Tone Selection
–
To select the required first stage tone set the tone Set DIP switch 1 (6 way DIP see Fig 3) to the required tone setting shown in the table below. The table also shows
the second stage tone can be set independently with the Stage 2 DIP switch to select the required tone. The 3
required, they are set/linked via the first stage tone selection.
Stage 1
Set DIP
Tone Description
Switch 1
Tone No
1
1000Hz PFEER Toxic Gas
1200/500Hz @ 1Hz DIN /
2
PFEER P.T.A.P.
1000Hz @ 0.5Hz(1s on, 1s off)
3
PFEER Gen. Alarm
1.4KHz-1.6KHz 1s, 1.6KHz-
4
1.4KHz 0.5s NF C 48-265
544Hz(100mS)/440Hz
5
(400mS) NF S 32-001
1500/500Hz - (0.5s on , 0.5s
6
off) x3 + 1s gap AS4428
500-1500Hz Sweeping 2 sec
7
on 1 sec off AS4428
500/1200Hz @ 0.26Hz(3.3s
8
on, 0.5s off) Netherlands -
NEN 2575
1000Hz (1s on, 1s off)x7 + (7s
9
on, 1s off) IMO Code 1a
1000Hz (1s on, 1s off)x7 + (7s
10
on, 1s off) IMO Code 1a
420Hz(0.5s on, 0.5s off)x3 +
11
1s gap ISO 8201 Temporal
Pattern
1000Hz(0.5s on, 0.5s off)x3 +
12
1s gap ISO 8201 Temporal
Pattern
422/775Hz - (0.85 on, 0.5 off)
13
x3 + 1s gap NFPA - Temporal
Coded
1000/2000Hz @ 1Hz
14
Singapore
15
300Hz Continuous
16
440Hz Continuous
17
470Hz Continuous
500Hz Continuous IMO code 2
18
(Low)
19
554Hz Continuous
20
660Hz Continuous
21
800Hz IMO code 2 (High)
22
1200Hz Continuous
23
2000Hz Continuous
24
2400Hz Continuous
440 @0.83Hz (50
25
cycles/minute) Intermittent
26
470 @0.9Hz - 1.1s Intermittent
470Hz @5Hz - (5
27
cycles/second) Intermittent
544Hz @ 1.14Hz - 0.875s
28
Intermittent
29
655Hz @ 0.875Hz Intermittent
660Hz @0.28Hz - 1.8sec on,
30
1.8sec off Intermittent
660Hz @3.34Hz - 150mS on,
31
150mS off
Intermittent
www.acornfiresecurity.com
Tone Visual
1000Hz
1200Hz
500Hz
1s
1000Hz
1s
1s
1600Hz
0.5s
1400Hz
1s
544Hz
0.1s
0.4s
440Hz
1500Hz
0.5s 0.5s
0.5s 0.5s 0.5s
500Hz
1500Hz
500Hz
2s
1200Hz
500Hz
3.3s
1000Hz 1s
1s
1s
1s
1s
1s
1s
1s
1s
1s
1s
420Hz 0.5s
0.5s
0.5s
0.5s
0.5s
1000Hz 0.5s
0.5s
0.5s
0.5s
775Hz
422Hz
0.85s
0.5s
0.85s
0.5s
0.5s
2000Hz
0.5s
1000Hz
300Hz
440Hz
470Hz
500Hz
554Hz
660Hz
800Hz
1200Hz
2000Hz
2400Hz
440Hz
0.6s
0.6s
470Hz 0.55s
0.55s
470Hz
0.1s
0.1s
470Hz 0.43s
0.44s
655Hz 0.57s
0.57s
660Hz
1.8s
1.8s
660Hz 0.15s
0.15s
www.acornfiresecurity.com
rd
th
and 4
stage tones are available if more than two tone output stages are
Stage 1 & 2 DIP
Switch Settings
1 2 3 4 5 6
0 0 0 0 0 0
1 0 0 0 0 0
0 1 0 0 0 0
1 1 0 0 0 0
0 0 1 0 0 0
1 0 1 0 0 0
1.5s
0 1 1 0 0 0
1s
1 1 1 0 0 0
0.5s
0 0 0 1 0 0
7s
1s
1s
1s
7s
1 0 0 1 0 0
0 1 0 1 0 0
1.5s
0.5s
1 1 0 1 0 0
1.5s
0 0 1 1 0 0
0.85s
1.5s
1 0 1 1 0 0
0 1 1 1 0 0
1 1 1 1 0 0
0 0 0 0 1 0
1 0 0 0 1 0
0 1 0 0 1 0
1 1 0 0 1 0
0 0 1 0 1 0
1 0 1 0 1 0
0 1 1 0 1 0
1 1 1 0 1 0
0 0 0 1 1 0
1 0 0 1 1 0
0 1 0 1 1 0
1 1 0 1 1 0
0 0 1 1 1 0
1 0 1 1 1 0
0 1 1 1 1 0
Stage 4
Stage 2
Stage 3
Set DIP
Set DIP
Set DIP
Switch 1
Switch 2
Switch 1
Tone
Tone (S2)
Tone (S3)
(S2 + S3)
1
2
44
2
3
44
3
2
44
4
24
1
5
19
1
6
44
1
7
44
1
8
24
35
9
34
1
10
34
1
11
1
8
12
1
8
13
1
8
14
3
35
15
24
35
16
24
35
17
24
35
18
24
35
19
24
35
20
24
35
21
24
35
22
24
35
23
3
35
24
20
35
25
44
8
26
44
8
27
44
8
28
24
8
29
44
8
30
24
8
31
24
8
Need help?
Do you have a question about the GNEXS1DC024 and is the answer not in the manual?
Questions and answers