Carrier WeatherMaker 50FE-16 Series Installation Instructions Manual
Carrier WeatherMaker 50FE-16 Series Installation Instructions Manual

Carrier WeatherMaker 50FE-16 Series Installation Instructions Manual

Single package rooftop cooling only with puron advance (r-454b) refrigerant and ecoblue fan technology
Table of Contents

Advertisement

Quick Links

CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Rated Indoor Airflow (cfm) . . . . . . . . . . . . . . . . . . . . . 2
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Step 1 - Plan for Unit Location . . . . . . . . . . . . . . . . 6
Step 3 - Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . . 7
Step 4 - Provide Unit Support . . . . . . . . . . . . . . . . . 7
• ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR
Step 5 - Field Fabricate Ductwork . . . . . . . . . . . . . . 7
Step 6 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . 9
Step 8 - Install Outside Air Hood . . . . . . . . . . . . . . 10
Electric Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
®
CONTROL CONNECTIONS
(Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500422-01
Installation Instructions
Printed in U.S.A.
Form No. 50FE-16-01SI
Single Package Rooftop Cooling Only
with Puron Advance™ (R-454B) Refrigerant
and EcoBlue™ Fan Technology
Leak Dissipation System . . . . . . . . . . . . . . . . . . . . .27
Page
EconomizerONE (Factory Option) . . . . . . . . . . . . . .30
Step 12 - Install Accessories . . . . . . . . . . . . . . . . .52
Step 13 - Fan Speed Set Up . . . . . . . . . . . . . . . . . .52
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified service personnel should install, repair, or
service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of
cleaning coils and filters and replacing filters. All other operations
should be performed by trained service personnel. When working
on air-conditioning equipment, observe precautions in the
literature, tags and labels attached to the unit, and other safety
precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguisher
available for all brazing operations.
It is important to recognize safety information. This is the
safety-alert symbol
in instructions or manuals, be alert to the potential for personal
injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
®
WeatherMaker
. When you see this symbol on the unit and
Pg 1
4-24
50FE-*16
Replaces: New

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the WeatherMaker 50FE-16 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier WeatherMaker 50FE-16 Series

  • Page 1: Table Of Contents

    ® WeatherMaker 50FE-*16 Single Package Rooftop Cooling Only with Puron Advance™ (R-454B) Refrigerant and EcoBlue™ Fan Technology Installation Instructions CONTENTS Leak Dissipation System .....27 •...
  • Page 2: Electrical Shock Hazard

    DANGER AVERTISSEMENT ELECTRICAL SHOCK HAZARD Soyez prudent lors de l’entretien des bornes du compresseur. Les anomalies du système ou du compresseur peuvent déloger Failure to follow this warning will result in personal injury or les bornes, permettant à l’huile et au réfrigérant de s’évacuer death.
  • Page 3 Position: 9 10 11 12 13 14 15 16 17 18 Example: Unit Heat Type Packaging 48 = Cooling with Electric Heat 0 = Standard ® Model Series - WeatherMaker Electrical Options FE = Entry Tier Puron Advance™ A = None C = Non-Fused Disconnect (NFDC) D = Thru-The-Base Connections (TTB) Heat Size...
  • Page 4 Fig. 2 — 50FE-*16 Unit Dimensional Drawing...
  • Page 5 Fig. 2 — 50FE-*16 Unit Dimensional Drawing (cont)
  • Page 6: Installation

    DIMENSION LOCATION CONDITION in. (mm) 48 (1219) Unit disconnect is mounted on panel. 18 (457) No disconnect, convenience outlet option. 18 (457) Recommended service clearance. 12 (305) Minimum clearance. 42 (1067) Surface behind servicer is grounded (e.g., metal, masonry wall). 36 (914) Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass).
  • Page 7: Curb-Mounted Installation

    CURB-MOUNTED INSTALLATION SLAB MOUNT (HORIZONTAL UNITS ONLY) Install curb Provide a level concrete slab that extends a minimum of 6 in. (150 mm) beyond unit cabinet. Install a gravel apron in front of Install field-fabricated ductwork inside curb condenser coil air inlet to prevent grass and foliage from obstruct- Install accessory thru-base service connection package ing airflow.
  • Page 8 Fig. 5 — 50FE-*16 Roof Curb Details...
  • Page 9: Step 6 - Rig And Place Unit

