mono Figure 3-4.4: Wiring overview for 8/10/12/14/16kW models Item Descrip�on Item Descrip�on Outdoor unit SV2: 3-way valve (field supply) Solar energy kit (field supply) SV1: 3-way valve for domes�c hot water tank (field supply) User interface Domes�c hot water tank Room thermostat (field supply) Booster heater Boiler (field supply)
Mono 5 DIP Switch Se�ngs DIP switch is located on the hydraulic module main control board and allows configura�on of addi�onal hea�ng source thermistor installa�on, the second inner backup heater installa�on, etc. Factory Switch ON=1 OFF=0 defaluts 00=IBH(One-step control) Set according to 01=IBH(Two-step control) unit configura�on 11=IBH(Three-step control)
Mono 7 User Interface Field Se�ngs Introduc�on During installa�on, the Mono’s se�ngs and parameters should be configured by the installer to suit the installa�on configu- ra�on, climate condi�ons and end-user preferences. The relevant se�ngs are accessible and programmable through the FOR SERVICEMAN menu on the Mono’s user interface.
Mono FOR SERVICEMAN Menu FOR SERVICEMAN allows installers to input the system configura�on and set Figure 3-7.2: FOR SERVICEMAN password screen the system parameters. To enter FOR SERVICEMAN, go to MENU > FOR FOR SE RVICEMAN SERVICEMAN. Please input password: Enter the password, using ◄...
Page 74
Mono Only when the space hea�ng/cooling is OFF will the heat pump operate to heat domes�c water. DHW PUMP_D sets whether or not the DHW pump is controlled by the Mono heat pump. If the DHW pump is to be controlled by the Mono unit, select YES.
Page 75
Mono t_INTERVAL_DHW sets the DHW mode compressor re-start delay. When the compressor stops running, it will not re-start un�l at least t_INTERVAL_DHW minutes have elapsed. dT5_TBH_OFF sets the temperature difference between the DHW set temperature (T5S) and the DHW tank water temperature (T5) below which the immersion is not used.
Page 76
Mono PUMP_D TIMER sets whether or not the user is able to set the DHW pump (field supply) in DHW mode. For installa�ons with a DHW pump, select ON so that the user is able to set pump start �mes. PUMP_D RUNNING TIME sets the length of �me the pump runs for at each of the user-specified start �mes on the DHW PUMP tab on the DOMESTIC HOT WATER (DHW) menu, if TIMER RUNNING is enabled.
Page 77
Mono 7.8 “TEMP. TYPE SETTING Menu”. t_INTERVAL_C sets the cooling mode compressor re-start delay. When the compressor stops running, it will not re-start un�l at least t_INTERVAL_C minutes have elapsed. T1SetC1 sets the temperature 1 of automa�c se�ng curve for cooling mode. T1SetC2 sets the temperature 2 of automa�c se�ng curve for cooling mode.
Page 78
Mono dT1SH sets the temperature difference between the heat pump leaving water Figure 3-7.16: dTSH temperature (T1) and the heat pump leaving water set temperature (T1S) above which the heat pump provides heated water to the space hea�ng terminals. Note: Only when ROOM TEMP is enabled will this func�on be available dTSH sets the temperature difference between the actual room temperature (Ta) and set room temperature (TS) above...
Page 79
Mono TEMP. TYPE SETTING Menu MENU > FOR SERVICEMAN > TEMP. TYPE SETTING Figure 3-7.19: TEMP. TYPE SETTING menu The TEMP. TYPE SETTING is used for selec�ng whether the water flow 5 TEMP. TYPE SETTING 5.1 WATER FLOW TEMP. temperature or room temperature is used to control the ON/OFF of the heat 5.2 ROOM TEMP.
Page 80
Mono Figure 3-7.23: DOUBLE ZONE to YES and set ROOM TEMP. to NON meanwhile set WATER FLOW TEMP. to YES or NON ◄ Homepage (zone 1) Addi�on page (zone 2) If set DOUBLE ZONE and ROOM TEMP. to YES, meanwhile set WATER FLOW TEMP. to YES or NON, the following page will be displayed.
