Download Print this page

Omron NS10-TV Series Operation Manual page 21

Programmable terminals , host connection manual: host link
Hide thumbs Also See for NS10-TV Series:

Advertisement

C200HX/HG/HE(-Z)E: Board Port B Connection
Word
Writing Value
DM6550
DM6551
DM6553
CPM1 Connection
Word
Writing Value
DM6650
DM6651
DM6653
Connecting to a CPM2C
The CPM2C PLCs do not have the same kind of port connectors found on CS-series PLCs.
The CPM2C's communications port handles both RS-232C and peripheral port connections
which are divided internally. Therefore, when using the CPM2C, it is necessary to select
RS-232C or peripheral port connections, according to the kind of cable and port (on the
cable) used, as shown in the following table. Refer to the CPM2C Operation Manual for more
details.
Port connecting to PT
RS-232C port (D-Sub 9-pin) of CPM2C-CN111
Peripheral port of CPM2C-CN111
RS-232C port (D-Sub 9-pin) of CS1W-CN118
Peripheral port of CS1W-CN114
Peripheral port
RS-232C port
(D-Sub 9-pin, female)
Setting the DIP Switches of a C200HX/HG/HE(-Z)E, CQM1 or CQM1H
When using a C200HX/HG/HE(-Z)E, CQM1, or CQM1H the DIP switches on the front panel
must be set as shown below in order to make the settings in the PLC Setup area (data
memory) effective.
0001
Host link mode, no CTS control, communications conditions
set by the contents of DM
0303
Data length 7 bits, 2 stop bits, even parity, communications
speed: 9600 bps
0304
Data length 7 bits, 2 stop bits, even parity, communications
speed: 19200 bps
0000
Unit # 00
0001
Host link mode, communications conditions set by the
contents of DM area
0303
Data length 7 bits, 2 stop bits, even parity, communications
speed: 9600 bps
0304
Data length 7 bits, 2 stop bits, even parity, communications
speed: 19200 bps
0000
Unit # 00
RS-232C port
(D-Sub 9-pin, female)
16
Settings
Settings
PLC Setup
Built-in RS-232C port settings
Peripheral port settings
Built-in RS-232C port settings
Peripheral port settings
Peripheral port