ANALOG THERMOSTAT Model ΑN1 V3
ATTENTION
Read carefully these instructions before installing and using this device and keep them for future reference. Attention to installation and electrical wiring. Use this
device only as described in this document and never use itself as a security device. Disconnect the power supply before performing any type of maintenance
operation. Do not expose the device to liquid leakage, high temperatures over +55
local standards for the collection of electrical and electronic equipment
DESCRIPTION
The analog thermostat AN1 Version 3 has the following technical characteristics:
1. One input, either for NTC temperature sensor of scale -50 ÷ +110 °C or PTC scale -50. ÷ +150 °C, and an input for signal 4-20mA, where the adjustment is made
through parameters. It analyzes 4-20 mA from 0 - 1000 units. This scale is defined by the parameter r nA, where if for example: r nA = 30, the scale of 4-20 mA will be
0 - 30.0 units (so 0 units = 4mA and 30.0 units = 20mA).
2. Output for 0-10 Volt signal. The signal settings are made through the parameters of the table below.
3.
One relay controlled based on SET POINT and the corresponding differentials for cooling and heating, parameters diC and diH.
4.
Power supply +12 Volt for transmitter
Through the AS2 parameter we set the analog output to work with the set point of cooling SCo (AS2 = 1) or heating SH1 (AS2 = 2) or both set points (AS2 = 3). In the 3rd
case the analog signal is controlled in both the cooling area and the heating area, while the relay works only in the cooling area. AS2 = 4 Adjusts the analog voltage driven
by the inverter / FAN so that the signal read by the differential pressure switch is equal to SET POINT SCo. Only in option AS2 = 4 the input to terminal 7-11 works. When
the contact is open, the display shows OFF
PROGRAMMING THE PARAMETERS
ATTENTION: to access the entire configuration menu the 3rd Cod parameter must be set to 22
1.
By pressing
we enter the parameters menu.
2.
Select the parameter you want with
3.
With
or
change its value and press
4.
By pressing
we exit the parameter's menu.
RESETTING TO FACTORY SETTINGS
We can reset the factory settings to the following table by entering Cod = 31 in the parameter and pressing twice
menu.
PARAMETER TABLE
#
description
1
SCo
SET POINT in cooling mode
2
SHt
SET POINT in heating mode
code to enter parameter's menu Cod = 22
3
Cod
Cooling function: temperature range to which the proportional voltage at the output corresponds (see
4
ArC
sketch below)
Heating function: temperature range to which the proportional voltage at the output corresponds (see
5
ArH
sketch below)
Lower analog output voltage
The analog output has a scale between the LLo and HLo limits and in a temperature range defined by the
respective set point and the corresponding parameter ArH or ArC.
6
LLo
For example, if LLo = 3VDC, HLo = 10VDC, set point in heating SHt = 45 °C and ArH = 3 °C, then the
voltage will vary from 3 to 10 VDC and from 42 to 45 °C
Higher voltage at the analog output
7
HLo
Adjusting the analog signal at the output according to the function:
8
IAO
0 = compressor mode / 1 = fan operation with signal reversal (see sketch below)
Analog input setting: 1 = cooling mode / 2 = heating mode
3 = cooling and heating function at the same time.
9
AS2
4 = adjustment of the analog voltage value to control the speed (supply) of the fan.
Input setting to sensor mode(NTC/PTC) or signal 4-20 mA : 1 = sensor / 2 = 4-20 mA
10
AIn
Adjust maximum limit of the mA scale, for example instead of 0 - 100 to show 0 - 30
11
r nA
Differential of relay in cooling mode
12
diC
Differential of relay in heating mode
13
diH
14
SEn
NTC/PTC sensor selection for Sen = 0 PTC and Sen = 1 NTC
SE1
Sensor offset
15
Relay time delay from OFF to ON
16
rtd
17
tS
Delay in displaying the actual temperature on the screen
18
C_F
Switching °C/°F (0=°C, 1=°F) ATTENTION: switching between °C/°F do not change the SPo
Time response of the device on network
19
trE
Address of the device on network
20
Add
Increasing the value, reduces the change speed of the signal 0-10 Volt.
21
dEr
Increasing the value, reduces the change speed of the signal 0-10 Volt.
22
dr2
ALARM TABLE
1
LF1
Room sensor malfunction / malfunction in input for signal 4-20mA
o
C, high humidity over 80%. The device must be disposed of in accordance with
or
and press
to display its value.
to enter the new
value.
to enter the value and exit the parameter
min
max
default
-50.0
150
10.0
-50.0
150
20.0
0
255
0
1.0
25.0
3.0
1.0
25.0
3.0
0.0
5.0
3.0
6.0
10.0
10.0
0 =
0
1
compressor
1 =
1
4
cooling
1
2
1 = PTC
10
100
100
0.5
25.0
3.0
0.5
25.0
3.0
0
1
0
-10.0
15.5
0.0
0
240
0
0
20
0
0
1
0 =°C
20
100
30
0
255
1
2
12
2
1
100
2
Firmware V3.0
UOM
°C/°F
°C/°F
-
°C/°F
°C/°F
Volt DC
Volt DC
Units
Units
Units
Units
°C/°F
°C/°F
Units
°C/°F
seconds
seconds
°C/°F
Units
Units
Units
Units

Advertisement

loading
Need help?

Need help?

Do you have a question about the AN1 V3 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for KIOUR AN1 V3

  • Page 1 ANALOG THERMOSTAT Model ΑN1 V3 ATTENTION Firmware V3.0 Read carefully these instructions before installing and using this device and keep them for future reference. Attention to installation and electrical wiring. Use this device only as described in this document and never use itself as a security device. Disconnect the power supply before performing any type of maintenance operation.
  • Page 2 The device is under two year’s guarantee. The guarantee is valid only if the manual instructions have been applied. The control and service of the device must be done by an authorized technician. The guarantee covers only the replacement or the service of the device. KIOUR preserves the right to adjust its products without further notice.