    Place All Gasket in Place Before Placing Unit on Roof Curb. (914-1371) “B” 36”-54” “C” Detail “A” Duct End “A” “A” See Detail “A” DIMENSIONS MAX WEIGHT UNIT 50FE-*16 2088 116.0 2945 53.0 1345 59.5 1510 NOTE(S): 1. Dimensions in () are in millimeters. 2.
  • Page 10: Step 7 - Convert To Horizontal And Connect

    Step 7 — Convert to Horizontal and Connect Unit is shipped in the vertical duct configuration. Unit without factory-installed economizer or return air smoke detector option may be field-converted to horizontal ducted configuration using accessory CRDUCTCV002A00. To convert to horizontal config- uration, remove screws from side duct opening covers and remove covers.
  • Page 11: Step 9 - Install External Condensate Trap And Line

    Panel Minimum Pitch 1 in. (25 mm) Per Base Rail 10 ft (3 m) of Line Indoor Coil 3 in. (76 mm) Access Panel Open Vent See Note To Roof Drain Screw Roof Drain Plug Curb NOTE: Trap should be deep enough to offset maximum unit static Left difference.
  • Page 12: Fire Hazard

    Fig. 16 — Conduit into Factory Option Disconnect Fig. 19 — Mounting Position for Field Disconnects (over 100A) Fig. 17 — Conduit into Control Box Fig. 20 — Mounting Position for Field Disconnects (up to 100A) Field power wires are connected to the unit at line-side pressure lugs at the main terminal block (TB1) or at factory-installed option non-fused disconnect switch.
  • Page 13: Field Wiring

    Such operation would invalidate any Disconnect factory test leads; discard. applicable Carrier warranty. Fig. 22 — Power Wiring Connections UNITS WITH FACTORY-INSTALLED NON-FUSED  TEST LEADS - Unit may be equipped with short leads (pigtails)
  • Page 14: Units Without Factory-Installed Non-Fused Disconnect

    Install the handle on to the painted cover horizontally with CONVENIENCE OUTLETS the red arrow pointing to the left. 10. Secure the handle to the painted cover with (2) screws and WARNING lock washers supplied. 11. Engaging the shaft into the handle socket, re-install (3) ELECTRICAL OPERATION HAZARD hex screws on the NFD enclosure.
  • Page 15: All Units

    GFCI Receptacle Cover — While-In-Use Not Included Weatherproof Gasket Baseplate For GFCI Receptacle Fig. 26 — Weatherproof Cover Installation UNIT CONNECT PRIMARY TRANSFORMER Non-powered type VOLTAGE CONNECTIONS TERMINALS Requires the field installation of a general-purpose 125-v 15-A L1: RED+YEL H1+H3 208, 230 L2: BLU+YEL H2+H4...
  • Page 16: Field Control Wiring

    The 50FE-*16 requires an external temperature control device. This device can be a thermostat (field-supplied) or a SystemVu™ 1-1/2 in. Electrical controller (available as factory-installed option for use on a Carrier Bulkhead Comfort Network or as a stand-alone control). All field added ®...
  • Page 17: Electric Heaters

    Heater modules are installed in the compartment below the indoor (supply) fan outlet. Access is through the electric heat access panel. See Fig. 32-34. Not all available heater modules may be used in every unit. Use only those heater modules that are UL listed for use in a specific size unit.
  • Page 18: Single Point Boxes And Supplementary Fuses

    SINGLE POINT BOXES AND SUPPLEMENTARY FUSES SINGLE POINT BOXES WITHOUT FUSES When the unit MOCP device value exceeds 60-A, unit-mounted Unit heater applications not requiring supplemental fuses require a supplementary fuses are required for each heater circuit. These special single point box without any fuses. The accessory single fuses are included in accessory single point boxes, with power point boxes contain a set of power taps and pigtails to complete distribution and fuse blocks.
  • Page 19: Humidi-Mizer

