    Seplos Xtreme battery pack specification www.seplos.com Safety Precautions ............................. 1 Off- grid solar inverter system ........................... 3 Features ................................3 Installation ................................5 Battery connection ............................. 6 Product operation ............................17 LCD display information ...........................28 Error code ................................30 warning code ..............................31 Battery equalization charge ..........................
  • Page 3: Safety Precautions

    Seplos Xtreme battery pack specification www.seplos.com Safety Precautions Warning: This section contains important safety and operating instructions. Please read it carefully and retain this manual for future reference. Please specify which battery you are using, lithium battery or lead- acid battery, if you set the wrong battery mode, the system will not work properly.
  • Page 4: Product Introduction

    Seplos Xtreme battery pack specification www.seplos.com Product introduction ( To understand the detailed parameters of POLO- S, please refer to the instruction manual of POLO- S) The battery system is suitable for home energy storage and small and medium- sized commercial storage. It uses 3 . 2 V 5 0 Ah lithium cells to form 2 P16 S battery modules and Smart BMS to form 51.2 V100 Ah lithium battery system.
  • Page 5: Product Overview

    Seplos Xtreme battery pack specification www.seplos.com Product overview...
  • Page 6 Seplos Xtreme battery pack specification www.seplos.com Parameters 3*POLO-S + 4*POLO-S + 5*POLO-S + 6*POLO-S + Item\ Stack Quantity IF-5000-S IF-5000-S IF-5000-S IF-5000-S Rated energy(kWh) 15.36kWh 20.48kWh 25.6kWh 30.72kWh Nominal Capacity( Ah) 300AH 400AH 500AH 600AH Nominal Voltage( V) 51.2V Cel l type...
  • Page 7: Installation

    Seplos Xtreme battery pack specification www.seplos.com Installation Unpacking and inspection Before installation, you need to check whether the items are in good condition. Unpack the inverter and make sure there are no damaged items in the package. Check that the following items are all included :...
  • Page 8: Battery Connection

    Seplos Xtreme battery pack specification www.seplos.com Battery connection Lithium battery connection Notice: In order to operate safely and comply with safety regulations, a DC over current protection disconnecting device must be installed between the battery and the inverter. The fuse or circuit breaker of a single machine is recommended to use a specification of 40 A for M3500H BP, and a specification of 50A for M5000H BP.
  • Page 9 Seplos Xtreme battery pack specification www.seplos.com Standard configuration is a 1. 5 m power cable and a PS-0 soft copper bar Connect one end of the RJ4 5 cable to the inverter BMS communication interface ( RS4 8 5 / CAN) .
  • Page 10 Seplos Xtreme battery pack specification www.seplos.com Notice: If you choose a lithium battery and communicate with the inverter, please make sure to use the RJ4 5 communication cable to connect the battery and the inverter, and select the battery type as "Li" on the inverter .
  • Page 11 Seplos Xtreme battery pack specification www.seplos.com Remarks: To switch the protocol, turn to the corresponding protocol interface, press the confirmation key twice, and the protocol switch is successful As shown in the figure above, click the Confirm button, and the window shown in the figure below will appear...
  • Page 12 Seplos Xtreme battery pack specification www.seplos.com As shown in the picture above, press the Down key six times, and the window shown in the picture below will appear As shown in the figure above, click the Confirm button, and the window shown in the figure below will appear.
  • Page 13 Seplos Xtreme battery pack specification www.seplos.com Flooded water battery Li Lithium battery ( only for communication with BMS) USE User- defined ( suitable for manual setting of lead- acid battery Battery Type performance) If it is set to "USE", the battery voltage value setting items 19, 20, and 21 are not...
  • Page 14 Seplos Xtreme battery pack specification www.seplos.com When the battery mode is set to " Li" , the setting items for setting the maximum charging current, item 2 and item 1 1 cannot be manually set. When selecting SBU mode or SOL mode in item 01 of...
  • Page 15 Seplos Xtreme battery pack specification www.seplos.com Follow the steps below to perform AC input/ output connections: Before making AC input/ output connections, make sure that the DC protector or isolating switch is disconnected. Strip off the 10 mm insulating sleeves of the 6 wires, and cut the L wire and N wire 3mm shorter .
  • Page 16 Seplos Xtreme battery pack specification www.seplos.com PV connection Before connecting the PV modules, please install a DC circuit breaker between the inverter and the PV modules. All wiring must be performed by professionals. Connecting PV modules with proper cables is important for safe and efficient system operation. In order to reduce the risk of system use, please use the following recommendations correct cable specification.
  • Page 17 Seplos Xtreme battery pack specification www.seplos.com Make sure the wiring is secure. Product Wiring Diagram Installation Finishing Once all the wires are connected, put the bottom cover back on and screw it in. Dry node There is a dry node (3 A/2 5 0 VAC) in the bottom port, which is used to send a signal to the external device when the battery voltage or capacity...
  • Page 18: Product Operation