Page 81
Mono 7.10 OTHER HEATING SOURCE Menu 7.10.1 OTHER HEATING SOURCE menu overview MENU > FOR SERVICEMAN > OTHER HEATING SOURCE Figure 3-7.26: OTHER HEATING SOURCE menu 7 OTHER HEATING SOURCE 7.1 dT1_IBH_ON 5°C 7.2 t_IBH_DELAY 30MIN 7.3 T4_IBH_ON -5°C 7.4 dT1_AHS_ON 5°C 7.5 t_AHS_DELAY 30MIN...
Mono 7.11 HOLIDAY AWAY SETTING Menu MENU > FOR SERVICEMAN > HOLIDAY AWAY SETTING Figure 3-7.29: HOLIDAY AWAY SETTING menu The HOLIDAY AWAY SETTING menu se�ngs are used to set the outlet water 8 HOLIDAY AWAY SETTING temperature to prevent water pipes freezing when away from home in cold 8.1 T1S_H.A._H 20°C weather seasons.
Page 83
Mono 7.14 TEST RUN 7.14.1 TEST RUN Menu overview MENU > FOR SERVICEMAN > TEST RUN TEST RUN is used to check that the valves, air purge func�on, circula�on pump, space cooling mode, space hea�ng mode and DHW mode are all opera�ng correctly. Figure 3-7.32: TEST RUN start screen and TEST RUN menu 11 TEST RUN 11 TEST RUN...
Page 84
Mono 7.14.3 AIR PURGE opera�on MENU > FOR SERVICEMAN > TEST RUN > AIR PURGE Once installa�on is complete it is important to run the air purge func�on to remove any air which may be present in the water piping and which could cause malfunc�ons during opera�on. Figure 3-7.35: AIR PURGE operation The AIR PURGE opera�on is used to remove air from the water piping.
Page 85
Mono 7.14.6 HEAT MODE RUNNING opera�on Figure 3-7.38: HEAT MODE RUNNING display The HEAT MODE RUNNING opera�on is used to check the opera�on of the 11 TEST RUN system in space hea�ng mode. Test run is on. Heat mode is on. During the HEAT MODE RUNNING opera�on the Mono unit leaving water set Leaving water temperature is temperature is 35°C.
Mono 7.15 SPECIAL FUNCTION Figure 3-7.40: Special functions menu 7.15.1 SPECIAL FUNCTION menu overview 12 SPECIAL FUNCTION 12 SPECIAL FUNCTION MENU > FOR SERVICEMAN > SPECIAL FUNCTION 12.1 PREHEATING FOR FLOOR ACTIVE THE SETTINGS AND ACTIVE THE “SPECIAL FUNCTION”? 12.2 FLOOR DRYING UP SPECIAL FUNCTION is used to pre-hea�ng floor and drying up floor once installa�on is complete or the first �me start up the unit or restart the unit a�er a long �me...
Page 87
Mono Figure 3-7.43: Preheating for floor screens 12.1 PREHEATING FOR FLOOR 12.1 PREHEATING FOR FLOOR Preheat for floor is Do you want to turn off the preheating running for 25 minutes. for floor function? Water flow temperature is 20°C. CONFIRM CONFIRM 7.15.3 FLOOR DRYING UP MENU >...
Mono 7.16 AUTO RESTART MENU > FOR SERVICEMAN > AUTO RESTART Figure 3-7.47: AUTO RESTART menu 13 AUTO RESTART AUTO RESTART sets whether or not the unit re-applies the user interface se�ngs 13.1 COOL/HEAT MODE when the power returns following a power failure. Select YES to enable auto restart or 13.2 DHW MODE NON to disable auto restart.
Page 89
Mono Ta-adj is an correc�on value for Ta. SOLAR INPUT sets whether solar control signal is connected to hydronic PCB. (0=NON; 1=CN18; Tsolar 2=CN11SL1SL2) F-PIPE LENGTH sets the length of refrigerant pipes between outdoor unit and indoor unit. RT/Ta_PCB sets whether M-kit is valid. Pump silent mode can decrease water pump maximum output by 5% in order to decrease the noise of heat pump.
