The Double Action Manual Release Station is a normally-open,
dry contact signal initiating device that requires two actions by
the user. Two contacts are provided.
To initiate the release of a fire suppression agent:
1.
Raise the upper door marked, "LIFT THEN PULL
HANDLE."
2.
Pull the release handle to initiate the release.
Specifications
Ratings
1.5 A @ 30 Vac
1 A @ 28 Vdc
Switch contacts: 2-pole normally-open
Maximum wire size: 12 AWG
Construction: High-impact plastic with steel backplate
Color: Yellow with black on yellow markings
Operating mechanism: double-action pull lever
Shipping weight: 1.0 lb (0.4 kg)
Mounting
North American 2.5 in (64 mm) deep 1-gang box
Standard 4 in square box, 1.5 in (38 mm) deep with 1-
gang cover
Replacement glass rods
US: P/N 276-GLR (pkg 20 rods)
Canada: P/N 276-GLR (pkg 20 rods)
© 2017 United Technologies Corporation
Double Action Manual Release Station
Installation instructions
To mount the release station:
1.
Insert the key into the cover lock and rotate the key to
open the release station (Figure 1).
2.
Pull the cover away from the backplate and let it hang
down.
3.
Make the wiring connections shown in the wiring diagram
(Figure 5).
4.
Verify that all field wiring is free of opens, shorts, and
ground faults.
5.
Mount the backplate to electrical box with the 6-32 x 1/2 in
screws provided.
To install a glass rod:
1.
Install the glass rod in the mounting brackets inside the
front cover of the release station (Figure 2).
2.
Set the toggle switch on the backplate to the normal
position (Figure 3).
3.
Lift the front cover over the backplate.
4.
Rotate the cover lock to secure the front cover to the
backplate (Figure 4).
Electrical box
Front cover
Figure 1: Mounting the release station
WARNINGS: Disconnect power to cabinets before installing or
removing components. Failure to do so may result in serious
injury or loss of life.
This device will not operate without electrical power. As fires
frequently cause power interruption, we suggest you discuss
further safeguards with your local fire protection specialist.
1 / 2
278A-REL
Backplate
6-32 x 1/2 in screw
cover lock
P/N 3100156 • REV 002 • ISS 31JAN17

Advertisement

loading
Need help?

Need help?

Do you have a question about the 278A-REL and is the answer not in the manual?

Questions and answers

Summary of Contents for Edwards 278A-REL

  • Page 1 278A-REL Double Action Manual Release Station Product diagram Installation instructions To mount the release station: Insert the key into the cover lock and rotate the key to open the release station (Figure 1). Pull the cover away from the backplate and let it hang down.
  • Page 2 Mounting brackets Front cover (rear view) Glass rod Figure 2: Glass rod installation Figure 3: Toggle switch in normal position Figure 4: Mounted releasing station Wiring diagram See the appropriate module or panel installation sheet for wiring specifications From releasing panel, module, or device To next device or end -of-line resistor Second circuit may be connected or left open Release Station (rear view)