Controlled Access FP500-C Service & Installation Manual

Waist high turnstile

Advertisement

Quick Links

FP500-C Waist High Turnstile
Service & Installation Manual
Note: Successful turnstile installation depends on reading this manual.
Please keep this service manual after installation. If an installation is done by a construction company
or outside installer, please pass this book along to the end user. This book is required for maintenance,
troubleshooting & repairs.
Service Manual: 0740 E Gen. 3

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FP500-C and is the answer not in the manual?

Questions and answers

Summary of Contents for Controlled Access FP500-C

  • Page 1 FP500-C Waist High Turnstile Service & Installation Manual Note: Successful turnstile installation depends on reading this manual. Please keep this service manual after installation. If an installation is done by a construction company or outside installer, please pass this book along to the end user. This book is required for maintenance, troubleshooting &...
  • Page 2: Important Electrical Information

    Canadian Electrical Code, CSA C22.1, Part I, Safety Standard for Electrical Installations The 6500 Series Control Head is suitable for indoor & outdoor use, within in an appropriate turnstile or gate model. 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 3: Table Of Contents

    Limit Switch & Limit Switch Cam Information Maintenance & Cleaning Troubleshooting Proper Turnstile Usage Warranty Coin Acceptor Introduction Coin Acceptor Literature VAL 343 Interface Board / Wiring Information Coin Acceptor Programming 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 4: Model Datasheet

    Security Pros and Engineers FP500-T (ticket box) For more than 30 years, Controlled Access has been the globally trusted name in pedestrian control equipment. Made in Ohio and shipped worldwide, we are the first choice of leading architects, facility managers, security consultants, and engineers.
  • Page 5 • Bill acceptor • Minimal exposed hardware CAN/ULC S319 & CSA C22.2#247 4008027 • Ticket drop box Controlled Access, Inc. is certified • Additional options available upon request by Advantage International Registrar Dimensions: to be an ISO 9001:2015 company • Height: 38.062" (966.8mm) Warranty: •...
  • Page 6: Preinstallation Tips

    This is accomplished by removing the two 10/32 phillips screws that connect the front panel to the cabinet located at the upper inside of the cabinet. 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 7: Installation Instructions

    (reference hydraulic shock information later in this manual). Reinstall the front panel and lid on the cabinet then provide this manual to the end user or leave within the cabinet for future reference. 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 8: Concrete Anchor Information

    Anchor spacing and edge distance (anchor installation locations) are the responsibility of the engineer of record. Installing product in oversized holes is not recommended. Product will not set properly or achieve full designed load in oversized holes. 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 9: Mechanical Overview

    100-240 VAC (single phase) receptacle. The power supply will automatically set itself to function on your local voltage and convert it to 24VDC. 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 10: Internal Parts Breakdown

    FP500-C Waist High Turnstile Service & Installation Manual 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 11: Parts List

    Phone: (800)942-0829 Complete control heads are Fax: (800)942-0828 available upon request. Web: www.controlledaccess.com Contact us for pricing details. Email: sales@controlledaccess.com Control Head Castings Locking Bar Assemblies – I2 IB IC ID IE 0373 - Bottom Casting 0382 - Fail Open Assembly XD10 0740 - Logic Controller (XD10) –...
  • Page 12: Control Head Con Gurations

    Note that the key override option makes conversion between fail lock and fail open very di cult to accomplish and also may not be available for some turnstile or gate models. 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 13: Locking Bar Information

    Fail Open Fail Lock Fail Lock Fail Open Pivot Point Pivot Point Pivot Point Pivot Point Direction 1 Solenoid Direction 2 Solenoid 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 14 Make sure the solenoid spring is between the alignment tabs on the linkage or the assembly may bind when pivoting. Correct Alignment Incorrect Alignment Locking Bar Linkage Spring Alignment Tabs Solenoid Spring 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 15: Hydraulic Shock & Indexing

    Failure to turn the shock back out after threading it in all of the way will likely cause the part to wear out very quickly. 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 16: Electrical Introduction