    This device may be a separate humidistat control (con- by contact with the condenser coil. tact closes on rise in space RH above control setpoint) or a com- bination thermostat-humidistat control device such as Carrier’s Connect one of the leads from the 2-conductor cable to the Edge ®...
  • Page 20 Programmable Thermostat Unit Control Board Thermostat Connections O/W2/B S RTN Fig. 40 — 50FE-*16 Unit with Humidi-MiZer Adaptive Dehumidification System with Edge ® Pro Thermidistat Device...
  • Page 21 Fig. 41 — 50FE-*16 Typical Control Wiring Diagram, Electro-Mechanical with POL224 Controller...
  • Page 22 Fig. 42 — 50FE-*16 Typical Control Wiring Diagram, SystemVu™ Controller...
  • Page 23 Fig. 43 — 50FE-*16 Typical Electro-Mechanical Controller Power Wiring Diagram – 208/230, 460-3-60 Unit Shown...
  • Page 24 Fig. 44 — 50FE-*16 Typical SystemVu™ Controller Power Wiring Diagram – 575-3-60 Unit Shown...
  • Page 25: Humidi-Mizer Dehumidification System

    Humidi-MiZer Dehumidification System  DEHUM/MECH COOLING (SUBCOOLING) MODE (Optional) This mode increases the latent heat removal and decreases sen- sible cooling compared to normal cooling. This occurs when Units with the factory-installed Humidi-MiZer system option there is a cooling and dehumidification demands. are capable of providing multiple modes of improved dehu- midification as a variation of the normal cooling cycle.
  • Page 26 Indoor Supply Valve 3-Way Valve Condenser Coil Hot Gas Reheat Coil Outdoor Air Expansion Valve (TXV) Compressor Evaporator Coil = Closed Valve = Open Valve Indoor Return Air = 3-Way Valve Fig. 46 — Subcooling Mode – Humidi-MiZer System for 50FE**16 Indoor Supply Valve 3-Way...
  • Page 27: Leak Dissipation System

    SEQUENCE OF OPERATION Leak Dissipation System 50FE units use R-454B refrigerant. These units are equipped with The control functions as an R-454B refrigerant dissipation system. a factory installed R-454B leak dissipation system to ensure safe If the refrigerant detection sensor sends a signal indicating a re- operation in the event of a refrigerant leak.
  • Page 28 Detail A Detail B Detail A — Test Button Detail B — Status LED Fig. 51 — Dissipation Control Board — Shown without Dust Cover Press the Test button on the dissipation system control board to en- Table 5 — Minimum Dissipation Air Flows sure proper dissipation system operation under each test condition MINIMUM DISSIPATION AIR FLOW (cfm) listed below.
  • Page 29: Troubleshooting

    TROUBLESHOOTING For all flash codes, first try power cycling the system to remove the code. No Power Verify the wiring to/from pins 1 and 8 on the power harness plug. Check the 24V system wiring from the transformer. See Table 7 for details on the operating status and troubleshooting of the Dissipation system for the various flash codes.
  • Page 30: Economizerone (Factory Option)

    LED Indication EconomizerONE (Factory Option) NOTE: If different faulty events occur at the same time, the ECONOMIZER SETTINGS sensor/DAC LED lights up following this priority: Red  Interface Overview Yellow  Off. For example, if there is a humidity sensor error and air temperature failure at the same time, the sensor LED EconomizerONE turns red rather than yellow.
  • Page 31 Table 8 — LED Indication FREE SENSOR Power STATUS COOLING DAC LED Yellow Yellow Yellow Commissioning mode Blinking Blinking Blinking Power start-up Yellow On Yellow On Yellow On Free cooling is running Green On — — Free cooling is available Green —...
  • Page 32 Table 9 — Free Cooling Functions CONTROL MODE SENSORS USED ENABLE FREE COOLING? The outside air dry bulb temperature is compared with the set temperature OA (Outside Air) temperature sensor Control Mode 1 shutoff set point. • Fixed Dry Bulb If the outside air dry bulb temperature is below the temperature shutoff set MA (Mixed Air) temperature sensor point, then the outside air is used to meet all or part of the cooling demand.
  • Page 33 Table 10 — 1 and 2-Stage Cooling Stage I/O Logic Table 13 — Different Fan Speeds with Different Configured Outputs ECONOMIZER COOLING COOLING CONDITION MET STAGE 1 STAGE 2 FAN TYPE 1-SPEED COOLING 2-STAGE COOLING • Spd H (regardless of •...
  • Page 34 Table 15 — Different Damper Position Setting with Different Configured Outputs (DCV is Enabled) FAN TYPE 1-STAGE COOLING 2-STAGE COOLING • 2VENTMIN H to 2VENTMAX H (regardless of • 2VENTMIN H to 2VENTMAX H (regardless of 1-SPEED FAN cooling demand, OCC=Yes) cooling demand, OCC=Yes) 2VENTMIN L to 2VENTMAX L ...
  • Page 35 • If Exhaust Fan 2 is connected and configured, then Fault Detection and Diagnostics Exhaust Fan 2 parameter group (L, M, and H) is available, The economizer controller can detect and diagnose free cooling depending on fan configuration. faults, sensor operation faults, and damper modulating faults. It •...
  • Page 36: Wiring

