Installation; Standard Connections - Omron V1000 Product Information

Hide thumbs Also See for V1000:
Table of Contents

Advertisement

Installation

Standard connections

For 1-phase
power supply use
R/L1 and S/L2
Fuses
L1
Power
L2
Supply
L3
Main
Switch
Multi-function
digital inputs
(default setting)
Multi- function pulse / analog inputs
(default: frequency reference)
Safe Disable
inputs
V1000
DC reactor
(option)
Link
+2
R/L1
S/L2
Filter
T/L3
S1
Forward/Stop
Reverse/Stop
S2
External Fault
S3
S4
Fault Reset
Multi-speed 1
S5
Multi-speed 2
S6
DIP
switch S3
SC
Shielded ground
terminal
Pulse Input
RP
(max. 32kHz)
Analog input power supply
+V
+10.5 VDC, max. 20 mA
2 kΩ
A1
Multi-function analog input 1
0 to 10 V (20 k Ω )
A2
Multi-function analog input 2
0 to 10 V (20 k Ω ) or
AC
0/4 to 20 mA (250 Ω )
H2
H1
HC
Symbols:
Use twisted pair cables
Use shielded twisted pair cables
Braking
Thermal
resistor
relay
(opt)
+1
B1
B2
U/T1
V1000
V/T2
W/T3
Ground
+24 V 8 mA
MA
MB
Fault
24 V
MC
SINK
SOURCE
P1
0 V
P2
PC
MP
Pulse train output
(max. 32 kHz)
(Output frequency)
AM
AC
Terminal resistance
(120 Ω , 1/2 W)
R+
R−
S+
S−
IG
Indicates a main circuit terminal
Indicates a control circuit terminal.
U
V
M
W
Shielded
Cable
Multi-function relay output
250 Vac / 30 VDC (10 mA to 1A)
(default setting)
During run
Multi-function photo-
coupler output
48 VDC, max. 50 mA
Frequency agree
(default setting)
Photocoupler
common
Monitor outputs
(default setting)
Analog output
0 to +10 VDC (2mA)
(Output frequency)
Memobus comm.
RS-485/422
max. 115 kBps