    Seplos Xtreme battery pack specification www.seplos.com Dry contact port : Device status Condition NC & C NO & C Device is off The output is bypassed by the mains at load Battery voltage ( or SOC) < Low voltage alarm (or low pressure alarm SOC)
  • Page 19: Operation And Display

    Seplos Xtreme battery pack specification www.seplos.com Operation and display The operation and display panel shown in the figure below is located on the front panel of the inverter. It includes three indicator lights, four function keys and an LCD display for indicating operating status and input/ output power information.
  • Page 20 Seplos Xtreme battery pack specification www.seplos.com LCD display Icon Introduction Power description Icon AC input Display AC input power, AC input voltage, AC input frequency, AC input current AC bypass operation PV input Display PV power, PV voltage, PV current...
  • Page 21 Seplos Xtreme battery pack specification www.seplos.com Display load priority, SOL, UTI, SBU, SUB, see item 1 of the setting item for details Display warning or fault codes Display warning or fault codes Displayed in the setup parameters Display buzzer off...
  • Page 22 Seplos Xtreme battery pack specification www.seplos.com > 47.592V < 44.808V 44.808 ~ 46.8V load < 20% 46.8 ~ 48.792V > 48.792 LCD display parameter setting Press the ENTER key for 3 seconds to enter the setting item, and press the up and down keys to scroll through the options. Use ENTER to confirm the option, ESC key to exit the setting interface.
  • Page 23 Seplos Xtreme battery pack specification www.seplos.com SUB mode Photovoltaic power is given priority to the load. When the photovoltaic is insufficient, the photovoltaic and the mains supply power to the load together. The battery will only discharge when the photovoltaic power is insufficient and there is no mains power.
  • Page 24 Seplos Xtreme battery pack specification www.seplos.com AGM ( Default) Flooded water battery Li Lithium battery ( only for communication with BMS) Battery Type User- defined Suitable for manual setting of lead- acid battery parameters US2 User- defined 2 Suitable for lithium batteries without communication If it is set to "USE", it is recommended that items 19 and 20 can be set to the same value.
  • Page 25 Seplos Xtreme battery pack specification www.seplos.com connected in series Default 3 0 A, 0 A~8 0 A configuration Maximum Mains Charging ( The setting value of this item should not exceed the value of item 2. If item 5 is set to "Li", this setting...
  • Page 26 Seplos Xtreme battery pack specification www.seplos.com Alarm off Alarm control Alarm on Default backlight off backlight on Default Backlight control Alarm off Alarm on Default Buzzer alarm when input is disconnected Overload to bypass on Overload t obypass o ff...
  • Page 27 Seplos Xtreme battery pack specification www.seplos.com the battery; If there is PV, mains power and battery at this time, the system will switch to bypass load and charge the battery at the same time Single- phase parallel mode: Stand- alone mode:...
  • Page 28 Seplos Xtreme battery pack specification www.seplos.com water batteries Balanced charging voltage Default 58.4 V, 48.0 V~58.4V configuration Balanced charging time Default 60 min, 5min~9 0 0 min configuration Default 12 0 min, 5min~9 0 0 min configuration Balanced charging timeout...
  • Page 29: Lcd Display Information

