5.Purging Method:

Push the air out of the indoor unit
and piping as followes:
(1) Remove the valve cap on 2-way
valve in outdoor unit.
(2) Loosen by 1/2 turn the flare nut of
gas pipe, which is conneted to
3-way valve.
(3) Loosen 2-way valve by 90
hexagon wrench, and after approx.
10 sec tighten it up. Gas comes out
through flare nut on wide pipe. If no
gas is discharged, tighten flare nut
with specified torque.
(4) Open 2-way and 3-way valves
using specified torque.
(5) Tighten the caps on the valves
with specified torque.
Tighten torque N.m
Valve rod
Valve cap
When connecting pipe exceeds 5 meters, 20g or 60g(only for 22k) refrigerant
shall be added per exceeding meter . Charge according to the following list.
Piping length
Additional amount
Piping length
Additional amount
Note: When extending piping, air inside piping shall be removed by using external
refrigerant gas, charge according to the following list.
Brand new outdoor unit is charged 50g or 80g(22k) more refrigerant than regulated
weight. Only for first installation, this extra 50g or 80g(22k) can be used to purge air
in pipes.
During this procedure, 50g or 80g(22k) refrigerant will be discharged in piping.
(This must be strictly controlled within 90
Outdoor unit
o
using
7-9
20-25
for 5k 7k 9k 12k 18k
5m
7m
40g
No need
for 22k 24k
5m
7m
No need
120g
HSU-05LEA03
HSU-09LEA03
2-way valve
6.35mm(1/4")
HSU-12LEA03
HSU-18LEA03
2-way valve
9.52mm(3/8")
10m
100g
10m
300g
o
and 10 sec.)
7
2-way valve
6.35mm(1/4")
3-way valve
9.52mm(3/8")
3-way valve
12.7mm(1/2")
3-way valve
15.88mm(5/8")
HSU-22LEA03
HSU-24LEA03