Refrigerant Line Connections; Leak Testing (Nitrogen Or Nitrogen-Traced) - Daikin DX14XA090 Installation Instructions Manual

Table of Contents

Advertisement

suspending refrigerant tubing from joists and studs with
rigid wire or straps that would come in contact with the
tubing. Use an insulated or suspension type hanger. Keep
both lines separate and always insulate the suction line.
REFRIGERANT LINE LENGTH (ft)
Cond Unit
0-24
(Tons)
Suct
7 1/2
1 1/8
10
1 3/8
* Full rating line size
** Lines greater than 74 feet in length or vertical elevation changes more
than 50 feet refer to TP-108* Long Line Set Application Guideline or
contact your local distributor for assistance.
Insulation is necessary to prevent condensation from
forming and dropping from the suction line. Armflex (or
satisfactory equivalent) with 3/8" min. wall thickness is
recommended. In severe conditions (hot, high humidity
areas) 1/2" insulation may be required. Insulation must be
installed in a manner which protects tubing from damage
and contamination.
Where possible, drain as much residual compressor oil
from existing systems, lines, and traps; pay close attention
to low areas where oil may collect. NOTE: If changing
refrigerant types, ensure the indoor coil and metering
device is compatible with the type of refrigerant being used;
otherwise, the indoor coil must be replaced. To facilitate oil
return to the compressor, a horizontal suction line should
be pitched (1/2" per 10' toward the condensing unit.
25-49*
50-74**
Line Diameter (In. OD)
Liq
Suct
Liq
Suct
5/8
1 3/8
5/8
1 3/8
5/8
1 5/8
5/8
1 5/8
Filter Drier and Sight Glass
A liquid line filter drier is factory installed. Field-install the
supplied sight glass/moisture indicator on the liquid line as
close as practical to the service valve.
Burying Refrigerant Lines
If burying refrigerant lines can not be avoided, use the
following checklist.
1. Insulate liquid and suction lines separately.
Liq
2. Enclose all underground portions of the refrigerant
5/8
lines in waterproof material (conduit or pipe) sealing
5/8
the ends where tubing enters/exits the enclosure.
3. If the lines must pass under or through a concrete
slab, ensure lines are adequately protected and
sealed.

Refrigerant Line Connections

IMPORTANT: To avoid overheating the service valve, TXV
valve, or filter drier while brazing, wrap the component
with a wet rag, or use a thermal heat trap compound as
recommended by the compound manufacturer. Use a
brazing alloy of 2% minimum silver content. Do not use
flux.
1. The ends of the refrigerant lines must be cut square,
deburred, cleaned, and be round and free from nicks
or dents. Any other condition increases the chance of
a refrigerant leak.
2. This unit is factory shipped with a holding charge.
"Sweep" the refrigerant line with nitrogen or inert gas
during brazing to prevent the formation of copper-
oxide inside the refrigerant lines.
3. After brazing, quench the joints with water or a wet
cloth to prevent overheating of the service valve.
4. Ensure the filter drier paint finish is intact after
brazing. If the paint of the steel filter drier has
been burned or chipped, repaint or treat with a rust
preventative. This is especially important on suction
line filter driers which are continually wet when the
unit is operating.
NOTE: Be careful not to kink or dent refrigerant
lines. Kinked or dented lines will cause poor
performance or compressor damage.
Do NOT make final refrigerant line connection until plugs
are removed from refrigerant tubing.

Leak Testing (Nitrogen or Nitrogen-Traced)

To avoid the risk of fire or explosion, never use oxygen,
high pressure air or flammable gases for leak testing of a
refrigeration system.
4