Exhausto VEX200 Series Manual

Hce electric heating coil with exact2 control system
Hide thumbs Also See for VEX200 Series:

Advertisement

Quick Links

3005111-2014-08-12
VEX250 HCE electric heating coil
with EXact2 control system
Product information........................................Chapter 1 + 5
Mechanical assembly.....................................Chapter 2
Electrical installation.......................................Chapter 3
Commissioning and operation........................Chapter 4
EXHAUSTO A/S
Odensevej 76
DK-5550 Langeskov
Tel.: +45 65 66 12 34
Fax: +45 65 66 11 10
exhausto@exhausto.dk
www.exhausto.dk
HCE-VEX250
Original instructions

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VEX200 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Exhausto VEX200 Series

  • Page 1 EXact2 control system Product information........Chapter 1 + 5 Mechanical assembly........Chapter 2 Electrical installation........Chapter 3 Commissioning and operation......Chapter 4 Original instructions EXHAUSTO A/S Tel.: +45 65 66 12 34 Odensevej 76 Fax: +45 65 66 11 10 DK-5550 Langeskov exhausto@exhausto.dk...
  • Page 2: Table Of Contents

    3005111-2014-08-12 1. Product information 1.1. Application......................3 1.1.1. Application.......................3 1.2. Description......................3 1.2.1. Construction of the heating coil...............3 1.3. Principal dimensions.....................4 2. Mechanical assembly 2.1. Unpacking......................5 2.1.1. Weight......................5 2.2. Position in relation to VEX..................5 2.2.1. Left/Right positioning..................5 2.2.2. Correct installation on the duct system............5 2.2.3.
  • Page 3: Product Information

    Product information 3005111-2014-08-12 1. Product information 1.1 Application 1.1.1 Application The EXHAUSTO VEX200 HCE heating coil is an accessory to the VEX200 range and is used to increase the temperature of the supply air. Designations used in these instructions Component term...
  • Page 4: Principal Dimensions

    Product information 3005111-2014-08-12 Pos. no. Part Function Temperature sensor Measures the temperature in the supply air duct Connection box Connection box for connecting the heating coil to the VEX unit control system and power sup- Isolation switch Isolation switch used for servicing Reset Manual reset 1.3 Principal dimensions...
  • Page 5: Mechanical Assembly

    Mechanical assembly 3005111-2014-08-12 2. Mechanical assembly 2.1 Unpacking Supplied compo- The following components are supplied: ● Electric heating coil with integral connection box. nents 2.1.1 Weight Heating coil weighs 29 kg 2.2 Position in relation to VEX 2.2.1 Left/Right positioning The heating coil is positioned on the supply air duct as shown below: 2.2.2 Correct installation on the duct system Position the heating coil on the supply air duct or directly on the ventilation unit supply...
  • Page 6: Location Of Te-Hce-Supply

    3005111-2014-08-12 The heating coil must always be supported - during fitting as well (The fixture for this is not part of the EXHAUSTO delivery). The heating coil must always be positioned so that ● air flows through it horizontally or ●...
  • Page 7: Electrical Installation

    Electrical installation 3005111-2014-08-12 3. Electrical installation 3.1 Connection diagram Diagram The diagram below illustrates the connection of the supply current and the heating coil connection box. 7/16...
  • Page 8: Connection Of Modbus Devices

    "Electrical Installation Guide for VEX with EXact control" for the VEX unit in question. This shows the method for connecting standard components on the connection box connection diagram. * Not supplied by EXHAUSTO MHCW/MHCE Heat control (water or electric)
  • Page 9: Cable (Type, Max. Length And Termination)

    Electrical installation 3005111-2014-08-12 3.2.2 Cable (type, max. length and termination) Cable EXHAUSTO recommends the use of 4-core, twisted pair, shielded cable. To limit □ voltage drop across the cable, 0.25 conductors are recommended. For correct connection of shielded cable to Modbus units, refer to the "Electrical Installation Guide"...
  • Page 10: Commissioning And Operation

    If heating is required, and airflow does not exceed 288 m³/h (80 l/s), an alarm is tripped. For more information about alarms refer to the "EXact2 Control System Basic In- structions for the VEX200 series". 4.3 Maintenance and alarms Maintenance See "Maintenance"...
  • Page 11 Commissioning and operation 3005111-2014-08-12 Alarms See "Alarms" section in the "EXact2 Control System Basic Instructions for VEX". 11/16...
  • Page 12: Technical Specifications

    Technical specifications 3005111-2014-08-12 5. Technical specifications 5.1 Electric heating coil Electric heating coil Weight Heating coil HCE, weight 29 kg Data Total power rating 12 kW Supply voltage to connection box 3 x 400 V + N + PE, 50 Hz Thermal fuse,(control system), TSA60 60 °C Thermal fuse, TSA70...
  • Page 13 Technical specifications 3005111-2014-08-12 Spare parts list The following parts are stocked as spares for the coil. Spare parts Electric heating control system, MHCE module 13/16...
  • Page 14 3005111-2014-08-12 14/16...
  • Page 15 3005111-2014-08-12 15/16...

This manual is also suitable for:

Vex250

Table of Contents