Omron G3ZA Manual page 12

Multi-channel power controller g3za series
Hide thumbs Also See for G3ZA:
Table of Contents

Advertisement

Specifications
■ Certified Standards
UL508, CSA22.2 No. 14, and EN60950-1
■ Ratings
Input (at an Ambient Temperature of 25 C)
Rated voltage
Operating Voltage range
5 to 24 VDC
4 to 30 VDC
Note: The G3PA uses the input current as a constant current (at an ambient temperature of 25 C).
Output
Model
Rated load voltage
G3PA-210B(L)-VD
24 to 240 VAC (50/60 Hz)
G3PA-220B(L)-VD
G3PA-240B(L)-VD
G3PA-260B(L)-VD
Note: The load current depends on the ambient temperature.
Refer to Engineering Data for further details.
■ Characteristics
Item
Operate time
1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
Output ON voltage drop 1.6 V (RMS) max.
Leakage current
5 mA max. (at 100 VAC)
10 mA max. (at 200 VAC)
Insulation resistance
100 M
Dielectric strength
4,000 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.375–mm single amplitude (mounted to DIN rail)
Shock resistance
Destruction: 300 m/s
Ambient operating
Operating: –30 C to 80 C (with no icing or condensation)
temperature
Storage:
Certified standards
UL508, CSA C22.2 (No.14, No.950), EN60950 File No. 5915ÜG
Ambient operating
Operating: 45% to 85%
humidity
Weight
Approx. 260 g
12
Solid State Relays
Input current impedance
20 mA max.
Load voltage range
19 to 264 VAC (50/60 Hz)
G3PA-210BL-VD
G3PA-220BL-VD
min. (at 500 VDC)
2
(mounted to DIN rail)
–30 C to 100 C (with no icing or condensation)
Approx. 340 g
G3PA
(See note.)
Must operate voltage
4 VDC max.
Applicable load
Load current (See note.)
0.1 to 10 A (at 40°C)
0.1 to 20 A (at 40°C)
0.5 to 40 A (at 40°C)
0.5 to 60 A (at 40°C)
G3PA-240BL-VD
10 mA max. (at 100 VAC)
20 mA max. (at 200 VAC)
Approx. 460 g
Voltage level
Must release voltage
1 VDC min.
Inrush current
150 A (60 Hz, 1 cycle)
220 A (60 Hz, 1 cycle)
440 A (60 Hz, 1 cycle)
440 A (60 Hz, 1 cycle)
G3PA-260BL-VD
Approx. 900 g