    WIRING WARNING Failure to follow this caution may result in damage to equipment. Be sure to allow enough time for compressor startup and shutdown between checkout tests so that the compressors do not short-cycle.  Mounting Devices Connected to the Economizer Controller Devices like damper actuators, sensors (temperature sensor, hu- midity sensor, combination temperature and humidity sensor, CO...
  • Page 37 Table 17 — Economizer Control Wiring Settings LABEL TYPE DESCRIPTION RS485 Modbus A Line A RS485 Modbus B Line B ¬ GND_ISO Earth Ground Type II NTC 10K or 0-10 vdc Mixed or Discharge Air Temperature Sensor Mixed or Discharge Air Temperature Sensor Common Type II NTC 10K or 0-10 vdc Outside Air Temperature Sensor 0-10 vdc or 4-20mA...
  • Page 38 Connecting Peripheral Devices to the Economizer Controller See Fig. 60-64 for wiring details. • Outside Air: Connect to the Mixed or Discharge Air Temperature Sensor OAT and COM terminals of the Outside Air Temperature Sensor device. • Return Air (Differential): Return Air Temperature Sensor Connect to the RAT and S-COM...
  • Page 39: Pressure Sensor Connection

    • Outside Combination Temperature/ Humidity: Connect Combo Temperature and Humidity Sensor to the OAT, COM, and OAH terminals of the device. • Combo Temperature and Humidity Sensor Return Combination Temperature/ Humidity: Connect to the RAT, S-COM, and RAH terminals of the device. Fig.
  • Page 40: Setup And Configuration

    SETUP AND CONFIGURATION NOTE: Parameters and display menus may display differently/dynamically if different applications are config- ured. See Tables 18-25. IMPORTANT: Before setup and configuration, it is recom- mended to obtain some location-based values, such as shutoff points, or utilize the location services in the Climatix ™...
  • Page 41 Table 18 — Status Display PARAMETER DESCRIPTION VALUE 1FREECOOL Indicates if the system can use outdoor air for free cooling. 1ECON ENAB Indicates if outdoor air is being used for the first stage of cooling. Indicates if the space is occupied. If users choose ALWAYS for 6OCC when configuring I/Os, the parameter value is YES;...
  • Page 42 Table 19 — Parameter Settings — Basic PARAMETER DESCRIPTION RANGE DEFAULT Temperature shutoff set point can be obtained automatically if a smartphone or tablet is connected to the network provided by a Wi-Fi/WLAN stick 2 TEMP OFF plugged into the Economizer Controller and the mobile application is 48...80°F;...
  • Page 43 Table 20 — Parameter Settings — Advanced PARAMETER DESCRIPTION VALUE/RANGE DEFAULT 3FREEZE POS Anti-freeze protection damper position (closed or minimum). 3SD ACT POS Damper position during shutdown (open or closed). MAT sensor location: • Choose MAT if the sensor is installed before the DX (Direct Expansion) coil. 3DIF T LOC •...
  • Page 44 Table 21 — Parameter Settings — I/O Configurations (cont) PARAMETER DESCRIPTION VALUE DEFAULT Choose ACT FB if feedback signal is available from the connected damper ACT FB 6AUX-AI2 ACT FB actuator. Otherwise, choose NONE. NONE Choose “COOL 2” if Cooling Stage 2 is available (another compressor is COOL 2 6Y2O COOL 2...
  • Page 45: Installing Optional Hh57Lw001 Single Outside Air Enthalpy Sensor

