1 - Introduction The GE (General Electric) Digital Energy™ NetPro UPS series is a compact, truly on-line system (VFI, Voltage and Frequency Independent) which incorporates the most advanced power electronics technology to provide exceptional protection for electrical equipment. Each GE Digital Energy UPS is thoroughly tested and conforms within tolerance to the following specifications. (Data are mean values and are subject to change without notice.) Information applies to all models unless otherwise...
BATTERY EXTENSION CardConnect under overload conditions it may not FRONT PANEL INTERFACE MICRO-PROCESSOR CONTROL be able to protect the load. Figure 3 Bypass operation page 3/10 Modifications reserved PRD_NPE_XXX_0K6_1K5_XGB_0502.doc - Feb 05 Product description GE Digital Energy NetPro 600-1500 UPS...
225 x 185 x 430 Shipping dimensions (hxwxd, mm) 320 x 290 x 530 3.4 Weight NetPro model 1000 1500 Weight (kg) 15.5 Shipping weight (kg) page 4/10 Modifications reserved PRD_NPE_XXX_0K6_1K5_XGB_0502.doc - Feb 05 Product description GE Digital Energy NetPro 600-1500 UPS...
EN 50091-2; EN 50081-1 + EN 50082-1; IEC 801-5: 6kV Note: The NetPro UPS is intended for use in normal domestic and office situations (see Safety: EN 50091-1-1) page 5/10 Modifications reserved PRD_NPE_XXX_0K6_1K5_XGB_0502.doc - Feb 05 Product description GE Digital Energy NetPro 600-1500 UPS...
125% of TCB value: for 200 seconds 200% of TCB value: for 10 seconds 300% of TCB value: for 4 seconds page 6/10 Modifications reserved PRD_NPE_XXX_0K6_1K5_XGB_0502.doc - Feb 05 Product description GE Digital Energy NetPro 600-1500 UPS...
The function is default activated (front selectable) to avoid accidentally switching on during transport. page 7/10 Modifications reserved PRD_NPE_XXX_0K6_1K5_XGB_0502.doc - Feb 05 Product description GE Digital Energy NetPro 600-1500 UPS...
Interface kits (cables and/or software) are available for operating systems supporting JAVA and most commonly used network operating systems, including Novell, UNIX, VMS, Windows, IBM AS/400, IBM OS/2, LINUX. For specific information on GE Digital Energy's connectivity products please contact your local dealer or Internet: www.gedigitalenergy.com.
Interface kits (cables and/or software) are available for operating systems supporting JAVA and most commonly used network operating systems, including Novell, UNIX, VMS, Windows, IBM AS/400, IBM OS/2, LINUX. Please contact your dealer for specific information. page 9/10 Modifications reserved PRD_NPE_XXX_0K6_1K5_XGB_0502.doc - Feb 05 Product description GE Digital Energy NetPro 600-1500 UPS...
-20 and +30°C: every 3 months, if the storage temperature is within -20 and +45°C: every month. page 10/10 Modifications reserved PRD_NPE_XXX_0K6_1K5_XGB_0502.doc - Feb 05 Product description GE Digital Energy NetPro 600-1500 UPS...
Page 12
A product by: GE Digital Energy General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 51 44 E gedeinfo@ge.com www.gedigitalenergy.com...