Omron CIMR-J7AZ - QUICK Manual page 25

Compact general purpose inverter 200v class 3-phase 0.1 to 4.0kw; 200v class single-phase 0.1 to 1.5kw; 400v class 3-phase 0.37 to 4.0kw
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Multi-function Inputs
*1
Value
Function
8
Multi-step speed reference 3
10
Inching Command
12
External base block (NO)
13
External Base block (NC)
17
Local/Remote selection
*1 Refer to user's manual for full set value
Example of Parameter Settings
Key
Indicator
Sequence
In approximately
1s.
Note 1: To cancel the set value, press the Mode Key instead, The parameter number will be
displayed.
2: There are parameters that cannot be changed while the Inverter is in operation. Refer to the
list of parameters. When attempting to change such parameters, the data display will not
change by pressing the Increment or Decrement Key.
Cancels
Set Data
In approximately 1s.
Display example
Multi-function Outputs
*1
Value
Function
15
Undervoltage in progress
Analogue Output Functionsts
*1
Value
Function
0
Otput frequency
1
Output current
Explanation
Power On
Press the Mode Key repeatedly until the PRGM indicator
is lit.
Use the Increment or Decrement Key to set the parameter
number.
Press the Enter Key. The data of the selected parameter
number will be displayed.
Use the Increment or Decrement Key to set the data.
At that time, the display will flash.
Press the Enter Key so that the set value will be entered and the
data display will be lit (see note 1)
The parameter number will be displayed.