1. DESCRIPTION
Viking Standard Response Upright Sprinkler VK580 is a thermosensitive glass bulb
spray sprinkler available in various temperature ratings to meet design requirements.
With a 16.8 nominal K-Factor, the sprinkler provides greater flows at lower pressures
than sprinklers with smaller K-Factors. This feature allows reduced pipe sizing for
hydraulically calculated sprinkler systems, and provides the higher densities required
to allow an increase in the hazard classification of an occupancy. Viking Standard
Response Sprinkler VK580 was subjected to full-scale high piled storage fire testing
and is cULus Listed and FM Approved for use in protecting high-piled storage.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Class 2024
NOTE: This sprinkler is NOT Listed or Approved as a Specific Application
Sprinkler.
Refer to Approval Chart 1 and Design Criteria for cULus requirements, and refer to Approval Chart 2 and Design Criteria
for FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 2004.
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).
Thread size: 3/4" (20 mm) NPT
Nominal K-Factor: 16.8 U.S. (242 metric
* Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown
by 10.0.
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-7/16" (62 mm)
Material Standards:
Sprinkler Frame: Brass UNS-C84400
Deflector: Phosphor Bronze UNS-C51000
Bulb: Glass, nominal 5 mm diameter
Pip Cap: Brass UNS-C31600 or Brass UNS-C31400
Compression Screw: Brass UNS-C36000
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Ordering Information: (Also refer to the current Viking price list.)
Order Standard Response Upright Sprinkler VK580 by adding the appropriate suffix for the sprinkler temperature rating to the
sprinkler base part number.
Finish Suffix: Brass = A
Temperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, and 286 °F (141 °C) = G
For example, sprinkler VK580 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12739AB.
Available Finishes And Temperature Ratings:
Refer to Table 1.
Accessories: (Also refer to the Viking website.)
Sprinkler Wrench:
Part No. 07297W/B (available since 1991)
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)
Form No. F_041904
18.10.11
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
)
*
Rev 18.3.P65
STANDARD RESPONSE
UPRIGHT SPRINKLER
VK580 (K16.8)
(STORAGE-DENSITY/AREA)
NOTE: As of May 2018 all logos have been removed
from the wrench boss.
Replaces Form No. F_041904 Rev 18.2
(Added P65 Warning.)
Page 1 of 4

Advertisement

loading
Need help?

Need help?

Do you have a question about the VK580 and is the answer not in the manual?

Questions and answers

Summary of Contents for Viking VK580

  • Page 1 Temperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, and 286 °F (141 °C) = G For example, sprinkler VK580 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12739AB.
  • Page 2: Technical Data

    Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Model VK580 Sprinkler is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
  • Page 3 (Also refer to Approval Chart 1 above.) cULus Listing Requirements: Standard Response Upright Sprinkler VK580 is cULus Listed for installation in accordance with the latest edition of NFPA 13 for standard upright spray sprinklers: Designed for use in hazard occupancies up to and including Extra-Hazard Group II for hydraulically calculated wet or dry systems.
  • Page 4 Sprinkler VK580 is FM Approved as a standard response Non-storage upright sprinkler as indicated in the FM Approval Guide. • Sprinkler VK580 is also FM Approved as a standard response Storage upright sprinkler as indicated in the FM Approval Guide. •...
  • Page 5 Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance instructions. For additional product and system information Viking data pages and installation instructions are available on the Viking Web site at www.vikinggroupinc.com.
  • Page 6 * Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com.
  • Page 7 • while ceiling finish work is being completed. Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. NOTE: The protective cap is • temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed.
  • Page 8 Take care not to crack the wax coating on the units. • For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after •...
  • Page 9: Listings And Approvals

    1. DESCRIPTION Viking fire sprinklers consist of a threaded frame with a specific waterway or orifice size and a deflector for distributing water in a specified pattern. A closed or sealed sprinkler refers to a complete assembly, including the thermosensitive operating element. An open sprinkler does not use an operating element and is open at all times.
  • Page 10 TECHNICAL DATA SPRINKLER OVERVIEW The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com VERTICAL SIDEWALL (VSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The deflector provides a water spray pattern outward in a quarter-spherical pattern and can be installed in the upright or pendent position with the flow arrow in the direction of discharge.
  • Page 11 Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
  • Page 12: Warranty Terms And Conditions

    For more information, go to www.P65Warnings.ca.gov 2. WARRANTY TERMS AND CONDITIONS For details of warranty, refer to Viking’s current list price schedule at www.vikinggroupinc.com or contact Viking directly. New Bulletin Form No. F_111218 18.11.15...

This manual is also suitable for:

K16.8