    Table 24 — Enter Running State PARAMETER DESCRIPTION 8RUN STATE Change to Running State. Press Enter to confirm the change. 8ENTER RUN? Confirm the change to Running State. Perform factory reset. Press Enter to confirm the reset. (This action resets the controller 8FACTORY DEF password to default: OneBT.) 8DEF CONFIRM?
  • Page 46 Fig. 65 — HH57LW001 Dimensional, Connection and Switching Information Fig. 66 — HH79NZ039 Dry Bulb and Mixed Air Sensor Wiring Economizer Actuator Outside Air (this end) Damper Wiring Harness Return Air Damper Fig. 67 — EconomizerONE System Component Locations Fig. 68 — California Title 24 Zones...
  • Page 47 U.S. and Canada I-Codes / ASHRAE Zones Climate Zone 1 Climate Zone 5 and Marine Climate Zone 2 Climate Zone 6 Climate Zone 3 Climate Zone 7 and 8 Climate Zone 4 (Except Marine) Fig. 69 — U.S. and Canada Climate Zones Table 26 —...
  • Page 48 Economizers are shipped standard with an HH79NZ039 outside Table 27 — California Title 24 Regional High Limit air dry bulb sensor (refer to Fig. 66). System default setting (high Dry Bulb Temperature Settings temp limit) is 63°F (17°C) and has a range of 48°F to 80°F (9°C to REQUIRED HIGH LIMIT 27°C).
  • Page 49: Checkout

    CHECKOUT NOTE: All settings are stored in non-volatile flash memory. Status Inspect all wiring connections at the economizer module’s termi- nals, and verify compliance with the installation wiring diagrams. Use the Status menu (refer to Table 18) to check the parameter For checkout, review the Status of each configured parameter and values for the various devices and sensors configured.
  • Page 50: Troubleshooting

    TROUBLESHOOTING For EconomizerONE troubleshooting issues, see Table 29. Table 29 — Operating Issues and Concerns SYMPTOM REASON SOLUTION An alarm is displayed on the Sensor, damper, or the whole working Check sensor, damper, or the whole working system following the detailed alarm information. system may not work properly DAC LED is blinking RED Damper slippage...
  • Page 51: Systemvu™ Controller (Factory Option)

    ADDITIONAL APPLICATION DATA SystemVu™ Controller (Factory Option) For details on operating 50FE-*16 units equipped with the Refer to the application data sheet titled “Factory-Installed Smoke factory-installed SystemVu controller option, refer to the FC/GC Detector, for Small and Medium Rooftop Units 2 to 25 Tons” for Series Single Package Rooftop Units with SystemVu Controller discussions on additional control features of these smoke detectors Controls, Start-up, Operation and Troubleshooting manual.
  • Page 52: Step 11 - Adjust Factory-Installed Options

    NOTE: The Fan Speed Set Up labels are located on the High Step 11 — Adjust Factory-Installed Options Voltage cover in the Control Box. SMOKE DETECTORS Connect a multimeter to the vdc terminals on the UCB. Smoke detector(s) will be connected at the Unit Control Board Set the Range Switch to either A, B, or C per the Switch (UCB), at terminals marked “Smoke Shutdown.”...
  • Page 53: Units With Systemvu™ Controls

    ESP in. wg Factory Setting: Calculator 9.0 V 3000 Field Setting: 3250 Record field setting here 3500 3750 4000 Switch Range: 4250 4500 4.1 - 7.5 4750 10.0 6.9 - 8.7 5000 7.7 - 10.0 Field Accessories: Economizer * Overlap in A, B, C switch range designed for maximum field adjustment potential.
  • Page 54 Economizer Fig. 74 — Example of Fan Speed Set Up Labels for SystemVu™ Controls © 2024 Carrier Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500422-01 Printed in U.S.A.
  • Page 55: Preliminary Information

    START-UP CHECKLIST 50FE**16 Single Packaged Rooftop Electric Cooling Units (Remove and use for job file) NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preceding sections of this Installation Instruction document.
  • Page 56 (Y/N) _____ 10. Restore set points for thermostat and humidistat. (Y/N) _____ © 2024 Carrier Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500422-01 Printed in U.S.A.

Table of Contents

Save PDF