AKO-D14545 / AKO-D14545-C
5-stage compressor racks + 2 converter outputs
User Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AKO-D14545 and is the answer not in the manual?

Questions and answers

Summary of Contents for AKO AKO-D14545

  • Page 1 D145H4502 Ed. 01 AKO-D14545 / AKO-D14545-C 5-stage compressor racks + 2 converter outputs User Manual...
  • Page 2: Table Of Contents

    Only qualified personnel should install or perform technical assistance on this product. This product is designed to be used in the applications described in the product manual. AKO Electromecánica gives no guarantee of its ope- ration in any use not foreseen in the manual, and is not responsible for any damage resulting from improper use, configuration, installation or commissioning.
  • Page 3: Precautions

    MODELS POWER SUPPLY PROBES (2+1) ANALOGUE OUTPUTS RELAYS COMMUNICATION INPUTS 0.5 -4.5 V / 2 x 0-10 V / AKO-D14545 90-240 V 4-20 mA / NTC / Up to 6 4-20 mA AKO-D14545-C + 1 x NTC (inverter controls) Description...
  • Page 4: Display Messages

    D145H4502 Ed. 01 Display messages Flashing 0: Access code (Password) request PRES TEMP You must enter the access code configured on L5 to execute the requested function (See page 22). Probe 1, 2 or 3 faulty PRES PRES PRES TEMP TEMP TEMP (open circuit, crossover or temperature outside the probe limits;...
  • Page 5: Initial Setup

    D145H4502 Ed. 01 Initial setup The unit has a wizard that configures the unit’s parameters and assigns the input and output functions according to the installation type chosen. When connecting the power supply for the first time, the Configuration Wizard will start, displaying the message INI on screen.
  • Page 6: Legend

    D145H4502 Ed. 01 The second group specifies the function assigned to each relay depending on the INI option selected. Relays Relays R1 to R5 OUTPUTS Function assigned to each relay depending on the INI option selected* The third group specifies the function assigned to each digital input depending on the INI option selected. Inputs Inputs I1 to I6 INPUTS...
  • Page 7: Wizard" Table

    D145H4502 Ed. 01 “WIZARD” table OUTPUTS INPUTS R1 R2 R3 R4 R5 T-C1 L.P. H.P. C1 C1a - T-C1 L.P. H.P. C1 C1a C1b - T-C1 L.P. H.P. C1 C1a C1b C1c AL T-C1 L.P. H.P. C1 C2 T-C1 T-C2 L.P.
  • Page 8 D145H4502 Ed. 01 OUTPUTS INPUTS R1 R2 R3 R4 R5 T-V1 L.P. H.P. V1 V2 T-V1 T-V2 L.P. H.P. V1 V2 V3 T-V1 T-V2 T-V3 L.P. H.P. V1 V2 V3 V4 AL T-V1 T-V2 T-V3 T-V4 L.P. H.P. V1 V2 V3 V4 V5 T-V1 T-V2 T-V3...
  • Page 9: Wiring

    19 20 21 22 23 24 25 26 27 28 90-240 V~ 15 16 17 19 2 15 16 17 19 2 50/60 Hz AKO-D14545 AKO-D14545-C 9 10 0.5 - 4.5 V Ratiometric R1 R3 15 16 17 19 2...
  • Page 10: Compressors Control

    D145H4502 Ed. 01 Compressors control Proportional mode WITHOUT FREQUENCY CONVERTER The controller activates (red line) or deactivates (green line) the different stages/compressors available in a linear manner depending on the reading obtained in probe 1 until the Set Point (E01) is reached again, as shown in the following figure Direct Inverse...
  • Page 11: Neutral Zone Mode

    D145H4502 Ed. 01 Neutral zone mode WITHOUT FREQUENCY CONVERTER In this mode, a neutral zone is defined, whose lower limit is the Set Point minus the bandwidth, and whose upper limit is the Set Point plus the bandwidth. While the reading of probe 1 remains in that zone, no stages or compressors are connected or disconnected.
  • Page 12: Pump Down

    D145H4502 Ed. 01 WITH FREQUENCY CONVERTER Operation is the same as in the previous point, but modulating the power of compressor 1 with the converter while it remains in the neutral zone using a PID control. Near the upper limit, the compressor operates at its maximum capacity, and if said limit is exceeded, more stages/ compressors are added, in accordance with the interval defined in t02, until returning to the neutral zone.
  • Page 13: Fan Control

    D145H4502 Ed. 01 Fan control Proportional mode WITHOUT FREQUENCY CONVERTER The controller activates (red line) or deactivates (green line) the different fans available in a linear manner depending on the reading obtained in probe 2 until the Set Point (E01) is reached again, as shown in the following figure. The delays t05 to t08 must be accounted for.
  • Page 14: Neutral Zone Mode

