1. DESCRIPTION
Viking Standard/Quick Response Extended Coverage Dry Horizontal Sidewall
Sprinklers are thermosensitive spray sprinklers suitable for use in areas subject to
freezing. The sprinklers are designed for dry systems and preaction systems where
it is necessary to prevent water or condensation from entering the drop nipple be-
fore sprinkler operation. They may also be installed in spaces subject to freezing
and supplied from a wet system in an adjacent heated area.
The Polyester and Electroless Nickel PTFE (ENT) coatings have been investigated
for installation in corrosive atmospheres and are cULus listed as corrosion resistant
as indicated in the Approval Chart.
NOTE: When installed in some corrosive environments, the Polyester finish
may change color. This natural discoloration over time is not in itself an indi-
cation of corrosion and should not be treated as such. All sprinklers installed
in corrosive environments should be replaced or tested as described in
NFPA 25 on a more frequent basis.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
Refer to the Approval Chart and Design Criteria for cULus Listing requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 1998.
Minimum Operating Pressure: Refer to the Approval Chart
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1" NPT or 25 mm BSPT
Nominal K-Factor: 5.6 U.S. (80.6 metric*) for all listed and approved lengths.
* Metric K-factor measurement shown is when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Covered by the following U.S. Patent numbers: 8,636,075 and 8,376,060 and 10,220,231
Material Standards:
Frame Casting: Brass UNS-C84400
Deflector: Copper UNS-C19500
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Compression Screw: Brass UNS-C36000
Pip Cap and Pip Cap Adapter: Brass UNS-C36000
Orifice: Copper UNS-C22000
Tube: ERW Hydraulic Steel Tube
Support (Internal): Stainless Steel UNS-S30400
Barrel: Steel Pipe UNS-G10260, Electrodeposited Epoxy Base finish
Barrel End and Threads: QM Brass
Escutcheon Materials:
Recessed Dry Escutcheons: Cold Rolled Steel UNS-G10080
ENT Coated Adjustable and Recessed Escutcheons: Stainless Steel UNS-S30400
Ordering Information: (Also refer to the current Viking price list.)
Sprinkler: Base Part No. 10542U
Order Standard/Quick Response Extended Coverage Dry Horizontal Sidewall Sprinklers by first adding the appropriate suffix for
the sprinkler finish, the appropriate suffix for the temperature rating, and then the suffix for the length ("A" dimension) to sprin-
kler base part number. Order in a specific length noted as the "A" dimension (see Figure 3). The "A" dimension is the distance
from the face of the fitting (tee) to the desired finished surface of the wall in which it is to be installed.
These sprinklers are listed and approved in lengths from 3-1/4" to 47-1/2" (82.5 mm to 1,207 mm) for the adjustable recessed style.
Finish Suffix: Chrome = F, White Polyester = M-/W, and ENT = JN
Form No. F_051598
20.03.18
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Rev 20.1
STANDARD/QUICK
RESPONSE EXTENDED
COVERAGE DRY HORIZON-
TAL SIDEWALL SPRINKLER
For Light Hazard Occupancies Only
Replaces Form No. F_051598 Rev 19.1
(Revised factory test
Page 1 of 6
specifications.)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VK188 EC REC HS CH 155 6 and is the answer not in the manual?

Questions and answers

Summary of Contents for Viking VK188 EC REC HS CH 155 6

  • Page 1 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com 1. DESCRIPTION Viking Standard/Quick Response Extended Coverage Dry Horizontal Sidewall Sprinklers are thermosensitive spray sprinklers suitable for use in areas subject to freezing.
  • Page 2: Technical Data

    The Viking Corporation. Figure 1: Sprinkler with Protective Shield 8. GUARANTEE For details of warranty, refer to Viking’s current list price schedule or contact Viking directly. TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal...
  • Page 3 Footnotes Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. For areas of coverage smaller than shown, use the “Minimum Water Supply Requirement” for the next larger “Area of Coverage” listed for the sprinkler used.
  • Page 4 Figure 4: Dry Horizontal Sidewall Sprinkler Cover Part Number 15610 (Optional for temporary use with Viking Dry HSW Sprinklers until finish work is completed around the sprinkler.) Form No. F_051598 20.03.18...
  • Page 5 F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
  • Page 6 TAL SIDEWALL SPRINKLER The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Figure 6: Dry Sprinkler Seal Form No.
  • Page 7 Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance instructions. For additional product and system information Viking data pages and installation instructions are available on the Viking Web site at www.vikinggroupinc.com.
  • Page 8 * Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com.
  • Page 9 • while ceiling finish work is being completed. Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. NOTE: The protective cap is • temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed.
  • Page 10 Take care not to crack the wax coating on the units. • For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after •...
  • Page 11: Listings And Approvals

    1. DESCRIPTION Viking fire sprinklers consist of a threaded frame with a specific waterway or orifice size and a deflector for distributing water in a specified pattern. A closed or sealed sprinkler refers to a complete assembly, including the thermosensitive operating element. An open sprinkler does not use an operating element and is open at all times.
  • Page 12 TECHNICAL DATA SPRINKLER OVERVIEW The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com VERTICAL SIDEWALL (VSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The deflector provides a water spray pattern outward in a quarter-spherical pattern and can be installed in the upright or pendent position with the flow arrow in the direction of discharge.
  • Page 13 Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
  • Page 14: Installation

    STANDARD RESPONSE, QUICK RESPONSE, EXTENDED COVERAGE, AND DRY SPRINKLERS Viking thermosensitive spray sprinklers consist of a small frame and either a glass bulb or a fusible operating element. Available styles include pendent, flush pendent, concealed pendent, upright, horizontal sidewall, vertical sidewall, or conventional, depending on the particular sprinkler model selected.
  • Page 15 C. Installation Instructions - Dry Sprinklers WARNING: Viking dry sprinklers are to be installed in the 1” outlet (for dry and preaction systems), or run of malleable, ductile iron, or Nibco CPVC* threaded tee fittings (for wet systems) that meet the dimensional requirements of ANSI B16.3 (Class 150), or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16.4 (Class 125), even at branch line ends.
  • Page 16: Operation

    4. After installation, the entire sprinkler system must be tested. The test must be conducted to comply with the installation stand- ards. Viking high pressure sprinklers may be hydrostatically tested at a maximum of 300 psi (20.7 bar) for limited periods of time (two hours), for the purpose of acceptance by the Authority Having Jurisdiction.
  • Page 17 Refer to the Authority Having Jurisdiction for minimum replacement requirements. 7. AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.