Redlion DA 8DI/8RO Installation Manual

8 digital input / 8 relay output module

Advertisement

Quick Links

DA 8 Digital Input / 8 Relay Output Module
Installation Guide
z Adds I/O capability to the DA70
z Offers complete isolation; inputs, power and Controller
z Inputs independently software selectable for sink or source
signals, high or low active states, and high or low frequency
signals
z Ideal for data acquisition applications
z Configured using Crimson
U L
FOR USE IN HAZARDOUS LOCATIONS:
C C
US
US
R
Class I, Division 2, Groups A, B, C, and D
LISTED
T4
IND.CONT. EQ.
E317425
MODULE PACKAGE CHECKLIST
This product package should contain the items listed below. If
any items are missing or damaged, contact Red Lion immediately.
- DIN Rail Mount DA 8DI/8RO Module
- Installation Guide
GENERAL DESCRIPTION
The DA 8DI/8RO module is designed for use with the DA70
controllers, that can support up to 10 I/O modules simultaneously.
This module features 8 Digital Inputs and 8 Relay Outputs that
can be used to monitor contact or sensor inputs and actuate
relays, solenoids, PLC inputs, etc.
The inputs accept standard DC inputs or contact closures, and
are configured for Sink/Source signals via software switches.
Additionally, each input has a switch selectable input filter that
can be used to prevent contact bounce. Each input may also be
software configured as a high-active or low-active input.
The module is available with relay outputs that are capable of
switching up to one amp each. For applications requiring large
loads to be controlled, several DIN rail mount relays are available.
The modules connect and communicate via proprietary
backplane to the DA host device. The DA host device, equipped
with serial ports as well as an Ethernet port(s), allows the system
to share data with PCs, PLCs, and SCADA systems.
Internal power management circuits allow the module to be
replaced while power is applied, which reduces downtime in the
event of a module failure. All configuration information is stored
locally within the module, as well as in the Host, so replacement
modules do not need to be configured.
DIMENSIONS In Inches [mm]
0.49
4.53 [114.97]
[12.51]
32
31
30
29
28
27
26
25
24
23
22
21
20
6.00
19
18
17
16
[152.40]
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
0.45 [11.50]
®
software (version 3.1 or later)
1.91
[48.51]
1.35
[34.32]
6.22
[157.91]
CONFIGURATION
The DA 8DI/8RO modules are configured with Windows
®
compatible Crimson
software. The software is an easy to use,
graphical interface which provides a means of configuration and
commissioning of new systems, as well as routine module
re-calibration.
SAFETY SUMMARY
All safety related regulations, local codes as well as instructions
that appear in this document or on equipment must be observed
to ensure personal safety and to prevent damage to either the
device or equipment connected to it.
Do not use these products to replace proper safety interlocking.
No software-based device (or any other solid-state device) should
ever be designed to be responsible for the maintenance of
personnel safety or consequential equipment not equipped with
safeguards. Red Lion disclaims any responsibility for damages,
either direct or consequential, that result from the use of this
equipment in a manner not consistent with these specifications.
CAUTION: Risk of Danger
Read complete instructions prior to installation and
operation of the unit.
ATTENTION : Risque de danger
Lire les instructions complètes avant l'installation et
l'utilisation de l'appareil.
WARNING - Explosion Hazard - Substitution of
components may impair suitability for Class I, Division 2.
AVERTISSEMENT - Danger d'explosion - Le
remplacement de composants peut nuire à l'aptitude à la
classe I, division 2.
This equipment is suitable for use in Class I, Division 2,
Groups A, B, C, D, or non-hazardous locations only.
Cet équipement est adapté à une utilisation dans des
endroits de classe I, Division 2, Groupes A, B, C, D, ou
dans des endroits non dangereux seulement.
WARNING - Explosion Hazard. Not hot swappable. Do
not remove or replace while circuit is live unless the area
is free of ignitible concentrations.
AVERTISSEMENT - Risque d'explosion. Non échangeable
à chaud. Ne pas retirer ou remplacer sous tension sauf si
la zone est exempte de concentrations inflammables.
1
Installation 8DI/RO - D
Drawing No. LP1119
Revised 06/2024
®

Advertisement

loading
Need help?

Need help?

Do you have a question about the DA 8DI/8RO and is the answer not in the manual?

Questions and answers

Summary of Contents for Redlion DA 8DI/8RO

  • Page 1 GENERAL DESCRIPTION The DA 8DI/8RO module is designed for use with the DA70 SAFETY SUMMARY controllers, that can support up to 10 I/O modules simultaneously. All safety related regulations, local codes as well as instructions...
  • Page 2 13. WEIGHT: 14.0 oz (397 g) Host Controller EMC INSTALLATION GUIDELINES Attaching the Module/Cradle to the DIN Rail Visit https:/ /www.redlion.net/emi for more information on EMI rail should guidelines, Safety and CE issues as they relate to Red Lion mounted horizontally so that the products.
  • Page 3 Installing Module into Cradle I/O Wiring Push module into cradle until you hear an audible click The DA 8DI/8RO offers 8 discrete inputs and 8 Form A relay indicating it is properly latched. outputs. The discrete inputs and outputs operate on the same voltage that powers the unit.
  • Page 4 Red under normal use for the period of time provided in “Statement Lion’s technical support. of Warranty Periods” (available at www.redlion.net) current at the time of shipment of the Products (the “Warranty Period”). Support: support.redlion.net...