    D145H4502 Ed. 01 Neutral zone mode WITHOUT FREQUENCY CONVERTER In this mode, a neutral zone is defined, whose lower limit is the Set Point minus the bandwidth, and whose upper limit is the Set Point plus the bandwidth. While the reading of probe 2 remains in that zone, no fans are connected or disconnected.
  • Page 15: Floating Condensation

    D145H4502 Ed. 01 WITH FREQUENCY CONVERTER Operation is the same as in the previous point, but modulating the power of the fans with the converter while it remains in the neutral zone using a PID control. Near the upper limit, the fans operate at their maximum capacity, and if said limit is exceeded, the capacity is kept at its maximum until returning to the neutral zone.
  • Page 16: Alarms

    D145H4502 Ed. 01 Alarms IMPORTANT: The alarms that cause compressors and fans to stop will do so in a sequential manner, with a delay of 5 seconds between stops. LOW AND HIGH PRESSURE ALARM DUE TO DIGITAL INPUT PRES TEMP When the digital input I5 or I6 is activated, the message HPA (High) or LPA (Low) is shown on screen, the alarm relay is activated (if available) and the compressors are stopped.
  • Page 17: Remote Disconnection

    Connectivity The AKO-D14545-C model has a port for RS485 (MODBUS) data connection, which enables remote management via the AKO XaviP Edge gateway and the akonet.cloud platform. A different address must be assigned to each unit on the same network. This address is defined by parameter b20.
  • Page 18: Parameter Setup

    D145H4502 Ed. 01 Parameter setup Through the programming menu users can set different parameters to adjust the operation of the controller to the needs of their installation. Programming Menu It allows changing the unit’s operating parameters. To access the programming menu, press the SET button for 10 seconds, or until the “PRG” appears on the screen. IMPORTANT: If the password function has been configured, the system will demand entering the password programmed in L5.
  • Page 19: Parameters

    D145H4502 Ed. 01 Parameters The unit’s operation parameters are organized into groups or families according to their function. The Def. column shows factory-set default parameters. The pressure values featured on the table are expressed in bar and those for temperature in ºC. If the wizard meanwhile selects another set of units (parameter C09), the unit will make the conversion automatically.
  • Page 20 D145H4502 Ed. 01 Level 1.- CONDENSATION CONFIGURATION PRES TEMP Description Units Min. Def. Max. F01 Condensation pressure / temperature set point F02 Condensation set point upper limit (It cannot be set above this limit) F03 Condensation set point lower limit (It cannot be set below this limit) -0.7 -0.7 F02 Fan rotation type: 0=Balancing, depending on the operation time...
  • Page 21 D145H4502 Ed. 01 Level 1.- DIGITAL INPUT CONFIGURATION PRES TEMP Description Units Min. Def. Max. Polarity digital input 1 (thermal stage 1): 0=Activates on closing contact; 1=Activates on opening contact Polarity digital input 2 (thermal stage 2): 0=Activates on closing contact; 1=Activates on opening contact Polarity digital input 3 (thermal stage 3): 0=Activates on closing contact;...
  • Page 22 D145H4502 Ed. 01 Level 1.- CONFIGURATION OF PROTECTIONS AND ALARMS PRES TEMP Description Units Min. Def. Max. A01 Number of active compressor stages with error in probe 1 Without inverter A02 Number of active fans or inverter % with error in probe 2 With inverter 100% 100% A03 Low pressure alarm in probe 1...
  • Page 23: Limits And Default Values Of The Pressure And Temperature Parameters According To Units

    D145H4502 Ed. 01 Limits and default values of the pressure and temperature parameters accor- ding to units. The following table shows the default values and the limits of the pressure and temperature parameters according to the display units defined by parameter C09 during quick start (See page 5). MINIMUM DEFAULT value MAXIMUM...
  • Page 24: Technical Specifications

    Relays R1 to R4 ....................(EN60730-1: 5(4) A 250 V~ SPST) Relay R5 ......................(EN60730-1: 5(4) A 250 V~ SPDT) No. of relay operations ..................EN60730-1: 100.000 operations Types of probes ..........................NTC AKO-149xx ................................4-20 mA ..............................0-5 V ratiometric Measuring range NTC ................-50,0 ºC a +99,9 ºC (-58,0 ºF a 211 ºF) 4-20 mA / 0.5 - 4.5 V ....................-60 to 999...
  • Page 25: Dimensions

    D145H4502 Ed. 01 Dimensions PRES TEMP 7,1 mm 60,4 mm 79 mm Mounting 7 1 m m...
  • Page 26 D145H4502 Ed. 01...
  • Page 27 D145H4502 Ed. 01...
  • Page 28 AKO ELECTROMECÁNICA , S.A.L. Avda. Roquetes, 30-38 08812 • Sant Pere de Ribes. Barcelona • Spain www.ako.com We reserve the right to supply materials that might vary slightly to those described in our Technical Sheets. Updated information is available on our website.