    Dir 2 Fail Open Dir 1 Green Light Dir 1 Red Light Dir 2 Green Light Dir 2 Red Light XD10 Logic Controller Control Board 0740 0789 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 17: Wiring Diagram

    6500 Series Control Head w/ XD10 Controller Standard Wiring Diagram Direction 1 Direction 2 Direction 1 Direction 2 Access Control Relay Access Control Relay Override Relay Override Relay N.O. N.O. N.O. N.O. Input Voltage: 100-240 VAC 1 Phase 1.1 - .6A Max 50/60 Hz 24V 2.5A Grounding Tab...
  • Page 18: Wiring Legend

    As a side note, indicator lights purchased from Controlled Access, Inc. can also be wired to glow yellow. If desired, this can be used instead of red with the unused white wire on the light’s cable to indicate to pedestrians they require credentials to enter. This is especially handy for multi-lane installations in which some directions are “no passage”...
  • Page 19: Logic Controller Settings

    Options and con gurations may alter the quantity or layout of the limit switches. Some examples of this would be electronically controlled one direction turnstiles, turnstiles with counters and turnstiles equipped with home position switches. 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 20: Testing Procedure

    PLC software version. number (if known), enter it as a value then press B to save. 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 21: Limit Switch & Limit Switch Cam Information

    If there are other issues with operation, check out the troubleshooting guide for additional diagnostic procedures or call Controlled Access, Inc. for assistance. 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 22: Maintenance & Cleaning

    Please include contact information so we can call to discuss any issues your control head may have. Please note that any repairs that cost under $500.00 will require a credit card payment before being returned. 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 23: Troubleshooting

    Disconnect access control from logic controller. Preform testing Access control device procedures on page 20. If the malfunction. turnstile works properly, contact manufacturer of access control device. 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 24 Shim the unit from the oor if necessary. Turnstile seems to be binding Rotor is not plumb / turnstile mechanically. body is not level. 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 25 Refer to pages 19. Please contact us for any other Other problems. issues. 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 26: Proper Turnstile Usage

    - Piggybacking : More than one user trying to squeeze through the turnstile on one rotation should be avoided. Large bags and carts should be brought through an alternate means of entrance. 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 27: Warranty

    Warranty Information Seller warrants the goods against defective workmanship and materials provided that Buyer notify Seller within one (1) year after receipt by Buyer of the goods of any claim under this Warranty. The liability of Seller shall be limited to replacing or repairing defective goods returned by Buyer and delivered to the factory of the Seller, transportation charges prepaid.
  • Page 28: Coin Acceptor Introduction

    FP500-C Waist High Turnstile Service & Installation Manual Coin Acceptor Introduction The FP500-C is tted with a coin acceptor. This acceptor (Microcoin SP) has a wide range of functionality. It can be programmed to accept any currency or token and can also be set to activate the turnstile any vend price.
  • Page 29: Coin Acceptor Literature

    FP500-C Waist High Turnstile Service & Installation Manual SP 115 www.microcoin.com 115mm face plate. Ultra-compact. Stylish and appealing design. Unique “Parallel Path” debris release. Conforms to industry standards. 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 30 ISO9001 certified manufacturing plants and an international network of offices and market representation in Australia, Hong Kong, the United Kingdom, the USA. Printed 00.00 www.microcoin.com 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 31: Val 343 Interface Board / Wiring Information

    – + – + – I2 IB IC ID IE XD10 – PS24-60W V Out 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 32: Coin Acceptor Programming

    To reset the credit to zero, simply open the SP housing by pressing the reject lever and then release, whilst in this mode. MicrosystemControls August 2007 SP-PB-OBP Instructions.doc Page 1 of 3 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 33 Finish Briefly press button x 1 to complete. “M” LED will go steady GREEN MicrosystemControls August 2007 SP-PB-OBP Instructions.doc Page 2 of 3 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...
  • Page 34 SP will attempt to continue the OBP function from where the error occurred. If the problem persists, then escape the sequence. (see Escape above) MicrosystemControls August 2007 SP-PB-OBP Instructions.doc Page 3 of 3 0740E Gen 3. Controlled Access, Inc. (800) 942-0829 | (330) 273-6185 | Sales@controlledaccess.com...