    Seplos Xtreme battery pack specification www.seplos.com LCD display information By pressing the " UP" or " DOWN" key, the LCD display information will be switched in turn. Displayable information includes voltage, frequency, current, power, and firmware version. AC input voltage ①...
  • Page 30: Operating Mode Description

    Seplos Xtreme battery pack specification www.seplos.com Time (2018- 12- 15, 15:20:10) Operating Mode Description Operating mode LCD display Instruction standby mode Mains and solar charging at the Mains charging same time standby mode The inverter has : The machine has no...
  • Page 31: Error Code

    Seplos Xtreme battery pack specification www.seplos.com No battery mode Solar and battery on- load Solar and battery on- load Inverter Mode ( Battery Mode) battery only Error code Icon is always on Fan failure Overheating battery voltage too high battery voltage too low...
  • Page 32: Warning Code

    Seplos Xtreme battery pack specification www.seplos.com Battery disconnected current sensor failure output voltage is too low Negative work failure PV voltage is too high Internal communication failure CAN communication failed Host lost warning code Three beeps per second Fan failure...
  • Page 33: Battery Equalization Charge

    Seplos Xtreme battery pack specification www.seplos.com One beep per second Lithium battery cell under voltage One beep per second Do not work without battery in parallel One beep per second Lithium battery overall under voltage One beep per second Discharge over current...
  • Page 34: Parameters Table

    Seplos Xtreme battery pack specification www.seplos.com When to start equalizing charging In the floating charging stage, when the start time is reached after the cycle equalizing charging is set, or when the equalizing charging starts immediately, the charging will enter the equalizing charging stage.
  • Page 35 Seplos Xtreme battery pack specification www.seplos.com Table 1 Mains mode parameter information Model Input voltage waveform Pure sine wave / consistent with the input voltage waveform of the mains or generator 230Vac Rated input voltage 170Vac±7V ( UPS) ; 90Vac± 7V (Appliances) Low voltage cut- off voltage 180Vac±7V ( UPS);...
  • Page 36 Seplos Xtreme battery pack specification www.seplos.com Table 2 Inversion mode parameter information Model M5000H BP 5KVA/5 KW Rated output power pure sine wave Output voltage waveform 230Vac±5% The output voltage 50Hz Output frequency 21.7A Rated output current 80A/ 300 μs...
  • Page 37 Seplos Xtreme battery pack specification www.seplos.com 60.8Vdc DC high voltage cut- off voltage <60W Load loss Table 3 Charging mode parameter information Model M5000H BP Mains Charging Mode charging logic 3 stage charging 80Amp(@VI/P=230Vac) Maximum AC charging current Water battery 58.4Vdc...
  • Page 38: Troubleshooting

    Seplos Xtreme battery pack specification www.seplos.com Table 4 Basic parameters Model M5000H BP Certification standards operating temperature 0 ℃ to 5 5 ℃ Storage temperature - 1 5 ℃ ~ 6 0 ℃ 5 % to 95% Relative humidity (non-condensing)
  • Page 39 Seplos Xtreme battery pack specification www.seplos.com correctly The first load priority is set to "SOL" LED green light flashing Modify loading priority or "SBU" After power-on, LCD display and lights battery disconnected Check if the battery cable is well connected...
  • Page 40 BUS voltage is too high 1 .If the lithium battery is connected and there is no Error code 08 communication with the battery, check whether the values of items 19 and 20 are set too high 2 . Restart the inverter, if the failure still occurs, send it...
  • Page 41 Seplos Xtreme battery pack specification www.seplos.com the same- phase devices is connected properly Check whether the L lines of all parallel machines are connected together If the failure still occurs, send it to the maintenance center Error code 80 CAN communication failure...