Mono The STOP BIT of wired controller and upper computer so�ware should be the same to ensure the reliability of data transforma�on. 8 Opera�on parameter MENU > OPERATION PARAMETER This menu is for installer or service engineer reviewing the opera�on parameters. There are nine pages for the opera�ng parameter as following Figure 3-9.1: Operation parameter OPERATION PARAMETER...
When the product is connected to the network, please make sure that the phone is as close as possible to the product. KAISAI only supports 2.4GHz band routers at present. Special characters (punctua�on, spaces, etc.) are not recommended as part of the WLAN name. It is recommended that you connect no more than 10 devices to a single router lest home appliances are affected by weak or unstable network signal.
Page 92
Mono Log in or register In case of a new user registra�on it is necessary to enter a verifica�on code sent to the specified e-mail address. Accept the privacy policy and condi�ons for using the applica�on...
Mono Wi-Fi connec�on Device management Network name and password From the applica�on, you can may not contain add new devices or manage exis�ng ones. languagespecific or special characters.
Page 94
Mono AP mode on the controller Choose the right arrow on the controller to go to the AP mode. When the Wi-Fi icon starts to flash, move forward.
Page 95
Mono No access to the Internet Confirm the message displayed on the phone’s screen by choosing OK.
Mono 10 USB func�on guidelines 10.1 Parameters se�ng transfer between wired controllers Installer can quickly copy the wired controller parameter se�ngs from unit A to unit B via USB disk, which save the �me of on-site installa�on. Steps are as follows: Step 1: Plug U disk into the port of hydronic PCB of A unit.
Page 97
Mono 10.2 Convenient program upgrade for unit There is no need to carry any heavy equipment but only USB disk can realize program upgrade. Steps are as follows: Step 1: Copy new program in U disk root directory where other files in bin format are not allowed in Step 2: Power on and make sure communica�on is normal.
Mono 11 Climate Related Curves The climate related curves can be selected in the user interface, MENU > PRESET TEMPERATURE > WEATHER TEMP. SET. In cooling/mode mode, eight curves which are already set in the user interface Figure 3-9.1: WEATHER TEMP. SET menu can be selected.
Page 99
Mono Figure 3-9.3: High temperature curves for heating mode T1S(℃) Curve 1 Curve 2 Curve 3 Curve 4 Curve 5 Curve 6 Curve 7 Curve 8 T4(℃) -30 -25 -20 -15 -10 Outdoor ambient temperature (⁰C ) Notes: It only has the curves of the high temperature se�ng for hea�ng, if the high temperature is set for hea�ng. Curve 4 is default in high temperature hea�ng mode and curve 6 is default in ECO mode.
Page 100
Mono Figure 3-9.5: High temperature curves for cooling mode T1S(℃) Curve 1 Curve 2 Curve 3 Curve 4 Curve 5 Curve 6 Curve 7 Curve 8 T4(℃) Outdoor ambient temperature (⁰C ) Notes: It only has the curves of the high temperature se�ng for cooling, if the high temperature is set for cooling. Curve 4 is default in high temperature cooling mode and curve 6 is default in ECO mode.
Mono 12 Error Code Table Table 3-10.1: Error code table Error code Content Transducer module temperature too high protect Water flow failure (E8 appears 3 �mes) Phase sequence error (for 3 phase models) Communica�on error between the main control board of hydraulic module and user interface Backup electric heater exchanger water outlet temperature sensor T1 error Domes�c hot water tank temperature sensor T5 error Air side heat exchanger refrigerant outlet temperature sensor T3 error...
Page 102
Mono DC bus high voltage protec�on MCE error Zero speed protec�on Phase sequence error Compressor frequency varia�on greater than 15Hz within one second protec�on Actual compressor frequency differs from target frequency by more than 15Hz protec�on Water side heat exchanger an�-freeze protec�on High temperature protec�on of refrigerant outlet temperature of condenser in cooling mode Water side heat exchanger inlet temperature is higher than outlet temperature in hea�ng/DHW mode PED board error...
Need help?
Do you have a question about the KHC-06RY1-B and is the answer not in the manual?
Questions and answers