EDW ARDS
Figure 1. Catalog Series 58-N5-100WH Signal
Description
The Adaptabeacon Catalog Series 58-N5-100WH signal is a UL
Listed, general purpose visual signaling appliance. The signal
is supplied in a UL Listed NEMA 4X enclosure. This signal is
suitable for installation in the hazardous locations outlined be-
low:
Class
Division
Group
I
2
A,B,C,D
II
2
F,G
III
1 and 2
The 58-N5-100WH contains a 100 watt halogen rotating bea-
con which is motor driven at 75 rpm. The signal operates on
120V AC, 50/60 Hz at 1.0 amp.
The 58-N5-100WH signal is suitable for indoor or outdoor
(weatherproof) installation and utilizes a standard base that al-
lows for direct surface mounting or mounting on 3/4" (19mm)
NPT conduit. For outdoor installation, the signal must be con-
duit mounted.
Installation
WARNINGS
To reduce the risk of ignition of hazar dous atmo-
spheres or risk of electrical shock, keep assembly
tightly closed when circuits are energized. Discon-
nect power before disassembling enclosure or
removing or replacing lamp.
To prevent leakage and a potential shoc k hazard,
use care when disassembling the signal to pre vent
tearing the gasket.
Installation Instructions for Catalog Series
58-N5-100WH AdaptaBeacon
Operating Temp. Code
T1 (450ºC, 842ºF)
T6 (85ºC, 185ºF)
T6 (85ºC, 185ºF)
Install in accordance with the latest edition of the National Elec-
trical Code and local regulations.
1. Unfasten and remove the clamp ring. Lift off the dome.
2. Remove the three screws in the rotating lamp assembly
mounting plate, lift the assembly off the base and pull the
wire leads out of the conduit entrance hole in the base.
3. For indoor, non-hazardous installation, the signal may be
direct surface mounted or mounted on 3/4" (19mm) NPT
conduit. For outdoor (weatherproof) and hazardous location
installation, the signal must be conduit mounted. Install the
signal base using one of the following applicable mounting
procedures.
Direct Surface Mounting (indoor , non-hazardous
location installation onl y)
NOTE: For direct surface mounting, the signal must be
installed with its dome f acing either directly up or
down.
•
Remove the three mounting screw knock-outs from the bottom
of the signal base.
•
Route the field wiring from the 120V AC power source
through the conduit entrance hole in the base.
•
Fasten the base to the surface by installing three #10 wood
screws (not supplied) or other suitable hardware through the
knock-out holes in the base. Proceed to step 4 for wiring
connections.
Conduit Mounting (hazar dous location, indoor or
outdoor installation)
WARNING
To prevent leakage and a potential shoc k hazard,
when mounting outdoors the signal m ust be
installed with the lens or dome facing directl y up.
•
Route the field wiring from the 120V AC power source
through the conduit entrance hole in the base.
•
Install the base on the conduit (not supplied).
4. Using wire nuts (not supplied), connect the field wiring to
the signal's wire leads. Connect one field wire to a wire lead
from each the motor assembly and the strobe tube. Connect
the other field wire to the other wire lead from each the motor
assembly and the strobe tube.
Connect the ground wire to the ground screw in the base of
the unit.
5. Place the connected wires inside the base of the signal and
reassemble the signal on the base using the three screws
removed in step 2.
Signals
® ® ® ® ®
P-047550-1641 ISSUE 5 © 1998
Need help?
Do you have a question about the AdaptaBeacon 58-N5-100WH Catalog Series and is the answer not in the manual?
Questions and answers